Technical guideFree to read2017

Technical Reference for Water Conservation in Cooling Towers

PUB, Singapore’s National Water Agency

PUB Singapore's November 2017 technical guide on cooling tower water balance, cycles of concentration (COC) optimisation, water quality and alternative sources; Green Mark rewards COC of 7 or more.

On this page

Overview

The guide explains that in hot, humid Singapore water-cooled chiller systems rely mostly on wet cooling towers, that evaporative towers are estimated to use more than 30 million gallons a day nationally, and that PUB aims to reduce these losses. It gives tower users, developers and building owners the basic management and maintenance knowledge to optimise cycles of concentration (COC) while controlling scale, corrosion, deposition and biological fouling. The BCA Green Mark scheme awards score for tower water treatment systems operating at COC of 7 or more.

The water balance section defines make-up as MU = ER + BD + DR + L (evaporation, blowdown, drift, other losses); without a meter it is estimated as MU = ER x COC / (COC - 1). Evaporation can be reduced by cutting load, improving operation or using alternatives such as dry, indirect or hybrid towers. Savings diminish as COC rises: from an initial COC of 2, raising it to 5 saves about 38%, to 10 about 45% and to 20 about 47%; from an initial COC of 4, raising it to 6 saves 10% and to 10 saves 17%. Blowdown is managed by an automatic valve controlled by a conductivity sensor, which should be cleaned at least monthly.

Achievable average COC depends on the water type: potable water 6-8 without acid injection and 10-15 with; NEWater 8-17 without and 15-20 with; industrial water 2-5 (conductivity above 1,000 µS/cm). Trade effluent limits to the public sewer are pH 6 to 9 and TDS below 3,000 ppm. Scale and corrosion limits mentioned include hardness above 400 ppm CaCO3, silica above 120 ppm and chloride of 300 ppm for stainless steel. Higher COC raises demand for anti-fouling chemicals and biological risk management such as Legionella.

The guide also covers water efficiency audits and reporting, chemical and non-chemical treatment, operation and maintenance practice (regular conductivity and flow readings, real-time conductivity and pH monitoring), best available technology, air-conditioning condensate reuse and, as annexes, the water balance calculation, a water saving checklist and typical parameters of potable water, NEWater and industrial water (conductivity 253, <250 and 600-1,600 µS/cm).

Key points

  1. Evaporative cooling towers in Singapore use more than 30 million gallons a day.
  2. BCA Green Mark scores tower water treatment systems with COC of 7 or more.
  3. Make-up: MU = ER + BD + DR + L; without a meter, MU = ER x COC / (COC - 1).
  4. From an initial COC of 2, raising COC to 5 saves about 38% and to 10 about 45%; savings diminish as COC rises.
  5. COC for potable water 6-8 (no acid), 10-15 (acid); NEWater 8-17 (no acid), 15-20 (acid); industrial water 2-5.
  6. Public sewer discharge limits: pH 6 to 9 and TDS below 3,000 ppm.
  7. Blowdown is managed by an automatic conductivity-controlled valve; the sensor is cleaned at least monthly.
  8. Hardness above 400 ppm CaCO3 and silica above 120 ppm raise scaling risk; a chloride limit of 300 ppm is often used for stainless steel.
  9. Typical conductivity of potable water, NEWater and industrial water is 253, <250 and 600-1,600 µS/cm.

Using it in design

  • Calculate the tower water balance (evaporation, blowdown, drift) and target COC at design and verify make-up demand with MU = ER x COC / (COC - 1).
  • Use the achievable COC by make-up water type (potable, NEWater, industrial) and discharge pH and TDS limits as inputs to the tower treatment programme.
  • Provide meters for make-up, blowdown and conductivity, an automatic conductivity-controlled blowdown valve and real-time conductivity and pH monitoring.
  • Include the extra anti-fouling chemicals and Legionella management needed at high COC in the O&M plan.
  • Consider air-conditioning condensate collection for tower make-up and dry or hybrid towers on water-stressed sites.

Who should read it

Mechanical engineers, building and data-centre operators who design, operate and set treatment programmes for cooling towers.

Document contents

  1. General Introduction of Cooling Towers: Overview, Tower Types, Guidelines and Regulatory Requirements
  2. Water Use and Conservation: Water Balance, Water Efficiency Audits, Water Quality and Chemical Treatment, Non-chemical Treatment, Operation and Maintenance, Factors Limiting COC, Alternative Water Sources
  3. Best Available Technology
  4. Air-Conditioning Condensate Re-Use
  5. Annex A: Cooling Tower Water Balance
  6. Annex B: Cooling Tower Water Saving Checklist
  7. Annex C: Typical Parameters of Potable Water, NEWater and Industrial Water as Makeup Water

Publication details

Authors
PUB, Singapore’s National Water Agency
Publisher
PUB, Singapore’s National Water Agency
Year
2017
Document number
First edition, November 2017
Document language
English
Source type
Government / public
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Official public source inspected. Document-specific permission for commercial redistribution was not established; metadata and original short summaries only.

Citation

PUB, Singapore’s National Water Agency (2017). Technical Reference for Water Conservation in Cooling Towers. PUB, Singapore’s National Water Agency. First edition, November 2017. https://www.pub.gov.sg/-/media/Images/Feature/Content-Pages/Public/Singapore-Water-Loop/Water-Conversation/Resources-on-Water-Efficiency-Measures/TechnicalReference_WaterConservation_CoolingTowers.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.