Sectoral Water Efficiency Benchmark
PUB, Singapore’s National Water Agency
A December 2025 page from Singapore's national water agency PUB publishing a data-centre median water efficiency index of 2.1 m³/MWh, derived from mandatory large-user submissions.
On this page
Overview
Under the Mandatory Water Efficiency Management Practices (MWEMP), PUB requires large water users to submit their water consumption, business activity indicators and water efficiency plans every year. From these data it develops sectoral benchmarks for office buildings, retail malls, hotels, schools, data centres, commercial laundries, semiconductor and electronics plants and biomedical manufacturing.
The indicator is the Water Efficiency Index (WEI): total water consumed divided by a business activity indicator. The published data-centre median is 2.1 m³/MWh. Other examples: office buildings with water-cooled towers 1.0 m³/m²/year, retail malls 1.1 m³/m²/year, commercial laundries 13.1 m³/tonne. Average recycling rates: wafer fabrication 46%, electronics 45%, semiconductors 29%, biomedical 15%.
The page carries a disclaimer: consumption figures may not include tenants' usage depending on site or building arrangement, and WEI can vary year to year with economic conditions and other external influences. The value is therefore a benchmark from submissions, not a target or guarantee.
Key points
- The published data-centre median WEI is 2.1 m³/MWh (December 2025).
- WEI = total water consumed / business activity indicator.
- Data come from annual submissions by large water users under MWEMP.
- Office buildings with water-cooled towers: median 1.0 m³/m²/year; commercial laundries 13.1 m³/tonne.
- Average recycling rates: wafer fabrication 46%, electronics 45%, semiconductors 29%, biomedical 15%.
- Figures may omit tenant usage and vary with external conditions.
Using it in design
- In Singapore, benchmark the data-centre water target against the 2.1 m³/MWh median and confirm which denominator (IT or facility energy) applies.
- Determine whether tenant usage is in scope and build the water metering architecture accordingly.
- Include water consumption and business activity indicators in the metering plan for the annual MWEMP submission.
- Interpret the benchmark with environmental and economic variables, not as a stand-alone design limit.
Who should read it
Engineers designing and operating data centres in Singapore and sustainability specialists benchmarking water efficiency.
Document contents
- Overview
- How is WEI Calculated?
- Sectoral Water Efficiency Benchmarks
- Average Recycling Rates
- Disclaimer
Publication details
- Authors
- PUB, Singapore’s National Water Agency
- Publisher
- PUB, Singapore’s National Water Agency
- Year
- 2025
- Document language
- English
- Source type
- Government / public
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Official public source inspected. Document-specific permission for commercial redistribution was not established; metadata and original short summaries only.
Citation
PUB, Singapore’s National Water Agency (2025). Sectoral Water Efficiency Benchmark. PUB, Singapore’s National Water Agency. https://www.pub.gov.sg/public/waterloop/water-conservation/resources-on-water-efficiency-measures/sectoral-water-efficiency-benchmark
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.