White paperCitation2016

WP#68 - The Performance Indicator: Assessing and Visualizing Data Center Cooling Performance

The Green Grid · Mark Seymour, Maira Bana et al.

This Green Grid white paper introduces the Performance Indicator, which combines three cooling metrics, one of them based on PUE. It makes the trade-off between thermal performance and energy savings visible.

On this page

Overview

The document is dated 22 June 2016; its editors include Mark Seymour (Future Facilities). The Performance Indicator brings together three cooling performance metrics: one uses PUE, and the other two are IT thermal conformance and IT thermal resilience.

The paper shows trade-offs between thermal performance and energy savings. It includes calculation methods and a detailed case study, and its authors recommend modelling, simulation and monitoring. The trio stresses that cooling performance should be judged not only by measured energy but also by the actual temperature conditions of the equipment.

The most important warning is that focusing on PUE alone can cause stranded capacity or unintended risk. A low-PUE target may push IT inlet temperatures outside the recommended range, or leave redundancy inadequate when a cooling failure occurs.

As a limit, the summary gives neither formulas nor thresholds for the metrics; the document itself should be consulted. The related source is ASHRAE Thermal Guidelines, from which the notions of recommended and allowable ranges derive.

Key points

  1. Dated 22 June 2016; editors include Mark Seymour (Future Facilities).
  2. Three cooling performance metrics, one using PUE.
  3. Defines IT thermal conformance and IT thermal resilience.
  4. Includes calculation methods and a detailed case study.
  5. Warns that focusing on PUE alone can cause stranded capacity or unintended risk.
  6. Recommends modelling, simulation and monitoring.
  7. Related source: ASHRAE Thermal Guidelines.

Using it in design

  • In airflow/CFD results, report thermal conformance (share of IT inlets within the recommended range) alongside PUE.
  • Also report thermal resilience (share of IT inlets within the allowable range after a cooling failure).
  • Do not make the PUE target the sole optimisation criterion; weigh stranded capacity and risk together.

Who should read it

Engineers designing cooling and airflow, CFD analysts, and operations teams.

Related standards

  • ASHRAE Thermal Guidelines

Publication details

Authors
Mark Seymour; Maira Bana; David Wang; Danny Cummins; Veerendra Para; Magnus Herrlin; James Betts; Jay Vincent; Henry Wong; Chang Tsann; Bob Landstrom
Publisher
The Green Grid
Year
2016
Document number
WP 68
Document language
English
Source type
Industry body
Access
Citation only
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Download requires a free TGG account sign-in and is governed by The Green Grid Terms of Use; summary and facts from the public library landing page; full text not redistributed.

Citation

Mark Seymour; Maira Bana; David Wang; Danny Cummins; Veerendra Para; Magnus Herrlin; James Betts; Jay Vincent; Henry Wong; Chang Tsann; Bob Landstrom (2016). WP#68 - The Performance Indicator: Assessing and Visualizing Data Center Cooling Performance. The Green Grid. WP 68. https://www.thegreengrid.org/en/resources/library-and-tools/370-WP%2368---The-Performance-Indicator-Assessing-and-Visualizing-Data-Center-Cooling-Performance

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.