Improving Rack Cooling Performance Using Airflow Management(TM) Blanking Panels
Original title Improving Rack Cooling Performance Using Airflow Management™ Blanking Panels
Schneider Electric · Neil Rasmussen
Schneider Electric WP 44 quantifies how empty U space in racks lets hot exhaust air recirculate to equipment inlets, using a laboratory rack test and field measurements.
On this page
Overview
The laboratory test used thirty 1U server simulators at 150 W each (4.5 kW) in a 42U enclosure with an 11U gap. With blanking panels the hottest server's inlet dropped from 35 C (95 F) to 23 C (73 F), a 12 C (22 F) reduction, while bottom servers stayed unaffected at 21 C (70 F). Field measurements in rooms with mixed density and short rows showed inlet reductions from 2.8 to 8.3 C (5 to 15 F).
Without eliminating recirculation, the only remedy is lowering the bulk supply temperature, which reduces air-conditioner efficiency and increases condensate and humidification needs. With blanking panels the same server inlet temperature is achieved at a higher air-conditioner discharge temperature, which reduces dehumidification and raises efficiency.
The paper discusses why panels are often omitted (misunderstanding, and the effort of screw-in panels) and compares tool-less 1U snap-in panels with screw-in kits for 100 racks with 10U empty each (1000U): snap-in panels save 41.2% of material and 96.7% of labour cost and install about 30 times faster.
A checklist covers other in-rack recirculation paths: blank all unused U; do not use 23 in (584 mm) racks with rails set to 19 in (483 mm); use brush or shield panels for cable pass-through; use fully perforated front and rear doors (no glass); bay racks together.
Key points
- Test: 42U enclosure with an 11U gap, thirty 1U simulators at 150 W each (4.5 kW).
- Blanking panels cut the hottest server inlet from 35 C to 23 C (12 C / 22 F); bottom servers stayed at 21 C.
- Field inlet reductions were 2.8-8.3 C (5-15 F).
- Without stopping recirculation the only fix is a lower supply temperature, which cuts efficiency and raises condensate and humidification needs.
- For 100 racks with 10U empty each (1000U), snap-in 1U panels save 41.2% material and 96.7% labour and install about 30 times faster.
- Checklist: blank all unused U; no 23 in racks with 19 in rails; brush/shield panels at cable pass-throughs; fully perforated doors; bay racks together.
- With panels the same inlet temperature is reached at a higher discharge temperature, reducing dehumidification.
Using it in design
- Add rack selection criteria for door perforation percentage (warn on glass or below the full-perforation spec), rail width versus cabinet width (warn on a 23 in cabinet with 19 in rails and no side seals) and blanking included.
- In the rack elevation editor compute empty U per rack, add 1U blanking panels to the BOM automatically, and warn when open U sits above or below powered equipment.
- Flag gaps between adjacent racks in a row (bay them together or add gap fillers).
- When blanking is not specified, assume up to a 12 C inlet penalty for equipment above open gaps.
Who should read it
Designers and operations teams managing in-rack airflow.
Publication details
- Authors
- Neil Rasmussen
- Publisher
- Schneider Electric
- Year
- 2011
- Document number
- WP 44
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Citation
Neil Rasmussen (2011). Improving Rack Cooling Performance Using Airflow Management™ Blanking Panels. Schneider Electric. WP 44. https://download.schneider-electric.com/files?p_Doc_Ref=SPD_SADE-5TPLKQ_EN
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.