Digital Liquids Leak Detection Systems for Indoor Applications: Design and Application Guide

Original title Design & Application Guide: Digital Liquids Leak Detection Systems For Indoor Applications

TTK

TTK's design guide (version 4.3.6, 2021) for its FG-NET, FG-SYS and FG-ALS leak detection panels, covering panel capacities, sense-cable layouts and data-centre and pipework applications.

On this page

Overview

The guide addresses consulting engineers, contractors and end users, and uses drawings to show typical in-building layouts of TTK's digital and analogue leak detection and locating systems. The first part introduces the product families: digital panels (FG-NET, FG-SYS), eight- and four-zone analogue panels (FG-ALS8, FG-ALS4), the single-circuit FG-A, satellite devices (FG-BBOX, FG-RELAYS), water, acid and hydrocarbon sense cables, point sensors and diversion boxes.

Capacities are tabulated. FG-NET and FG-SYS carry three circuits, each taking up to 40 cables and 600 m of sense cable, for 1,800 m per panel. The FG-BBOX satellite adds two circuits and 1,200 m of cable, and up to 16 can attach to one FG-NET. Analogue FG-ALS8 supports 100 m per circuit, FG-ALS4 45 m and FG-A 15 m. The jumper cable from panel to first sense cable can run up to 150 m.

The application part shows sense cable run around the perimeter of data-centre and air-conditioning rooms and in front of the units, fixed in drip trays under pipes or strapped to uninsulated pipes, and hydrocarbon cable (FG-OD) around generators and fuel tanks. The document is promotional and vendor-specific; for building management integration the panels offer RJ45 (TCP/IP), RS232/RS422/485 (JBUS/ModBUS) and relay outputs.

Key points

  1. FG-NET and FG-SYS: 3 circuits, up to 40 cables and 600 m of sense cable per circuit, 1,800 m per panel.
  2. The FG-BBOX satellite adds 2 circuits and 1,200 m (80 lengths) of cable; up to 16 FG-BBOX connect to one FG-NET.
  3. Analogue panels: FG-ALS8 (8 zones, 100 m per circuit), FG-ALS4 (4 zones, 45 m), FG-A (1 zone, 15 m).
  4. The jumper cable between panel and first sense cable is limited to 150 m.
  5. Standard water and acid cable lengths are 3, 7 and 15 m; hydrocarbon FG-OD cable comes in 3, 7, 12 and 20 m.
  6. Around air-conditioning units, sense cable is advised about 75 cm in front of the air outlet.
  7. Digital panels have 8 configurable relays and one power-failure relay; FG-RELAYS boxes extend this to up to 384 additional relays.
  8. FG-OD hydrocarbon cable is not compatible with the FG-SYS panel; it connects to FG-NET or FG-BBOX through an FG-DOD interface box.

Using it in design

  • Draw sense cable around the room perimeter and in front of cooling units in the data hall plan, and verify circuits, cable count and the 600 m limit per panel circuit.
  • Choose cable in drip trays under chilled-water pipes, and braided FG-ECB cable for insulated pipes without trays; allow for condensation when fitting inside insulation.
  • For remote areas use satellite devices and diversion boxes while staying inside the 150 m jumper limit.
  • Wire alarm outputs (TCP/IP, ModBus, relays) to the building management system and to pump or valve shut-off logic.
  • Plan hydrocarbon cable for generators and fuel tanks on a separate circuit with a compatible panel.

Who should read it

Consulting engineers, contractors and operations teams designing leak detection for data centres and technical rooms.

Document contents

  1. Introduction
  2. Products list
  3. Part 1: Design layouts (alarm units, point sensors, boxes, horizontal and vertical layouts, digital cable layouts, external relay box)
  4. Part 2: Applications (data centre and air-conditioner rooms, technical equipment, indoor water pipes, multi-level buildings)

Publication details

Authors
TTK
Publisher
TTK
Year
2021
Document number
EN_V4.3.6_032021
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Official public manufacturer source inspected. No document-specific redistribution permission established. Metadata and original brief summaries only; local downloads are research evidence, not a redistribution package.

Citation

TTK (2021). Design & Application Guide: Digital Liquids Leak Detection Systems For Indoor Applications. TTK. EN_V4.3.6_032021. https://www.ttk.fr/wp-content/uploads/2021/03/Design_Guide-EN-v4.3.6-2021.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.