Ten Cooling Solutions to Support High-density Servers
Schneider Electric · Peter Hannaford
Schneider Electric WP 42 ranks ten measures, from cheapest to most disruptive, for coping with high-density racks in rooms designed for low average density.
On this page
Overview
The early measures are operational hygiene: a cooling health check, maintenance, blanking panels and cable management, clearing underfloor blockages and sealing cut-outs, spreading high-density racks, hot/cold aisle layout, aligning CRACs with hot aisles and placing vents correctly. The last two are fan-assisted airflow devices and a change of air-distribution architecture to containment, row-based cooling or rack/row containment pods. The Uptime Institute found operational deficiencies (dirty coils, undercharged DX, reversed piping, unused economizer modes) in more than 50% of the data centres it visited.
A traditional raised-floor CRAC room without air containment is unlikely to deliver more than 3-6 kW to any rack regardless of CRAC count or floor depth; flooded-aisle hard-floor rooms deliver even less. The example room has a 5,000 ft2 raised floor, 30 in (762 mm) depth, 560 kW UPS load, 200 racks and a 2.8 kW average; cooling is unlikely to exceed 3 kW per rack. Five 10 kW racks grouped in one row cannot be supported, but spreading them lets them borrow neighbours' capacity.
With raised-floor cooling, CRAC units should be aligned with hot aisles (the return path) rather than cold aisles, since CFD shows hot air crossing over racks otherwise. Fan-assisted devices (ADU/ARU, active tiles) can raise rack cooling to between 3 kW and 8 kW and should be UPS-powered to avoid thermal overload before the generator starts.
When average rack density exceeds 3 kW in an uncontained flooded supply/flooded return system, the air-distribution architecture must change; row-based cooling suits smaller data centres of 200 kW or less. For sustained densities above 6 kW per rack over an area, going directly to solutions 9 or 10 may be appropriate; hot-aisle containment pods and rack air containment systems support up to 60 kW per rack.
Key points
- An uncontained raised-floor CRAC room is unlikely to deliver more than 3-6 kW to any rack regardless of CRAC count or floor depth; flooded hard-floor rooms deliver less.
- For sustained densities above 6 kW per rack over an area, going directly to solution 9 or 10 may be appropriate.
- The Uptime Institute found operational deficiencies in more than 50% of data centres visited.
- Example: 5,000 ft2, 762 mm floor, 560 kW UPS load, 200 racks, 2.8 kW average; cooling unlikely to exceed 3 kW per rack; five 10 kW racks in one row cannot be supported, but spread out they borrow neighbours' capacity.
- CRACs should align with hot aisles for the return path; otherwise hot air crosses over racks.
- Fan-assisted devices raise rack cooling to 3-8 kW and should be UPS-powered.
- Above 3 kW average in an uncontained flooded system the architecture must change; row-based cooling suits 200 kW or less.
- Hot-aisle containment pods and rack air containment systems support up to 60 kW per rack.
Using it in design
- Set density warnings by air-distribution type: uncontained flooded return above 3 kW/rack average, uncontained raised floor above 3-6 kW/rack, fan-assisted retrofit ceiling 8 kW/rack, HACS/RACS pods up to 60 kW/rack.
- Check layout: all racks in a row face the same way, rows alternate hot and cold, perimeter CRAC/CRAH sit at hot-aisle ends, perforated tiles only in cold aisles.
- Flag clustered high-density racks that exceed local tile or cooler capacity even when the room average is fine.
- Put fan-assist devices and row-cooler fans on UPS-backed circuits in high-density zones, and recommend row-based cooling by default for rooms of 200 kW or less with high-density loads.
Who should read it
Designers and operators adding high-density racks to rooms built for low average density.
Related standards
- ASHRAE TC 9.9 Thermal Guidelines
Publication details
- Authors
- Peter Hannaford
- Publisher
- Schneider Electric
- Year
- 2015
- Document number
- WP 42
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Citation
Peter Hannaford (2015). Ten Cooling Solutions to Support High-density Servers. Schneider Electric. WP 42. https://download.schneider-electric.com/files?p_Doc_Ref=SPD_TDOY-5U362W_EN
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.