Energy Consumption and Energy Saving Analysis of Air-Conditioning Systems of Data Centers in Typical Cities in China
Sustainability (MDPI AG) · Tiezhu Sun, Xiaojun Huang et al.
A survey of PUE and cooling load factor (CLF) of existing mechanically cooled data centres in seven Chinese cities from arid Urumqi to humid Haikou, binning each city's hourly wet- and dry-bulb data into operating-mode hours for two evaporative retrofit schemes.
CC BY 4.0 — share with attribution
On this page
Overview
The study examines the energy consumption status and saving potential of data-centre air-conditioning systems in seven cities with diverse climates (Xinjiang, Beijing, Jinan, Shanghai, Nanning, Guilin and Haikou), using PUE and cooling load factor (CLF) as indicators. The surveyed mechanically cooled data centres had CLF of 0.4-0.7 and PUE of 1.45-1.85, all above 1.3, with no clear relationship to city climate.
Two retrofit schemes are proposed: a water-side indirect evaporative chiller producing 15 °C water, and an air-side IEC air handler with dry, spray and mixed modes. In the water-side scheme, mode switching depends on outdoor wet-bulb: direct evaporative at Ts ≤ 13 °C; direct + indirect at 13 °C < Ts ≤ 15 °C; indirect + mechanical at Ts > 15 °C; the indirect evaporative chiller produces water 4-6 °C below ambient wet-bulb. For 15 °C chilled water, direct evaporative mode runs 6933 h in Urumqi, 5374 h in Beijing, 4020 h in Shanghai and only 262 h in Haikou, which needs indirect + mechanical cooling for 8112 h. The air-side IEC unit runs in dry mode 5773 h in Urumqi versus 415 h in Haikou, which spends 5997 h in mixed mode with compressor.
The water-system retrofit cut PUE from 1.62 to 1.13 (73.26% cooling energy saving) in Xinjiang and from 1.79 to 1.36 (41.23%) in Hainan; all retrofitted projects came in below 1.36. The air-system retrofit gave PUE below 1.39 everywhere, with the best case Xinjiang, 1.62 to 1.18 (69.26%).
Limits: saving estimates rest on simulation and operating-mode-hour calculation rather than measurement of installed systems, and the saving rate depends on climate and project specifics. The study provides a useful worked example of a climate potential-hours study for evaporative free cooling.
Key points
- Surveyed mechanically cooled data centres had CLF of 0.4-0.7 and PUE of 1.45-1.85, all above 1.3, with no clear relationship to city climate.
- Water-side scheme mode switching on outdoor wet-bulb: direct evaporative at Ts ≤ 13 °C; direct + indirect at 13-15 °C; indirect + mechanical above 15 °C; the indirect evaporative chiller produces water 4-6 °C below ambient wet-bulb.
- For 15 °C chilled water, direct evaporative mode runs 6933 h in Urumqi, 5374 h in Beijing, 4020 h in Shanghai and only 262 h in Haikou, which needs indirect + mechanical cooling for 8112 h.
- The air-side IEC unit runs in dry mode 5773 h in Urumqi versus 415 h in Haikou, which spends 5997 h in mixed mode with compressor.
- Water-system retrofit cut PUE from 1.62 to 1.13 (73.26% cooling energy saving) in Xinjiang and from 1.79 to 1.36 (41.23%) in Hainan; all retrofitted projects came in below 1.36.
- The air-system retrofit gave PUE below 1.39 everywhere; the best case was Xinjiang, 1.62 to 1.18 (69.26%).
Using it in design
- Show evaporative free-cooling feasibility with a potential-hours study that bins the city's hourly wet-bulb distribution against mode thresholds (13 and 15 °C); in a humid climate direct evaporative mode ran only 262 h a year.
- For retrofits of existing mechanically cooled halls, set the PUE target by climate (1.13-1.18 in arid climates, 1.36-1.39 in humid).
- Compare the water-side indirect evaporative chiller and the air-side IEC air handler on the same climate data.
Monthly newsletter · free
Keep your reading list current
Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.
SoSo CAD
Check cooling capacity alongside your design
Review zone heat loads, available capacity and the capacity balance after the largest unit is lost in SoSo CAD.
Request a demo
Who should read it
Designers and energy specialists assessing evaporative free-cooling retrofits of existing data centres in China and similar climates.
Document contents
- 1. Introduction
- 2. Research Data (2.1 Evaluation indicators, 2.2 Analysis of Research Data)
- 3. Introduction to Energy Saving Solutions
- 4. Analyses of Urban Meteorological Characteristics and Operating Time (4.1 Analysis of Climate Characteristics: Urumqi, Beijing, Jinan, Shanghai, Nanning, Guilin, Haikou, summary; 4.2 Operating-mode hours: water systems with indirect evaporative cooling chillers, air systems)
- 5. Analysis of Energy Saving Potential in Data Centers (5.2 Energy Savings from Air Systems Combined with Evaporative Cooling)
- 6. Conclusions
Related standards
- GB 50174
Read the document
dc-ac-energy-typical-cities-china-2023.pdf
CC BY 4.0 — share with attribution
The document is provided unaltered because its licence permits redistribution.
Publication details
- Authors
- Tiezhu Sun; Xiaojun Huang; Caihang Liang; Riming Liu; Yongcheng Yan
- Publisher
- Sustainability (MDPI AG)
- Year
- 2023
- Volume
- 15
- Issue
- 10
- Pages
- 7826
- Document language
- English
- Source type
- Scientific
- Access
- Open licence — downloadable
- Licence
- CC BY 4.0 — share with attribution
- Licence evidence
- www.mdpi.com
Original licence note
p.1 states the article is open access under the Creative Commons Attribution (CC BY) licence.
Citation
Tiezhu Sun; Xiaojun Huang; Caihang Liang; Riming Liu; Yongcheng Yan (2023). Energy Consumption and Energy Saving Analysis of Air-Conditioning Systems of Data Centers in Typical Cities in China. Sustainability (MDPI AG). 15(10), 7826. https://doi.org/10.3390/su15107826
Events on this subject
Browse the events calendarAll content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.