Digital Liquids Leak Detection Systems for Indoor Applications: Design and Application Guide
Original title Design & Application Guide: Digital Liquids Leak Detection Systems For Indoor Applications
TTK
TTK's design guide (version 4.3.6, 2021) for its FG-NET, FG-SYS and FG-ALS leak detection panels, covering panel capacities, sense-cable layouts and data-centre and pipework applications.
On this page
Overview
The guide addresses consulting engineers, contractors and end users, and uses drawings to show typical in-building layouts of TTK's digital and analogue leak detection and locating systems. The first part introduces the product families: digital panels (FG-NET, FG-SYS), eight- and four-zone analogue panels (FG-ALS8, FG-ALS4), the single-circuit FG-A, satellite devices (FG-BBOX, FG-RELAYS), water, acid and hydrocarbon sense cables, point sensors and diversion boxes.
Capacities are tabulated. FG-NET and FG-SYS carry three circuits, each taking up to 40 cables and 600 m of sense cable, for 1,800 m per panel. The FG-BBOX satellite adds two circuits and 1,200 m of cable, and up to 16 can attach to one FG-NET. Analogue FG-ALS8 supports 100 m per circuit, FG-ALS4 45 m and FG-A 15 m. The jumper cable from panel to first sense cable can run up to 150 m.
The application part shows sense cable run around the perimeter of data-centre and air-conditioning rooms and in front of the units, fixed in drip trays under pipes or strapped to uninsulated pipes, and hydrocarbon cable (FG-OD) around generators and fuel tanks. The document is promotional and vendor-specific; for building management integration the panels offer RJ45 (TCP/IP), RS232/RS422/485 (JBUS/ModBUS) and relay outputs.
Key points
- FG-NET and FG-SYS: 3 circuits, up to 40 cables and 600 m of sense cable per circuit, 1,800 m per panel.
- The FG-BBOX satellite adds 2 circuits and 1,200 m (80 lengths) of cable; up to 16 FG-BBOX connect to one FG-NET.
- Analogue panels: FG-ALS8 (8 zones, 100 m per circuit), FG-ALS4 (4 zones, 45 m), FG-A (1 zone, 15 m).
- The jumper cable between panel and first sense cable is limited to 150 m.
- Standard water and acid cable lengths are 3, 7 and 15 m; hydrocarbon FG-OD cable comes in 3, 7, 12 and 20 m.
- Around air-conditioning units, sense cable is advised about 75 cm in front of the air outlet.
- Digital panels have 8 configurable relays and one power-failure relay; FG-RELAYS boxes extend this to up to 384 additional relays.
- FG-OD hydrocarbon cable is not compatible with the FG-SYS panel; it connects to FG-NET or FG-BBOX through an FG-DOD interface box.
Using it in design
- Draw sense cable around the room perimeter and in front of cooling units in the data hall plan, and verify circuits, cable count and the 600 m limit per panel circuit.
- Choose cable in drip trays under chilled-water pipes, and braided FG-ECB cable for insulated pipes without trays; allow for condensation when fitting inside insulation.
- For remote areas use satellite devices and diversion boxes while staying inside the 150 m jumper limit.
- Wire alarm outputs (TCP/IP, ModBus, relays) to the building management system and to pump or valve shut-off logic.
- Plan hydrocarbon cable for generators and fuel tanks on a separate circuit with a compatible panel.
Who should read it
Consulting engineers, contractors and operations teams designing leak detection for data centres and technical rooms.
Document contents
- Introduction
- Products list
- Part 1: Design layouts (alarm units, point sensors, boxes, horizontal and vertical layouts, digital cable layouts, external relay box)
- Part 2: Applications (data centre and air-conditioner rooms, technical equipment, indoor water pipes, multi-level buildings)
Publication details
- Authors
- TTK
- Publisher
- TTK
- Year
- 2021
- Document number
- EN_V4.3.6_032021
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Official public manufacturer source inspected. No document-specific redistribution permission established. Metadata and original brief summaries only; local downloads are research evidence, not a redistribution package.
Citation
TTK (2021). Design & Application Guide: Digital Liquids Leak Detection Systems For Indoor Applications. TTK. EN_V4.3.6_032021. https://www.ttk.fr/wp-content/uploads/2021/03/Design_Guide-EN-v4.3.6-2021.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.