ZutaCore HyperCool 6U Air Heat Rejection Unit Datasheet, version 2.0 (March 2024)
Original title HyperCool 6U Air Heat Rejection Unit Version 2.0
ZutaCore
ZutaCore's HyperCool 6U is an in-rack air heat rejection unit: up to 20 kW per rack at 27 °C inlet air, waterless dielectric two-phase cooling, pressure under 3.2 bar and under 650 W power.
On this page
Overview
The document is the March 2024 datasheet (version 2.0) for the 6U air heat rejection unit (HRU) of ZutaCore's HyperCool direct-to-chip, waterless dielectric liquid cooling solution. HyperCool cools heat-emitting server components such as CPU, GPU and FPGA. Its subsystems are the HRU, manifold, dielectric cold plate, service unit and software defined cooling (SDC) software.
The HRU is a self-contained 6U unit, 875 mm deep, that sits at the bottom of a 19-inch rack and handles up to 20 kW total rack power. The principle is two-phase: vapor heated at the cold plates in the servers flows via the manifold to the HRU, fans push air through the condenser coil to condense it to liquid, the liquid drops to a buffer tank and is pumped back to the servers. The refrigerant is non-conductive, non-corrosive, non-flammable and non-toxic, with zero ozone depletion and low global warming potential. No facility water infrastructure is needed.
Technical data: operating temperature 5 to 45 °C, humidity 20% to 70%, maximum working pressure 3.2 bar, 6 L buffer tank, 1/2 inch liquid and 1 1/2 inch vapor tri-clamp connections, 200 to 240 VAC at 50/60 Hz, power under 650 W. Size is 482 x 874.5 x 264 mm and dry weight 55 kg. Power at 25 °C air inlet rises with compute load from 80 W (0 kW) to 150 W (9.1 kW), 285 W (12.1 kW) and 645 W (15.1 kW). Maximum compute load depends on air inlet and T-case temperature: 12.8 kW at 25 °C air and 56 °C T-case, 17.4 kW at 65 °C T-case; 4.8 kW at 40 °C air and 56 °C T-case.
Key points
- 19-inch rack mounted 6U, 875 mm deep HRU; supports up to 20 kW per rack at 27 °C air inlet.
- Waterless, dielectric two-phase direct-to-chip cooling; non-conductive, non-flammable, low-pressure (under 3.2 bar) refrigerant.
- Maximum working pressure 3.2 bar; buffer tank 6 L; fluid working temperature range -76 to 65 °C.
- Operating environment 5 to 45 °C, humidity 20% to 70%; power 200 to 240 VAC, consumption under 650 W; N+1 phase redundancy.
- N+1 pump and fan redundancy; field-replaceable in-rack electronic and power components.
- HRU power at 25 °C air inlet: 80 W at 0 kW load, 75 W at 6.1 kW, 150 W at 9.1 kW, 285 W at 12.1 kW, 645 W at 15.1 kW.
- Maximum load (T-case 56/60/65 °C): 15 °C air 15/17.5/19.8 kW; 25 °C air 12.8/15.2/17.4 kW; 30 °C air 10.3/12.4/14.7 kW; 35 °C air 7.3/10/12.4 kW; 40 °C air 4.8/7.6/10.1 kW.
- Size 482 x 874.5 x 264 mm, dry weight 55 kg; RJ45 TCP/IP with API and network monitoring.
Using it in design
- For halls with no facility water or where a liquid loop cannot be built, consider an air HRU with direct-to-chip cooling for racks up to 20 kW.
- Read maximum compute load from the table by air inlet temperature and T-case target: at 35 °C air and 56 °C T-case only 7.3 kW is available; set hall temperature against this curve.
- Because the HRU sits at the rack bottom and takes 6U, check in-rack layout, load distribution and the 55 kg weight.
- Include the vapor (1 1/2 inch) and liquid (1/2 inch) tri-clamp connections in the manifold layout; add charging and gas purging with the service unit to the maintenance plan.
- Include HRU power with load (80 to 645 W) in the PUE and electrical design.
Who should read it
Data center designers and operators evaluating air-based heat rejection for direct-to-chip cooled racks.
Document contents
- Features and advantages
- HyperCool subsystems
- HRU installation requirements
- 6U HRU air overview
- 6U HRU air specifications (environmental, refrigerant, connections, dimensions)
- Power consumption as a function of computing load
- Maximum computing load as a function of ambient air temperature
Publication details
- Authors
- ZutaCore
- Publisher
- ZutaCore
- Year
- 2024
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
ZutaCore (2024). HyperCool 6U Air Heat Rejection Unit Version 2.0. ZutaCore. https://hello.zutacore.com/hubfs/HyperCool-6U-Air-Datasheet.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.