Sealing Gaps Under IT Racks: CFD Analysis Reveals Significant Savings Potential
Original title Sealing Gaps Under IT Racks: CFD Analysis Reveals Significant Savings Potential (Technical Report)
Upsite Technologies · Lars Strong, Bruce Long
A 2016 Upsite Technologies technical report shows that in a 217 kW room, sealing gaps under IT racks cuts average inlet temperature of bottom-of-rack servers by 10.5 °F (up to 18.9 °F) and lets cooling fan speed fall 10%.
On this page
Overview
The report explains that gaps from half an inch to two or more inches under cabinets, created by casters and leveling feet, let hot exhaust air flow under the rack to the front, raising IT inlet temperatures, contributing to hot spots and failure rates. CFD analysis examines the effect of sealing these small gaps.
The model is a 2,260 ft² raised-floor room: 217 kW IT load, 335 kW rated cooling, 48 racks (1 to 12 kW, average 4.5 kW), 50,006 CFM conditioned airflow to the floor against 30,747 CFM of IT airflow (ratio 1.6:1), and 62 °F supply air. Cable openings are sealed, unused U-spaces blanked, rack rails sealed and rows fitted with modular containment; the two models differ only in 1.5 in gaps under racks versus sealing with the Upsite panel.
The result is a 10.5 °F reduction in average inlet temperature of servers at the bottom (up to 18.9 °F in rack Q4), and a maximum inlet in a representative row falling from 86.4 °F to 75.0 °F. Cooling unit fan speed can be cut 10%; energy savings are $5,318 a year in the small 2,260 ft² room and $47,059 for a 20,000 ft² room at $0.10/kWh. At $18 per panel, simple payback is under 2 months. Infrared images of operating data centers show equipment at the bottom of racks receiving about 10 °F warmer intake air than equipment about 2 ft above, because of a roughly 1.25 in gap.
The report is a vendor publication and the model uses the maker's AisleLok under-rack panel. Its conclusion is that sealing the gap is cheaper than adding high-flow grates or fan speed, and that it both corrects inlet temperature and releases stranded cooling capacity; all remediation was done without any IT inlet exceeding the ASHRAE recommended maximum of 80.6 °F (27 °C).
Key points
- Gaps under racks range from half an inch to two or more inches because of casters and leveling feet.
- Model: 2,260 ft², 217 kW IT, 335 kW cooling, 48 racks, 4.5 kW average per rack, supply-to-IT airflow ratio 1.6:1, 62 °F supply.
- Average inlet temperature of bottom servers falls 10.5 °F, up to 18.9 °F; the average of the maximum inlet reduction for all servers is 9.4 °F.
- Maximum inlet in a representative row falls from 86.4 °F to 75.0 °F (11.4 °F lower).
- Cooling unit fan speed is reduced 10%.
- Annual energy savings are $5,318 in a 2,260 ft² room and $47,059 in a 20,000 ft² room (at $0.10/kWh).
- At $18 per under-rack panel, simple payback is under 2 months.
- In field infrared images a 1.25 in gap brings about 10 °F warmer air to lower equipment; sealing gives 10 to 12 °F reduction.
Using it in design
- Add sealing of the bottom front edge of racks (blanking, gasket or under-rack panel) to the acceptance and commissioning checklist.
- In raised-floor designs treat cable openings, blanking panels and under-rack gaps together; do not rely on lower supply temperature or higher airflow alone.
- Use infrared imaging to compare bottom and top server inlet temperatures to verify under-rack leakage during site audits.
- After sealing, change fan speed and supply set points in steps and monitor IT inlet temperature below the 27 °C upper end of the ASHRAE recommended range.
- Count the released cooling capacity in the plan for new IT load or when deferring cooling unit investment.
Who should read it
Designers and operations teams improving airflow management in raised-floor data halls.
Document contents
- Executive Summary
- Background and model parameters
- IT equipment maximum inflow temperature reduction by rack
- Comparison of inflow temperatures for a representative cabinet row
- Isometric view of air temperature cross section
- Infrared imaging of operating data centers
- Conclusion
Related standards
- ASHRAE TC 9.9 thermal guidelines
Publication details
- Authors
- Lars Strong; Bruce Long
- Publisher
- Upsite Technologies
- Year
- 2016
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
© Upsite Technologies, Inc.; no open licence stated
Citation
Lars Strong; Bruce Long (2016). Sealing Gaps Under IT Racks: CFD Analysis Reveals Significant Savings Potential (Technical Report). Upsite Technologies. https://www.upsite.com/wp-content/uploads/Sealing-Gaps-Under-IT-Racks-Technical-Report.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.