Mitigating arc flash hazards in medium-voltage switchgear
Consulting-Specifying Engineer · Syed M. Peeran
Peeran explains the IEEE 1584 arc-flash calculation for medium-voltage gear and quantifies the effect of mitigation measures with worked numbers.
On this page
Overview
Peeran's article explains the IEEE 1584 arc-flash calculation for medium-voltage gear. An important point is why arcing current approaches bolted fault current at 4.16 and 13.8 kV: at these voltages arcing current is about 90 percent of bolted fault current, whereas at 480 V it is much lower because of an arc drop of about 200 V. The article also quantifies the effect of mitigation measures.
The validity range of IEEE 1584 is 208 V-15 kV, 700-106,000 A bolted fault current and 0.5-6 in. gaps. Working distances are 36 in. for 5/15 kV gear, 24 in. for LV switchgear and 18 in. for MCCs and panels. MV arcing current follows lg(Ia) = 0.00402 + 0.983 lg(Ibf), and the calculation factor Cf is 1.0 above 1 kV and 1.5 at or below.
Mitigation methods covered include smaller high-impedance transformers, differential protection, current-limiting fuses, relay maintenance modes, light-sensing arc-flash relays, arc-resistant switchgear, crowbar devices and remote operation. Replacing a 3,000 kVA 6%Z transformer with a 1,500 kVA 8%Z unit cut fault current from 6,940 A to 2,603 A and incident energy by 62 percent.
In relay maintenance mode, lowering the instantaneous pickup from 16,000 A to 6,000 A cut clearing time from 1.303 s to 0.015 s and energy from 12 to 1.2 cal/cm2 (HRC 3 to 1). Current-limiting fuses clear within a half cycle (under 0.0083 s). Crowbar devices are covered by IEC 62271-200, with no US standard yet. The article dates from 2013 and rests on IEEE 1584-2002, so later editions may differ.
Key points
- IEEE 1584 validity: 208 V-15 kV, 700-106,000 A bolted fault, 0.5-6 in. gaps; working distance 36 in. for 5/15 kV gear, 24 in. LV switchgear, 18 in. MCCs and panels.
- At 4.16-13.8 kV arcing current is about 90 percent of bolted fault current; at 480 V it is much lower due to a roughly 200 V arc drop.
- MV arcing current: lg(Ia) = 0.00402 + 0.983 lg(Ibf); calculation factor Cf = 1.0 above 1 kV, 1.5 at or below.
- Replacing a 3,000 kVA 6%Z transformer with 1,500 kVA 8%Z cut fault current from 6,940 A to 2,603 A and incident energy by 62 percent.
- Relay maintenance mode: lowering instantaneous pickup from 16,000 A to 6,000 A cut clearing from 1.303 s to 0.015 s and energy from 12 to 1.2 cal/cm2 (HRC 3 to 1).
- Current-limiting fuses clear within a half cycle (under 0.0083 s); crowbar devices are covered by IEC 62271-200 with no US standard yet.
Using it in design
- Implement IEEE 1584 working distances per equipment class in the MV arc-flash module.
- Allow maintenance-mode relay settings as a scenario.
- Suggest transformer size and impedance alternatives when secondary incident energy is high.
- Show mitigation options such as current-limiting fuses, differential protection and light-sensing relays side by side.
Monthly newsletter · free
Keep your reading list current
Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.
SoSo CAD
Review your power design in SoSo CAD
Inspect supply paths, equipment loads and UPS failure scenarios in one model.
Request a demo
Who should read it
Electrical engineers designing medium-voltage switchgear and protection, and consultants carrying out arc-flash studies.
Related standards
- IEEE 1584-2002
- NFPA 70E
- NFPA 70 Art. 110.16
- IEC 62271-200
Publication details
- Authors
- Syed M. Peeran
- Publisher
- Consulting-Specifying Engineer
- Year
- 2013
- Document language
- English
- Source type
- Expert / community
- Access
- Free to read
- Licence
- Copyright retained; citation only — the publisher’s terms apply to the original document
Citation
Syed M. Peeran (2013). Mitigating arc flash hazards in medium-voltage switchgear. Consulting-Specifying Engineer. https://www.csemag.com/articles/mitigating-arc-flash-hazards-in-medium-voltage-switchgear/