Data Center Chiller Plant: Simulation-based Comparative Control Design Case Study (2022 ASHRAE/IBPSA-USA Building Performance Analysis Conference and SimBuild)
ASHRAE / IBPSA-USA · Milica Grahovac, Paul Ehrlich et al.
A SimBuild 2022 paper uses the OpenBuildingControl toolchain to compare chiller-plant control sequences for a data centre; the ASHRAE Guideline 36-based sequence saves a quarter of annual cooling energy.
On this page
Overview
The paper was presented at the ASHRAE/IBPSA-USA SimBuild meeting and written by Milica Grahovac, Paul Ehrlich, Jianjun Hu and Michael Wetter (DOI 10.26868/25746308.2022.C042, pp. 373-381). It uses the OpenBuildingControl toolchain, with the Control Description Language being standardised as ASHRAE 231P, to compare chiller-plant control sequences for a data centre.
The model is a closed-loop plant of one chiller, a water-side economizer and an evaporative cooling tower serving 27 C supply air in Sacramento, California. A base sequence and an alternative based on ASHRAE Guideline 36 are run. The Guideline 36-style sequence, including condenser-water reset, cuts cooling energy 25% annually and about 18% in a typical summer.
Annual PUE is about 1.3 for the base and 1.29 for the alternative; non-IT, non-cooling loads (UPS, distribution, lighting) are assumed equal to 20% of cooling energy. Condenser-water reset cut tower fan energy about 88% annually (67% in summer), with average tower fan speed at 29%, at the cost of higher chilled-water pump energy. In the sensitivity analysis, raising the supply set point by 2 K increased savings to 28% annually, while lowering it by 2 K reduced savings to 11%. The authors argue that simulating real control sequences should become part of controls delivery. Limit: a single climate and a single plant configuration.
Key points
- Plant: one chiller, water-side economizer and evaporative cooling tower serving a data centre at 27 C supply air in Sacramento, California.
- Alternative (Guideline 36-based) controls cut cooling energy 25% annually and about 18% in a typical summer.
- Annual PUE of about 1.3 (base) and 1.29 (alternative); non-IT, non-cooling loads assumed equal to 20% of cooling energy.
- Condenser-water reset cut tower fan energy about 88% annually (67% in summer), average fan speed 29%, at the cost of higher chilled-water pump energy.
- Sensitivity: raising the supply set point 2 K increased savings to 28% annually; lowering it 2 K reduced savings to 11%.
Using it in design
- Give cooling plant templates a control-sequence attribute (for example Guideline 36 condenser-water reset, economizer modes); it materially changes annual energy.
- Expose supply-air set point sensitivity in the energy model.
- Include the pump energy increase caused by condenser-water reset in the net energy calculation.
- Add simulation-based verification of control sequences before commissioning to the handover criteria.
Monthly newsletter · free
Keep your reading list current
Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.
SoSo CAD
Check cooling capacity alongside your design
Review zone heat loads, available capacity and the capacity balance after the largest unit is lost in SoSo CAD.
Request a demo
Who should read it
Mechanical engineers and energy modellers designing cooling plants and control sequences.
Related standards
- ASHRAE Guideline 36
- ASHRAE Standard 231P (CDL)
- ASHRAE Standard 90.4
Publication details
- Authors
- Milica Grahovac; Paul Ehrlich; Jianjun Hu; Michael Wetter
- Publisher
- ASHRAE / IBPSA-USA
- Year
- 2022
- Document number
- DOI 10.26868/25746308.2022.C042, pp. 373-381
- Event
- ASHRAE/IBPSA-USA SimBuild 2022
- Document language
- English
- Source type
- Standard
- Access
- Free to read
- Licence
- Copyright retained; citation only — the publisher’s terms apply to the original document
Citation
Milica Grahovac; Paul Ehrlich; Jianjun Hu; Michael Wetter (2022). Data Center Chiller Plant: Simulation-based Comparative Control Design Case Study (2022 ASHRAE/IBPSA-USA Building Performance Analysis Conference and SimBuild). ASHRAE / IBPSA-USA. DOI 10.26868/25746308.2022.C042, pp. 373-381. ASHRAE/IBPSA-USA SimBuild 2022. https://publications.ibpsa.org/conference/paper/?id=simbuild2022_C042
Events on this subject
Browse the events calendarAll content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.