White paperFree to read2019

Liquid Cooling Technologies for Data Centers and Edge Applications

Schneider Electric · Tony Day, Paul Lin et al.

A Schneider Electric white paper that introduces liquid cooling for data centres and edge sites. It compares the five main methods on heat capture, density, retrofit friendliness and serviceability.

On this page

Overview

The paper first explains why liquids move heat far better than air, and that this saves fan energy and enables warm-water heat rejection. Liquid cooling can use water up to 45 C (113 F), which allows compressor-free heat rejection in most climates and reduces evaporative water use. Removing or reducing server fans saves about 4 to 15% of IT energy.

It describes five main methods: two direct-to-chip (DTC) variants (single-phase and two-phase cold plates) and three immersion variants (chassis-based, tub single-phase, tub two-phase). On heat capture, DTC puts about 50 to 80% of IT heat into the liquid and the rest still needs air cooling; in typical servers 70 to 80% of heat comes from CPUs, GPUs and memory, which cold plates target. Immersion removes more than 95% of heat via liquid.

On density, an average above 20 kW per rack is possible with air but difficult; immersion handles 20 kW per rack easily and can exceed 100 kW per rack. The selection advice depends on context: for retrofit sites the paper favours rack-based direct-to-chip or chassis immersion, and for new or harsh-environment sites, immersion. This is an introductory paper: it classifies and compares methods but does not give a detailed sizing method for a specific product. The heat-capture fraction is given with different ranges in later Schneider papers (WP 279: 70 to 80%, WP 133: 60 to 90%), so it should be re-verified for the chosen architecture.

Key points

  1. Direct-to-chip captures about 50 to 80% of IT heat in the liquid; the rest still needs air cooling.
  2. Immersion removes more than 95% of heat via liquid.
  3. Removing or reducing server fans saves about 4 to 15% of IT energy.
  4. Liquid cooling can use water up to 45 C (113 F), enabling compressor-free heat rejection in most climates and less evaporative water use.
  5. In typical servers 70 to 80% of heat comes from CPUs, GPUs and memory, the components cold plates target.
  6. An average rack density above 20 kW is possible with air but difficult; immersion handles 20 kW per rack easily and can exceed 100 kW per rack.
  7. Five main methods: DTC single-phase, DTC two-phase, chassis immersion, tub single-phase, tub two-phase.

Using it in design

  • Compare air cooling, rear-door heat exchangers, single- and two-phase direct-to-chip cooling, chassis immersion and single- and two-phase tank immersion.
  • Specify the liquid heat-capture fraction and calculate residual air cooling as (1 − fraction) × rack kW. Identify the source assumptions: DTC 0.7, range 0.5–0.8; immersion at least 0.95.
  • Apply a default IT-energy credit of 8% (range 4 to 15%) for fan removal in PUE and energy models.
  • Default facility water for liquid loops to 35 to 45 C, which unlocks dry coolers.

Who should read it

Designers and decision makers evaluating liquid cooling for the first time, or choosing between retrofit and new-build methods.

Related standards

  • ASHRAE TC9.9 Liquid Cooling Guidelines (W-classes)
  • OCP Advanced Cooling Solutions

Publication details

Authors
Tony Day; Paul Lin; Robert Bunger
Publisher
Schneider Electric
Year
2019
Document number
WP 265
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document

Citation

Tony Day; Paul Lin; Robert Bunger (2019). Liquid Cooling Technologies for Data Centers and Edge Applications. Schneider Electric. WP 265. https://download.schneider-electric.com/files?p_Doc_Ref=SPD_VAVR-AQKM3N_EN

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.