Technical guideFree to read2025

Reference Design: Supermicro's Extreme Energy-Efficient Compute Cluster powered by Submer

Original title Reference Design: Supermicro's Extreme Energy-Efficient Compute Cluster powered by Submer - Unlocking the value of free-cooling

Submer · Submer, Supermicro

A Submer and Supermicro reference design for a 1,920-CPU immersion cluster using 45 °C facility water for free cooling up to 40 °C ambient and targeting PUE below 1.1.

On this page

Overview

The document is a reference design combining Supermicro servers with Submer immersion cooling for general compute, edge and cloud. The aim is free cooling with no water- or power-consuming chillers, lowering operating cost and reaching PUE below 1.1; with less energy spent on cooling, more IT fits within the same power availability.

The setup builds on blocks of 192 AMD Turin 9825 CPUs including power distribution, network and cabling, scalable to any size. The example is a 1,920-CPU cluster cooled with 45 °C (113 F) facility water supply (FWS), allowing free cooling at ambient up to 40 °C (104 F). The tank is the SmartPod EXO TwinTank: 99.999% SLA availability (fully redundant, HA), 45 °C FWS inlet and a fluid setpoint up to 60 °C.

The CPU is the AMD Turin 9825 (400 W TDP, up to 3.7 GHz, 384 MB L3) in AS-1126HS-TN1U dual EPYC 9004/9005 servers; a 960-CPU, 138,240-core example is quoted. The document shows hall layout (main busbar to secondary busbar to SmartPods) and a bill of materials (48 servers, 40 SmartPod EXO S100 Unitanks, PAO2-compatible hydrocarbon fluids). It is a vendor reference design without a measured site PUE result.

Key points

  1. Goal: free cooling without chillers and PUE below 1.1.
  2. Building block: 192 AMD Turin 9825 CPUs; example cluster 1,920 CPUs.
  3. Facility water supply 45 °C (113 F); free cooling up to 40 °C (104 F) ambient.
  4. SmartPod EXO TwinTank: 99.999% SLA, fluid setpoint up to 60 °C.
  5. CPU: AMD Turin 9825, 400 W TDP, up to 3.7 GHz, 384 MB L3 cache.
  6. Server: AS-1126HS-TN1U, 24 DIMMs up to 6 TB at 6400 MT/s.
  7. Lower cooling energy lets more IT be added at the same power.
  8. The bill of materials lists 40 SmartPod EXO S100 Unitanks and PAO2-compatible hydrocarbon fluids.

Using it in design

  • Compare the 45 °C facility water supply and 40 °C peak ambient with site climate data for free cooling.
  • Set the tank fluid setpoint (up to 60 °C) together with heat reuse needs.
  • Recalculate the PUE target (below 1.1) against existing power capacity by shifting cooling energy to IT.
  • Plan the 192-CPU building block as a scalable module with power, network and cabling.
  • Re-verify reference design values against your own server and fluid choices.

Who should read it

Engineers designing immersion-cooled compute clusters and decision makers weighing free cooling and PUE targets.

Document contents

  1. Why free cooling
  2. Technology set up
  3. Datacenter set up
  4. Datasheets and SKUs

Publication details

Authors
Submer; Supermicro
Publisher
Submer
Year
2025
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Vendor reference design on submer.com; no open licence stated

Citation

Submer; Supermicro (2025). Reference Design: Supermicro's Extreme Energy-Efficient Compute Cluster powered by Submer - Unlocking the value of free-cooling. Submer. https://submer.com/wp-content/uploads/2025/10/Reference-Designs-Supermicro.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.