BCA-IMDA Green Mark for Data Centres (GMDC: 2024 beta version)
Building and Construction Authority / IMDA
Singapore's BCA and IMDA GMDC:2024 beta requires energy modelling at 25%, 50%, 75% and 100% IT load for new facilities, twelve months of PUE data for existing ones, and permanent cooling measurement.
On this page
Overview
GMDC 2024 beta is a public set of certification criteria for new and existing data centres in Singapore, published by the Building and Construction Authority (BCA) and the Infocomm Media Development Authority (IMDA). The document number is GMDC:2024 beta and the topics are energy, cooling, metrics and water.
The scheme separates the modelled performance of new facilities from twelve months of operational evidence for existing ones. New facilities model energy at 25%, 50%, 75% and 100% IT load; existing facilities submit twelve months of PUE data. Permanent cooling-efficiency instrumentation is also required, with one-minute trend logging.
Key points
- New facilities model energy at 25%, 50%, 75% and 100% IT load.
- Existing facilities submit twelve months of PUE data.
- Permanent cooling-efficiency instrumentation is required.
- Trend logging is kept at one-minute intervals.
- Scope covers energy, cooling, metrics and water.
Using it in design
- In new-facility design, build the energy model at the four load steps (25%, 50%, 75%, 100%) and document the phased-commissioning assumptions.
- Write permanent energy and efficiency measurement points for the cooling system and one-minute trend logging into the design specification.
- For an existing facility seeking certification, set up the twelve-month PUE recording infrastructure (sub-meters and time-stamped logging) in advance.
Who should read it
Engineers and operators designing data centres in Singapore and seeking certification.
Publication details
- Authors
- Building and Construction Authority / IMDA
- Publisher
- Building and Construction Authority / IMDA
- Year
- 2024
- Document number
- GMDC:2024 beta
- Document language
- English
- Source type
- Government / public
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Official BCA current scheme page links this beta PDF. Free public certification criteria; redistribution permission not established. ASHRAE-derived commissioning and environmental-class clauses were not used.
Citation
Building and Construction Authority / IMDA (2024). BCA-IMDA Green Mark for Data Centres (GMDC: 2024 beta version). Building and Construction Authority / IMDA. GMDC:2024 beta. https://isomer-user-content.by.gov.sg/338/a9e2205f-1da4-49e4-8b89-141a8783246d/20241008_gmdc2024_ver1.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.