The Use of Ceiling-Ducted Air Containment in Data Centers
Schneider Electric · Jim VanGilder, Simon Zhang et al.
This 2017 Schneider Electric white paper examines hot-air containment that ducts IT exhaust into a drop-ceiling return plenum: passive individually ducted racks (chimneys), fan-assisted ducted racks and ducted hot-aisle containment (HACS).
On this page
Overview
Using a flow-network model coupled to CFD, the analysis shows that performance is governed mainly by the vacuum the ceiling plenum holds relative to the room, which depends on cooling-to-IT airflow ratio, ceiling leakiness and plenum depth, more than on duct construction. Assumptions are IT airflow of 125 cfm/kW (212 m3/h/kW), racks filled to 30U, HACS clusters of 20 racks and 8 in (200 mm) server-to-rear-door clearance for ducted racks; 'Bad' means at least 10% recirculation.
At a plenum vacuum of 0.03 inH2O (7.5 Pa), individually ducted racks are limited to about 8 kW/rack while ducted HACS supports up to about 16 kW/rack. Vacuum above 0.03 inH2O needs deliberate sealing effort, and above about 0.06 inH2O (15 Pa) typical ceiling tiles begin to lift, capping achievable vacuum. A cooling-to-IT airflow ratio of 1 is generally acceptable for ducted HACS, but ducted racks may need 1.2 or higher. Rack-to-rack uniformity for HACS is good with plenums deeper than 18-24 in (0.46-0.61 m), even at 12 kW racks.
Active ducted racks allow up to about 12 kW/rack but add about 10 in (250 mm) to rack depth. Capital cost per rack is $500-700 for passive ducted, $1,800-2,000 for active ducted and $500-1,000 for ducted HACS.
The recommendation is to fix plenum pressure before adding fans. Implementation guidance: plenum at least 18 in (450 mm) deep, and ducted cooling airflow at least 10% above ducted IT airflow, or 20% for passive ducted racks with leaky ceilings.
Key points
- At 0.03 inH2O (7.5 Pa) vacuum, ducted racks reach about 8 kW/rack and ducted HACS about 16 kW/rack.
- Above about 0.06 inH2O (15 Pa), typical ceiling tiles lift and cap the vacuum.
- Cooling-to-IT airflow ratio: 1 for HACS, 1.2 or higher for ducted racks.
- HACS uniformity is good with plenums deeper than 18-24 in (0.46-0.61 m), even at 12 kW racks.
- Active ducted racks reach about 12 kW/rack and add about 10 in (250 mm) of depth.
- Cost per rack: passive $500-700, active $1,800-2,000, ducted HACS $500-1,000.
- Plenum at least 18 in (450 mm); ducted cooling airflow at least 10% above IT (20% for passive racks with leaky ceilings).
Using it in design
- Compare passive and active ducted racks and ducted hot-aisle containment against ceiling-plenum vacuum and density limits. Check the source’s 0.03 inH₂O / 7.5 Pa reference and its warning above 0.06 inH₂O / 15 Pa.
- Raise an error for plenum depth under 18 in (450 mm) in ducted designs, and warn when the cooling/IT airflow ratio is under 1.1 (1.2 for passive chimneys).
- Suggest ducted HACS when a passive chimney rack exceeds about 8 kW.
- For active ducted racks, state that CFD verification is required and add 250 mm to rack depth or row pitch.
Who should read it
Cooling and layout engineers designing ceiling-plenum containment.
Related standards
- ASHRAE TC 9.9 Thermal Guidelines for Data Processing Environments
- EN 50600-2-3
Publication details
- Authors
- Jim VanGilder; Simon Zhang; Paul Lin
- Publisher
- Schneider Electric
- Year
- 2017
- Document number
- WP 182
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Citation
Jim VanGilder; Simon Zhang; Paul Lin (2017). The Use of Ceiling-Ducted Air Containment in Data Centers. Schneider Electric. WP 182. https://download.schneider-electric.com/files?p_Doc_Ref=SPD_VAVR-8Q7K3X_EN
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.