ECO SNT: Instruction for Operation and Maintenance, Single Stage Norm Centrifugal Pumps

Original title ECO SNT: Instruction for Operation and Maintenance: Single Stage Norm Centrifugal Pumps

Standart Pompa

Standart Pompa's January 2017 installation, operation and maintenance manual for ECO SNT norm centrifugal pumps: DN32-DN150, up to 10 bar (16 bar), -20 to 140 °C, bearing temperature limit 80 °C.

On this page

Overview

The document is the installation, operation and maintenance manual for Standart Pompa's ECO SNT single-stage norm centrifugal pumps (01.2017, revision 0). It opens with general provisions such as safety signs, CE approvals, explosive-atmosphere labelling and temperature classes, followed by pump description, designation, nameplate and technical data.

Technical data give a discharge nozzle of DN32-DN150, operating temperature of -20 to 100 °C with uncooled soft packing, 100-140 °C with cooled packing and -20 to 140 °C with a mechanical seal, and casing pressure up to 10 bar (16 bar optional). Temperature class T4 allows a maximum surface of 135 °C and fluid of 110 °C; T3 allows 200 and 180 °C.

The installation section covers foundation and baseplate, piping, coupling alignment, minimum flow and electrical connection. Pipe velocity should not exceed 2 m/s on suction and 3 m/s on delivery. Long operation against a closed valve is prohibited because motor power turns into heat in the liquid. Start-up lists lubrication, venting and rotation checks.

The manual describes a general pump family; it holds no project duty or data-centre application. Its value is as a basis for a chilled-water pump installation, alignment and first-start checklist.

Key points

  1. Discharge nozzle DN32-DN150; casing pressure up to 10 bar, 16 bar optional.
  2. Operating temperature: uncooled soft packing -20 to 100 °C; cooled packing 100-140 °C; mechanical seal -20 to 140 °C.
  3. Temperature class T4: maximum surface 135 °C, maximum fluid 110 °C; T3: 200 °C and 180 °C.
  4. Pipe velocity should not exceed 2 m/s on suction and 3 m/s on delivery; high velocity causes cavitation.
  5. The foundation surface should be level within 0.25-0.40 mm/m on a precise spirit level.
  6. Bearing temperature may exceed ambient by at most 50 °C and must never exceed 80 °C.
  7. Long operation against a closed valve is prohibited; a by-pass valve goes on the delivery line when near-zero flow is possible.
  8. Motors conform to EN 60034-1 with at least IP22 enclosures (EN 60529); the pump must not run dry.

Using it in design

  • In a chilled-water pump specification, write the pipe velocity limits (suction 2 m/s, delivery 3 m/s) and a suction-line NPSH check as design criteria.
  • Provide a by-pass or minimum-flow line on circuits where the duty point can approach a closed valve.
  • Add baseplate and coupling alignment tolerances to the commissioning test plan; do the final alignment at operating temperature.
  • Include bearing temperature (80 °C upper limit) and vibration points in the monitoring system.
  • Put venting, flexible coupling and the rule that pipe loads must not reach the pump flange on the site checklist.

Who should read it

Site engineers, mechanical contractors and operations teams installing and commissioning chilled-water pumps.

Document contents

  1. General and Safety Instructions
  2. General Pump Description
  3. Unpacking, Handling and Storage
  4. Installation on Site
  5. Start Up and Shut Down
  6. Maintenance: Bearing Lubrication
  7. Disassembly, Tightening Torques, Assembly and Shaft Seal

Publication details

Authors
Standart Pompa
Publisher
Standart Pompa
Year
2017
Document number
01.2017 Revision 0
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Official public source inspected. No document-specific redistribution permission established; metadata and original brief summaries only. Local downloads are research evidence, not a redistribution package.

Citation

Standart Pompa (2017). ECO SNT: Instruction for Operation and Maintenance: Single Stage Norm Centrifugal Pumps. Standart Pompa. 01.2017 Revision 0. https://product.standartpompa.com/AppRepo/Document/20190530152156-1239.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.