White paperFree to read2011

Improving Rack Cooling Performance Using Airflow Management(TM) Blanking Panels

Original title Improving Rack Cooling Performance Using Airflow Management™ Blanking Panels

Schneider Electric · Neil Rasmussen

Schneider Electric WP 44 quantifies how empty U space in racks lets hot exhaust air recirculate to equipment inlets, using a laboratory rack test and field measurements.

On this page

Overview

The laboratory test used thirty 1U server simulators at 150 W each (4.5 kW) in a 42U enclosure with an 11U gap. With blanking panels the hottest server's inlet dropped from 35 C (95 F) to 23 C (73 F), a 12 C (22 F) reduction, while bottom servers stayed unaffected at 21 C (70 F). Field measurements in rooms with mixed density and short rows showed inlet reductions from 2.8 to 8.3 C (5 to 15 F).

Without eliminating recirculation, the only remedy is lowering the bulk supply temperature, which reduces air-conditioner efficiency and increases condensate and humidification needs. With blanking panels the same server inlet temperature is achieved at a higher air-conditioner discharge temperature, which reduces dehumidification and raises efficiency.

The paper discusses why panels are often omitted (misunderstanding, and the effort of screw-in panels) and compares tool-less 1U snap-in panels with screw-in kits for 100 racks with 10U empty each (1000U): snap-in panels save 41.2% of material and 96.7% of labour cost and install about 30 times faster.

A checklist covers other in-rack recirculation paths: blank all unused U; do not use 23 in (584 mm) racks with rails set to 19 in (483 mm); use brush or shield panels for cable pass-through; use fully perforated front and rear doors (no glass); bay racks together.

Key points

  1. Test: 42U enclosure with an 11U gap, thirty 1U simulators at 150 W each (4.5 kW).
  2. Blanking panels cut the hottest server inlet from 35 C to 23 C (12 C / 22 F); bottom servers stayed at 21 C.
  3. Field inlet reductions were 2.8-8.3 C (5-15 F).
  4. Without stopping recirculation the only fix is a lower supply temperature, which cuts efficiency and raises condensate and humidification needs.
  5. For 100 racks with 10U empty each (1000U), snap-in 1U panels save 41.2% material and 96.7% labour and install about 30 times faster.
  6. Checklist: blank all unused U; no 23 in racks with 19 in rails; brush/shield panels at cable pass-throughs; fully perforated doors; bay racks together.
  7. With panels the same inlet temperature is reached at a higher discharge temperature, reducing dehumidification.

Using it in design

  • Add rack selection criteria for door perforation percentage (warn on glass or below the full-perforation spec), rail width versus cabinet width (warn on a 23 in cabinet with 19 in rails and no side seals) and blanking included.
  • In the rack elevation editor compute empty U per rack, add 1U blanking panels to the BOM automatically, and warn when open U sits above or below powered equipment.
  • Flag gaps between adjacent racks in a row (bay them together or add gap fillers).
  • When blanking is not specified, assume up to a 12 C inlet penalty for equipment above open gaps.

Who should read it

Designers and operations teams managing in-rack airflow.

Publication details

Authors
Neil Rasmussen
Publisher
Schneider Electric
Year
2011
Document number
WP 44
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document

Citation

Neil Rasmussen (2011). Improving Rack Cooling Performance Using Airflow Management™ Blanking Panels. Schneider Electric. WP 44. https://download.schneider-electric.com/files?p_Doc_Ref=SPD_SADE-5TPLKQ_EN

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.