White paperFree to read2023

Quantifying Data Center Scope 3 GHG Emissions to Prioritize Reduction Efforts

Schneider Electric · Paul Lin, Robert Bunger et al.

A Schneider Electric white paper showing how to quantify Scope 3 (value-chain) emissions for a hypothetical enterprise data centre and which sources are the largest.

On this page

Overview

The starting point is that as operators switch to renewable electricity, Scope 2 shrinks and Scope 3 becomes the largest share. Scope 3 is dominated by the embodied carbon of IT and facility equipment plus upstream purchased energy. A carbon report that looks only at operating energy can therefore point a decision maker at the wrong target. The authors quantify this with a hypothetical but detailed example.

The reference model is a 1 MW, Tier 3 facility, 50% loaded, with an annual PUE of 1.34. It assumes N+1 power redundancy and chilled-water cooling, so it represents a mid-sized, redundant enterprise hall using half of its capacity. The IT mix is 94% servers with storage and 6% networking, and racks are 50% populated. Because these assumptions are explicit, a reader can adapt the model to their own site; rack fill and the IT load ratio matter most, since they set the basis on which embodied carbon is allocated.

The method is stepwise: embodied carbon is first separated into IT, facility infrastructure and subsystems. Embodied carbon is then allocated on the assumption that the installed IT fraction equals the IT load ratio. The paper also introduces a companion lifecycle CO2e calculator. This breakdown exists to rank which item deserves reduction effort first. IT equipment, facility infrastructure and subsystems each appear as a separate carbon line, so the discussion can focus on which line would give the largest drop rather than on the total alone.

The conclusion fits in two statements: once Scope 2 is decarbonised, Scope 3 is the largest emission source, and within it the embodied carbon of IT equipment dominates. The limit is that results rest on one hypothetical 1 MW model. A site with a different load ratio, cooling architecture or refresh cycle may see a different split, so the paper teaches the ranking logic rather than universal percentages.

Key points

  1. Reference model: 1 MW, Tier 3, 50% loaded, annual PUE 1.34.
  2. N+1 power redundancy and chilled-water cooling are assumed.
  3. IT mix: servers with storage 94%, networking 6%; racks 50% populated.
  4. Scope 3 becomes the largest source once Scope 2 is decarbonised.
  5. IT equipment embodied carbon dominates within Scope 3.
  6. Embodied carbon allocation assumes installed IT fraction equals IT load ratio.
  7. Embodied carbon is separated into IT, facility infrastructure and subsystems.
  8. A companion lifecycle CO2e calculator is introduced.

Using it in design

  • Add embodied-carbon parameters to the catalog: kgCO2e per server, per kW of UPS or cooling, and per m2 of building.
  • Produce the lifecycle carbon report split by Scope 1/2/3 and by IT versus facility.
  • Assess a 4–5-year IT refresh cycle as a starting assumption and update it against the project asset plan.
  • In renewable-supply scenarios, show the Scope 3 share separately so the reduction priority is visible.

Who should read it

Sustainability specialists doing carbon reporting and designers building catalog and lifecycle models.

Related standards

  • GHG Protocol Scope 3 Standard
  • ISO 14064
  • EN 50600-4-8

Publication details

Authors
Paul Lin; Robert Bunger; Victor Avelar
Publisher
Schneider Electric
Year
2023
Document number
WP 99
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document

Citation

Paul Lin; Robert Bunger; Victor Avelar (2023). Quantifying Data Center Scope 3 GHG Emissions to Prioritize Reduction Efforts. Schneider Electric. WP 99. https://download.schneider-electric.com/files?p_Doc_Ref=SPD_WP99_EN

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cost studies in SoSo CAD

Calculate equipment cost, energy cost and total cost of ownership (TCO) from the design’s quantities and your own price assumptions.

CAPEX and TCO estimates in the SoSo CAD cost workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.