How Microgrids for Data Centers Increase Resilience, Optimize Costs, and Improve Sustainability
Schneider Electric · Carsten Baumann
Schneider Electric WP 289 (2020) presents microgrids for colocation and service-provider data centres as a joint answer to grid instability, electricity cost and carbon targets.
On this page
Overview
Electricity is roughly 50% of data centre opex excluding IT; an internal study found 40-51% depending on enterprise, colocation or hyperscale type, excluding IT depreciation. Worldwide microgrid capacity is projected to grow more than 20% per year, and installed cost has fallen an estimated 25-30% since 2014. Standby diesel backup is not a microgrid because it does not run continuously; continuously operated distributed energy resources (CHP/CCHP, solar, wind, biomass, fuel cells, battery storage) run under a microgrid controller.
Diesel backup weaknesses: on-site fuel storage typically limits runtime to a few days, emissions rules cap annual run hours, and start-up is not guaranteed (fuel quality, loading, starter batteries). Solar needs about 4-5 acres of land per MW, and cited installed cost fell from $8.50/W in 2009 to $3.05/W in 2019. Energy storage suits peak loads while CCHP or fuel cells are better for base load.
Controller duties are managing grid disconnection and reconnection, balancing DER against load in island mode, maintaining breaker coordination for every DER combination in both modes, and maximizing renewables with export limits in grid-connected mode. Sizing-study inputs are site limits and weather, load profiles, tariffs and demand charges, fuel access and cost, asset and O&M costs, intended buy/generate/store/sell use, export limits or net-zero agreements, and expansion plans. Cybersecurity should align with IEC 62443-4-2 and IEC/ISA 62443-3-3, and ownership options include energy-as-a-service.
Key points
- Electricity is roughly 50% of opex excluding IT; 40-51% in an internal study.
- Microgrid capacity projected to grow over 20% per year; installed cost down 25-30% since 2014.
- Standby diesel is not a microgrid; continuously run DER under a controller is.
- Diesel limits: fuel storage of a few days, emissions caps on annual hours, no start guarantee.
- Solar needs 4-5 acres per MW; cost fell from $8.50/W (2009) to $3.05/W (2019).
- Storage suits peak loads; CCHP or fuel cells suit base load.
- Controller: islanding and reconnection, island balance, breaker coordination for every combination, export-limited renewables.
- Cybersecurity aligned with IEC 62443-4-2 and IEC/ISA 62443-3-3.
Using it in design
- Add an on-site energy/DER layer: sources utility, diesel_standby, gas_chp, cchp_absorption, pv, wind, fuel_cell, bess with a continuous vs standby flag.
- Calculate generator fuel autonomy in hours and days from tank volume and load, and compare it with multi-day resilience targets.
- Check protection coordination for each source combination including island mode, check PV land at about 4-5 acres/MW, and link CCHP waste heat to absorption-chiller capacity in the cooling plant.
- Include tariffs, demand charges, fuel prices and export limits in the feasibility study, and apply an IEC 62443 cybersecurity checklist to the microgrid controller.
Who should read it
Data-centre owners and electrical designers weighing on-site generation against energy cost, grid risk and carbon targets.
Related standards
- IEC 62443-4-2
- IEC 62443-3-3
- Uptime Institute Tier Standard: Topology
- IEEE 2030.7
Publication details
- Authors
- Carsten Baumann
- Publisher
- Schneider Electric
- Year
- 2020
- Document number
- WP 289
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Citation
Carsten Baumann (2020). How Microgrids for Data Centers Increase Resilience, Optimize Costs, and Improve Sustainability. Schneider Electric. WP 289. https://download.schneider-electric.com/files?p_Doc_Ref=Microgrids_for_Data_Centers
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.
