AisleLok Modular Containment vs. Legacy Containment: A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings
Upsite Technologies · Bruce Long, Lars Strong
A 2015 Upsite CFD study finds that in a 490 m², 433 kW IT room modular cold aisle containment cuts CRAH power 72% with 13.5-month payback, against 66% and 24 months for legacy full containment.
On this page
Overview
The study compares two types of cold aisle containment: modular containment applied to individual cabinets (magnetic rack top baffles and bi-directional doors on end-of-row cabinets) and legacy 'full' containment, a constructed enclosure around selected rows or a section of the room. The baseline is a theoretical raised-floor data center with airflow management but no containment, built from real field data.
The model is 5,280 ft² (490 m²), 60 × 88 ft, with 2 ft raised floor, 138 cabinets, average cabinet density 3.3 kW (0.75 to 12 kW), total IT load 433 kW, total heat load 488 kW and ten 30-ton chilled-water CRAH units. Without containment cabinet rails have 25% leakage and blanking panels 5%; with containment rails are 5% and blanking panels 0.03%, and the cabinet bottom front edge is sealed to the floor. CRAH blower speeds are lowered until maximum IT inlet approaches the ASHRAE recommended 80.6 °F (27 °C).
Results: maximum inlet temperature at end-of-row cabinets is 83.1 °F in the base, 66.7 °F with modular and 63.2 °F with legacy; mid-row 85.9 °F against 67.3 °F and 63.3 °F. Raised floor airflow falls from 124,000 CFM to 86,800 CFM (30% lower) and 80,600 CFM (35% lower), and CRAH power from 55.9 kW to 19.2 kW (66%) and 15.4 kW (72%). Annual energy savings are $32,171 and $35,320, deployment cost $36,180 and $70,993, and payback 13.5 and 24 months (24/7, $0.10/kWh).
The paper is a vendor publication and results rest on the theoretical model and stated assumptions. The vendor argues both approaches perform well on inlet temperature and fan speed, but modular containment gives faster ROI and lower total cost of ownership.
Key points
- Model: 5,280 ft² (490 m²), 138 cabinets, 433 kW IT, 488 kW total heat, 3.3 kW average and 12 kW maximum cabinet, ten 30-ton CRAH units.
- End-of-row maximum inlet: base 83.1 °F, modular 66.7 °F (16.4 °F lower), legacy 63.2 °F (19.9 °F lower).
- Mid-row maximum inlet: base 85.9 °F, modular 67.3 °F, legacy 63.3 °F.
- Raised floor airflow: 124,000 CFM, modular 86,800 CFM (30% lower), legacy 80,600 CFM (35% lower).
- CRAH power: 55.9 kW, modular 19.2 kW (66% lower), legacy 15.4 kW (72% lower).
- Annual energy savings: modular $32,171, legacy $35,320 (24/7, $0.10/kWh).
- Deployment cost: modular $36,180, legacy $70,993; payback 13.5 and 24 months.
- Fan speeds were reduced so that maximum IT inlet stays within the ASHRAE recommended 80.6 °F (27 °C).
Using it in design
- Compare containment options on the CRAH fan speed reduction achievable and payback as well as inlet temperature.
- Complete cabinet rail and bottom front edge sealing and blanking panels before containment; the model assumes them in place.
- Reduce fan speed in steps while keeping maximum IT inlet below 27 °C.
- Recalculate the report's energy and cost figures with your own electricity price, CRAH fan curve and local installation cost.
- Confirm compatibility of containment with fire detection and suppression with the authority having jurisdiction.
Who should read it
Mechanical designers and operations managers selecting cold aisle containment for raised-floor rooms.
Document contents
- Executive Summary
- Data Center Model Configuration
- Detailed Analysis and Recommendations (CFD results, inlet temperature analysis)
- Containment Solutions and Energy Savings (CRAH blower speed, power, ROI)
- Summary Conclusions
Related standards
- ASHRAE TC 9.9 thermal guidelines
Publication details
- Authors
- Bruce Long; Lars Strong
- Publisher
- Upsite Technologies
- Year
- 2015
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
©2015 Upsite Technologies, Inc.
Citation
Bruce Long; Lars Strong (2015). AisleLok Modular Containment vs. Legacy Containment: A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings. Upsite Technologies. https://www.upsite.com/wp-content/uploads/AisleLok-Modular-Containment-vs.-Legacy-Containment-A-Comparative-CFD-Study-of-IT-Inlet-Temperatures-and-Fan-Energy-Savings.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.