Reducing Room-Level Bypass Airflow Creates Opportunities to Improve Cooling Capacity and Operating Costs

Original title Reducing Room-Level Bypass Airflow Creates Opportunities to Improve Cooling Capacity and Operating Costs (Bypass Airflow Clarified)

Upsite Technologies · Lars Strong

An Upsite white paper defining bypass airflow as any conditioned air that returns to cooling units without passing through IT equipment; in Upsite's study of 45 rooms an average 48% of conditioned air escapes through unsealed openings.

On this page

Overview

The paper defines bypass airflow as conditioned air supplied by a cooling unit that does not pass through IT equipment before returning; air passing through IT equipment more than once is IT exhaust air circulation. Ideally every unit of conditioned air passes through IT once; any airflow beyond what IT consumes is bypass. The original Uptime Institute research found on average 60% of cooling capacity escaping through unsealed cable openings and misplaced perforated tiles; Upsite's recent study of 45 computer rooms finds an average of 48%.

Data centers are said to have nearly four times the capacity they need on average. The common misconception is that managing raised floor openings, or even installing full containment, eliminates bypass. The paper argues these measures solve inlet temperature problems and may cut IT fan cost, but the bypass volume stays unchanged unless the volume supplied by cooling units changes; air formerly escaping through sealed openings simply shifts to the cold aisle.

In the simple example, a unit supplies 10 volumes, unsealed openings release 6 and perforated tiles 4, and IT consumes 4. After the openings are sealed all 10 come from tiles and 6 leave the cold aisle as bypass. Return air temperature does not change; raising return air set points is the only way to raise cooling unit efficiency and capacity.

The four-step method is: measure the existing Cooling Capacity Factor (CCF), improve airflow management at raised floor, rack and row in that order (the three R's), change the cooling infrastructure (raise set points, turn off units or reduce fan speeds), and repeat. CCF is the total rated capacity of running cooling units divided by 110% of IT critical load. Changes must be made while carefully monitoring IT equipment and keeping redundant units running.

Key points

  1. Bypass airflow is conditioned air returning to cooling units without passing through IT; any airflow above IT's consumption is bypass.
  2. The original Uptime Institute research found on average 60% of capacity escaping through leaks; Upsite's 45-room study finds an average of 48%.
  3. Data centers on average have nearly four times the capacity they need.
  4. Sealing floor openings or installing containment alone does not change bypass volume; it changes only if cooling unit airflow volume changes.
  5. CCF = total rated capacity of running cooling units (kW) / (110% of IT critical load, kW).
  6. The three R's order: Raised floor, Rack, Row.
  7. Raising return air set points is the only way to increase cooling unit efficiency and capacity.
  8. When turning units off, redundant units must keep running; the number depends on floor height, blockages and layout.

Using it in design

  • Calculate CCF for an existing room; with fixed-speed or full-speed fans CCF is a good indicator of the bypass ratio.
  • Apply airflow management in the order floor openings, rack plane (blanking, under-rack, rail gaps) and row gaps; consider containment after that.
  • After airflow management improvements raise return air set points and lower fan speed (VFD) or switch off surplus units, monitoring IT inlet temperature after each step.
  • Determine the number of redundant units considering floor height, layout and room load variation.
  • State in the specification that sealing wall and partition penetrations may need fire-rated materials.

Who should read it

Mechanical engineers and operations managers improving cooling capacity and operating cost in existing data halls.

Document contents

  1. Executive Summary
  2. The Evolution of Bypass Airflow
  3. Misunderstandings About Bypass Airflow
  4. Four Steps to Improve Bypass Airflow
  5. Conclusions
  6. Glossary of Terms (RFBOA, CCF, AFM)

Publication details

Authors
Lars Strong
Publisher
Upsite Technologies
Year
2013
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

© 2013 Upsite Technologies, Inc.; contents copyrighted

Citation

Lars Strong (2013). Reducing Room-Level Bypass Airflow Creates Opportunities to Improve Cooling Capacity and Operating Costs (Bypass Airflow Clarified). Upsite Technologies. https://www.upsite.com/wp-content/uploads/2017/08/Bypass-Airflow-Clarified-White-Paper.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.