Remarks on the Safety of Lithium-Ion Batteries for Large-Scale Battery Energy Storage Systems (BESS) in the UK
Original title Remarks on the Safety of Lithium -Ion Batteries for Large-Scale Battery Energy Storage Systems (BESS) in the UK
Fire Technology (Springer Science and Business Media LLC) · Peter P. Edwards, Peter J. Dobson
An open-access commentary in Fire Technology (2025): large lithium-ion BESS carry fire, explosion and toxicity hazards, and the authors recommend pausing new UK deployments until statutory health and safety standards exist.
On this page
Overview
Published in Fire Technology on 21 December 2024 (volume 61, 2025) and open access, this article is a commentary of opinion and assessment rather than a research study. It addresses public concern about the rapid spread of grid-scale BESS in the UK and summarises fundamental battery chemistry and safety issues. The authors' stance is strongly cautionary, and the article recommends a pause in BESS deployment until the necessary regulatory conditions are in place.
The technical sections cover working principles of the Li-ion battery (cathode, anode, separator, electrolyte), thermal runaway, gas and other pollutant production and release, next-generation solid-state batteries and battery management systems. On gases, the paper reports that combustible gases from an LFP module split into H2 and CO and those from vaporised and decomposed liquid organic electrolyte, and that the vaporised electrolyte may be the main trigger of explosion. Fluorinated compounds including hydrofluoric acid are noted in the fumes of battery fires, and LFP is said to emit more toxic fumes than LMO in absolute terms.
The standards and regulations section stresses how hard extinguishment is: there are only smothering or isolating from air, and the physical configuration of BESS restricts both. Current advice is therefore to let a single module burn out while cooling adjacent modules. The effectiveness order for heptafluoropropane, CO2 and N2 is reported as C3HF7 > CO2 > N2, but heptafluoropropane can generate significant HF fumes at fire temperatures. Water mist may give some cooling but risks increasing CO, hydrogen and HF emissions.
The authors argue that no UK law specifically governs BESS safety, guidance to fire services is fragmentary, and the Health and Safety Executive is not a statutory consultee in planning. NFPA 855 (2023) is cited as a starting point. The most practical recommendation is that EPRI's May 2024 guide should be the basis for both regulatory guidance and advice to first responders. The article rests on literature and policy review, not measured site data.
Key points
- The authors strongly recommend pausing widespread BESS installation in the UK and other countries until statutory health and safety standards and practice are adopted.
- South Korea had 23 major battery fires over 2 years between 2020 and 2022; a recent explosion there killed 22 workers and injured 8.
- According to the text, no UK law specifically governs BESS safety; the health and safety regulator is not a statutory consultee in planning.
- In an LFP module, combustible gases are H2 and CO plus vaporised organic electrolyte; the vaporised electrolyte may be the main explosion trigger.
- Fluorinated electrolytes mean fire fumes can contain hydrofluoric acid (HF); one literature review says LFP emits more toxic fumes than LMO in absolute terms.
- Extinguishment is by smothering or isolating from air only; BESS configuration restricts both, and current advice is to let a single module burn out while cooling adjacent ones.
- Effectiveness order for heptafluoropropane, CO2 and N2 is C3HF7 > CO2 > N2, but heptafluoropropane can produce significant HF fumes at high temperature.
- Water mist may give cooling but risks higher CO, hydrogen and HF emissions.
- NFPA 855 (2023) is cited as the lead standard for stationary energy storage installation; EPRI's May 2024 guide is named the best advice to date.
Using it in design
- In battery room extinguishing decisions, assess water mist and clean agents for HF and CO release as well as suppression effectiveness.
- Make cooling of adjacent modules and propagation prevention in a single-module burn scenario central to the design.
- Include the vaporised electrolyte cloud, not only H2 and CO, in the ventilation and gas exhaust risk analysis of battery rooms.
- Add NFPA 855 (2023) and EPRI's 2024 guide as specification references; where national regulation is lacking, adopt them as the design basis.
- In the response plan, provide for advance briefing of the fire service on site size and hazards, and on-site training.
Who should read it
Engineers, fire officials and planning authorities following the regulatory and policy debate on battery energy storage and data-centre battery safety.
Document contents
- Overview
- General Principles of a Working Li-ion Battery
- Thermal Runaway
- Gas and Other Pollutant Production and Release
- Next Generation Lithium Solid-State Batteries
- Battery Management Systems
- Standards and Regulations
- Conclusions and recommendations
Related standards
- NFPA 855
- UL 9540A
Publication details
- Authors
- Peter P. Edwards; Peter J. Dobson
- Publisher
- Fire Technology (Springer Science and Business Media LLC)
- Year
- 2024
- Document language
- English
- Source type
- Scientific
- Access
- Free to read
- Licence
- CC BY 4.0: share with attribution
Original licence note
Publisher-deposited Crossref licence metadata: https://creativecommons.org/licenses/by/4.0 (OpenAlex: cc-by); landing page blocks automated fetch, abstract read via Crossref/OpenAlex. Round 1 ingestion retains bibliographic metadata only; no local full text is redistributed.