White paperFree to read2019

Capital Cost Analysis of Immersive Liquid-Cooled vs. Air-Cooled Large Data Centers

Schneider Electric · Robert Bunger, Wendy Torell et al.

A Schneider Electric white paper comparing the capital cost of a 2 MW air-cooled data centre with a chassis-based immersive liquid-cooled design. Capex is roughly equal at equal density and falls with compaction.

On this page

Overview

The paper compares the capex of a 2 MW air-cooled data centre with a chassis-based immersive liquid-cooled design. At equal density, 10 kW per rack, the two cost about the same (reference build cost about $10/W): savings of about $0.91/W from removing chillers and CRAHs offset a liquid-cooling technology premium of about $0.77/W. The sensitivity range for the technology premium is $0.50 to $1.10/W.

Because liquid cooling allows compaction, the paper also models 20 kW and 40 kW per rack. Capex falls by about 10% at 20 kW per rack and about 14% at 40 kW, thanks to less building and white space. Assumptions drive the result: the liquid design uses 40 C/47.75 C facility water supply/return with 25% glycol, against 20/30 C for air. The air-cooled room supplies 24 C with a 14 C deltaT, and core and shell cost $90/ft2 ($969/m2).

On energy, IT fan savings are assumed at 9% of server energy (15 to 20% measured on high-intensity compute), the micro-pump penalty at 3% and rack heat loss to air at 5.5%. 40 C facility water is assumed to give full free cooling. Limits: costs are 2019 dollars and need escalation before use. The authors note the technology was not mature at the time and expect costs to fall. The result applies to chassis-based immersion only and does not transfer directly to other liquid-cooling methods.

Key points

  1. At 10 kW per rack in a 2 MW site, air-cooled and immersion capex are roughly equal (reference about $10/W).
  2. Compaction to 20 kW per rack saves about 10% capex; to 40 kW per rack about 14%.
  3. At 10 kW per rack, chiller/CRAH removal saves about $0.91/W; the liquid-cooling technology premium is about $0.77/W (sensitivity $0.50 to $1.10/W).
  4. Liquid design assumptions: 40 C/47.75 C facility water supply/return with 25% glycol, versus 20/30 C for air.
  5. IT fan savings assumed at 9% of server energy (15 to 20% measured on high-intensity compute), micro-pump penalty 3%, rack heat loss to air 5.5%.
  6. Air-cooled room supply 24 C with 14 C deltaT; core and shell cost $90/ft2 ($969/m2).

Using it in design

  • In CAPEX and TCO comparisons, identify the source’s immersion technology premium of USD 0.77/W and chiller/CRAH saving of USD 0.91/W as study assumptions.
  • Compute compaction savings through smaller building area, and assume residual air heat of 5.5% of IT for immersion.
  • Compare the study’s equal-density and densified layouts separately: liquid cooling has roughly comparable capital cost in the former and lower cost in the latter.
  • Label costs as 2019 USD and require escalation.

Who should read it

Finance, planning and design teams comparing the capital cost of liquid and air cooling.

Related standards

  • ASHRAE TC9.9 Liquid Cooling Guidelines
  • OCP Advanced Cooling Solutions

Publication details

Authors
Robert Bunger; Wendy Torell; Victor Avelar
Publisher
Schneider Electric
Year
2019
Document number
WP 282
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document

Citation

Robert Bunger; Wendy Torell; Victor Avelar (2019). Capital Cost Analysis of Immersive Liquid-Cooled vs. Air-Cooled Large Data Centers. Schneider Electric. WP 282. https://download.schneider-electric.com/files?p_Doc_Ref=SPD_WP282_EN

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.