Technical guideFree to read2020

Four Firefighters Injured in Lithium-Ion Battery Energy Storage System Explosion, Arizona

Original title Four Firefighters Injured in Lithium-Ion Battery Energy Storage System Explosion - Arizona

UL Firefighter Safety Research Institute (Underwriters Laboratories) · Mark B. McKinnon, Sean DeCrane et al.

UL Firefighter Safety Research Institute report of 28 July 2020: on 19 April 2019 cascading thermal runaway in a 2.16 MWh lithium-ion ESS led to a deflagration that seriously injured four firefighters; gas monitoring, deflagration venting and emergency planning were lacking.

On this page

Overview

The report is an independent review of the incident in Surprise, Arizona on 19 April 2019. Cascading thermal runaway occurred in a 2.16 MWh lithium-ion energy storage system (ESS); the smoke detector alarmed at about 16:55 and discharged a total flooding clean agent (Novec 1230). The hazmat team arrived around 18:28, measured dangerously elevated hydrogen cyanide (HCN) and carbon monoxide, and opened the container door at about 20:01. A deflagration occurred at 20:04 and four team members were seriously injured. The system was commissioned before the first draft of NFPA 855 and complied with the codes active at the time.

The UL FSRI team reviewed the site in October 2019 and met the chiefs of two fire departments and the ESS owner. The report covers the fire departments, incident, ESS, personal protective equipment, timeline and a detailed narrative, followed by analysis, injuries, contributing factors, recommendations and decommissioning of the ESS. Appendix A explains ignition of gases produced during thermal runaway.

The contributing factors it finds are: responders held current hazmat competencies, but those curricula do not cover basic ESS hazards; the fire and smoke detection did not include, and was not required to include, flammable gas sensors; the team had no means to monitor toxic gas, LEL or internal conditions from a secure location; the ESS communication system failed before the team arrived; the emergency response plan was not provided to the fire service beforehand and was inadequate; the design lacked NFPA 68 deflagration venting and NFPA 69 mechanical ventilation; and the clean agent system prevented flaming early but was not designed for explosion protection.

Recommendations include adding ESS and explosive gas cloud knowledge to fire training, full-scale testing research, defining a conservative blast radius and treating the enclosure gas as above LEL until proven otherwise, remotely accessible gas monitoring, uninterrupted communications, an owner and operator emergency plan prepared with the fire service and authority, signage identifying ESS contents, and explosion prevention protection per NFPA 855 or International Fire Code Chapter 12.

Key points

  1. On 19 April 2019 cascading thermal runaway in a 2.16 MWh lithium-ion ESS caused a deflagration that seriously injured four firefighters.
  2. The smoke detector alarmed at about 16:55 and a total flooding clean agent (Novec 1230) discharged; the deflagration came at about 20:04, 3 minutes after the door was opened.
  3. The hazmat team measured dangerously elevated hydrogen cyanide (HCN) and carbon monoxide (CO) on each entry.
  4. The fire and smoke detection system had no flammable gas sensors and was not required to; the team could not monitor LEL or internal conditions from a safe place.
  5. The ESS communication system failed before the fire service arrived.
  6. The design lacked NFPA 68 deflagration venting and NFPA 69 mechanical ventilation; codes of the time did not require them.
  7. The clean agent system prevented flaming in the early phase but did not provide explosion protection.
  8. The emergency response plan had not been given to the fire service before the incident, and the plan provided gave inadequate guidance on thermal runaway, fire and explosion hazards.
  9. Recommendation: until definitive tactics exist, fire personnel should define a conservative blast radius and treat enclosure gas as above LEL until proven otherwise.

Using it in design

  • Include remotely accessible flammable gas (and, where needed, toxic gas) monitoring in battery rooms and containers so the fire service can see LEL and internal conditions from a safe place.
  • Build a robust communications architecture that keeps gas monitoring, BMS and fire alarm panel data uninterrupted.
  • Include NFPA 68 deflagration venting and NFPA 69 mechanical ventilation or explosion prevention within the NFPA 855 framework.
  • Treat the clean agent system as flame suppression, not explosion protection, and assess whether a separate explosion prevention solution is needed.
  • Prepare the emergency plan with the fire service and authority and share it before commissioning, with content signage at the installation.

Who should read it

Engineers designing battery energy storage and data-centre UPS battery rooms, fire and emergency planners, and code development and authority personnel.

Document contents

  1. Executive Summary (contributing factors, key recommendations)
  2. Introduction
  3. Fire Department Overview
  4. Incident Overview (weather, building construction, energy storage system, PPE, timeline, detailed narrative, analysis)
  5. Description of Injuries
  6. Contributing Factors
  7. Recommendations
  8. Decommissioning the ESS
  9. Appendix A: Ignition of Gases Produced During Thermal Runaway

Related standards

  • NFPA 855
  • NFPA 68
  • NFPA 69
  • UL 9540A
  • NFPA 2001

Publication details

Authors
Mark B. McKinnon; Sean DeCrane; Stephen Kerber
Publisher
UL Firefighter Safety Research Institute (Underwriters Laboratories)
Year
2020
Document language
English
Source type
Expert / community
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Copyright 2020 Underwriters Laboratories Inc. All rights reserved.

Citation

Mark B. McKinnon; Sean DeCrane; Stephen Kerber (2020). Four Firefighters Injured in Lithium-Ion Battery Energy Storage System Explosion - Arizona. UL Firefighter Safety Research Institute (Underwriters Laboratories). https://fsri.org/sites/default/files/2021-07/Four_Firefighters_Injured_In_Lithium_Ion_Battery_ESS_Explosion_Arizona_0.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Standards pre-assessment in SoSo CAD

Run TS EN 50600 and Tier pre-checks on the model, with missing inputs and items for engineering review listed separately.

Selected rule packs and findings in the SoSo CAD standards panel

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.