A Comprehensive Review of Refrigerant Selection for Two-Phase Thermosiphon Systems in Data Center Cooling

Original title Two-phase thermosiphon cooling in data centers: a comprehensive review of refrigerants for practical selection

Journal of Engineering and Applied Science (Springer Science and Business Media LLC) · Ahmed G. Rahma, Frédy Abadassi et al.

A December 2025 review in the Journal of Engineering and Applied Science scores thermosiphon refrigerants with a decision matrix: water 89 of 90, then methanol 58.5, ammonia 56.5 and ethanol 56.

On this page

Overview

The review covers two-phase thermosiphon (TPT) systems, which cool through gravity-driven natural circulation and refrigerant phase change with no moving parts. The introduction notes about 5 billion users growing about 5% a year and rising energy use: data centres consumed about 200 TWh in 2019 (1% of world electricity) and about 415 TWh in 2024 (1.5%), with the IEA projecting 945 TWh by 2030. Server power has grown from 1 kW to about 20 kW per rack.

Common refrigerants are assessed on five criteria: thermal capacity, operating conditions, geometric design limits, environmental impact (GWP and ODP), health and safety, and international regulation. Thermal capacity uses latent heat and the Merit number at 55 °C: water has the highest at 3.11 × 10^11 W/m², then ammonia at 7.91 × 10^10 and methanol at 4.42 × 10^10 W/m².

On operating conditions, water has the lowest saturation pressure over the 25-85 °C CPU range, and for 25-600 W CPUs its volume flow is about 0.015 L/min against 0.042, 0.053 and 0.063 L/min for methanol, ethanol and ammonia and above 0.15 L/min for others. For geometry, the critical tube diameter interval is about 44.80 mm for water (5.27 to 50.07 mm), about 27.6 mm for methanol and ethanol, and about 7.80 mm for R410A.

A decision matrix combines the results: water scores 89 of 90, followed by methanol, ammonia and ethanol at 58.5, 56.5 and 56; pentane and 2-methylbutane are moderately suitable and some alternatives score much lower on safety or environmental grounds. Water's low vapour density limits it to systems of limited height such as local cooling units.

Key points

  1. Decision matrix: water 89/90, methanol 58.5, ammonia 56.5, ethanol 56; pentane and 2-methylbutane moderate.
  2. Merit number at 55 °C: water 3.11 × 10^11 W/m², ammonia 7.91 × 10^10, methanol 4.42 × 10^10, ethanol 2.06 × 10^10 W/m².
  3. Required volume flow: water about 0.015 L/min; methanol 0.042, ethanol 0.053, ammonia 0.063 L/min; others above 0.15 L/min.
  4. Critical diameter interval: water about 44.80 mm, methanol and ethanol about 27.6 mm, R410A about 7.80 mm.
  5. Data centres used about 200 TWh in 2019 and about 415 TWh in 2024; the IEA projects 945 TWh by 2030.
  6. Server power rose from 1 kW to about 20 kW per rack.
  7. Water's low vapour density limits it to systems of limited height such as local cooling units.
  8. Under unstable flow, R134a shows little performance loss while water loses 5-20%.

Using it in design

  • Select the thermosiphon refrigerant by scoring the five criteria (thermal capacity, operating conditions, geometry, environment, safety and regulation).
  • If water is chosen, keep vertical distance limited because of its low vapour density and use it at local cooling unit scale.
  • Choose tube diameter inside the refrigerant's critical diameter interval (5.27 to 50.07 mm for water) to avoid dropping into pool boiling.
  • Where water is unsuitable, consider methanol or ethanol as second candidates for their operating-pressure advantage.
  • Put flammable or toxic alternatives through a safety review together with their GWP and regulatory status.

Who should read it

Thermal designers evaluating passive two-phase and heat-pipe cooling and engineers selecting refrigerants.

Document contents

  1. Introduction
  2. Thermal management strategies in data centers
  3. Refrigerants in TPT systems: theoretical considerations
  4. Thermal capacity (Merit number)
  5. Operating conditions (saturation pressure, volume flow rate)
  6. Geometrical design limitations (critical diameter)
  7. Environmental impact, health and safety, regulation
  8. Decision matrix
  9. Conclusion

Related standards

  • ISO 817 / ASHRAE 34 refrigerant safety classes

Publication details

Authors
Ahmed G. Rahma; Frédy Abadassi; Jiyan Akyol; Abderahmane Marouf; Pierre François; Fabrice Lawniczak; Abdellah Ghenaim; Yannick Hoarau; Constanze Bongs; Michael Kauffeld; Denis Funfschilling
Publisher
Journal of Engineering and Applied Science (Springer Science and Business Media LLC)
Year
2025
Document language
English
Source type
Scientific
Access
Free to read
Licence
CC BY 4.0: share with attribution
Original licence note

Publisher-deposited Crossref licence metadata: https://creativecommons.org/licenses/by/4.0 (OpenAlex: cc-by); landing page blocks automated fetch, abstract read via Crossref/OpenAlex. Round 1 ingestion retains bibliographic metadata only; no local full text is redistributed.

Citation

Ahmed G. Rahma; Frédy Abadassi; Jiyan Akyol; Abderahmane Marouf; Pierre François; Fabrice Lawniczak; Abdellah Ghenaim; Yannick Hoarau; Constanze Bongs; Michael Kauffeld; Denis Funfschilling (2025). Two-phase thermosiphon cooling in data centers: a comprehensive review of refrigerants for practical selection. Journal of Engineering and Applied Science (Springer Science and Business Media LLC). https://doi.org/10.1186/s44147-025-00833-3

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.