Immersion cooling fluid comparison using a single-phase immersion/liquid technique for data centers
Applied Thermal Engineering (Elsevier BV) · Ayoub Ruichek, Mohamad Hnayno et al.
The authors test four single-phase dielectric immersion fluids (Shell SL 3568, Fuchs FES 822-6542, Motul EGEN 100R8 and TotalEnergies BioLife 4) in a hybrid server: CPUs cooled by direct-to-chip water blocks, the rest of the board (RAM, NVMe, SSD) passively immersed in the fluid.
CC BY 4.0 — share with attribution
On this page
Overview
The study asks how different immersion fluids perform in a hybrid server. Fluids were ranked with the OCP Immersion Cooling Sub-Project Figure of Merit for natural convection (FOM1), component temperatures were measured, and a CFD model was validated for wider fluid screening; the CFD model matched experiments with a maximum temperature deviation of 10.7% (NVMe average temperature). SL 3568 properties: density 838/812/773 kg/m³ and kinematic viscosity 406/43/7.6 cSt at 0/40/100 °C, with thermal conductivity 0.142-0.134 W/m·K.
Roughly doubling FOM1 (BioLife 4 versus SL 3568) reduces the Prandtl number by about a factor of ten. A near doubling of FOM1 lowered average fluid temperature by approximately 7.7 °C. With roughly doubled FOM1, immersed RAMs, NVMes and SSDs ran about 6.7, 6.4 and 5.9 °C cooler respectively. Higher-FOM1 fluids cool immersed components better.
Unexpectedly, they make cold-plated CPUs hotter: CPU temperatures were highest with high-FOM1 fluids, attributed to dielectric fluid infiltrating the TIM between CPU and water block and reducing TIM viscosity by at least 94.4%. This is a compatibility risk for hybrid immersion/direct liquid cooling designs.
Limits: a single hybrid server and four commercial fluids; results are for this TIM (KP98) and server and must be re-verified for other TIM and fluid pairings. It shows a trade-off between cooling performance and TIM compatibility.
Key points
- Roughly doubling FOM1 (BioLife 4 vs SL 3568) reduces the Prandtl number by about a factor of ten.
- A near doubling of FOM1 lowered average fluid temperature by approximately 7.7 °C.
- With roughly doubled FOM1, immersed RAMs, NVMes and SSDs ran about 6.7, 6.4 and 5.9 °C cooler respectively.
- CPU temperatures were highest with high-FOM1 fluids, attributed to dielectric fluid infiltrating the TIM between CPU and water block and reducing TIM viscosity by at least 94.4%.
- The CFD model matched experiments with a maximum temperature deviation of 10.7% (NVMe average temperature).
- SL 3568 properties: density 838/812/773 kg/m³ and kinematic viscosity 406/43/7.6 cSt at 0/40/100 °C, thermal conductivity 0.142-0.134 W/m·K.
Using it in design
- In hybrid immersion/direct liquid cooling design, rank dielectric fluids by FOM1, but remember a high-FOM1 fluid can infiltrate the TIM of cold-plated CPUs and raise their temperature.
- Add fluid and TIM compatibility (viscosity drop of 94.4%) to design verification; in hybrid systems select the fluid together with a CPU cooling test.
- For immersed components (RAM, NVMe, SSD), a higher-FOM1 fluid gave 6-7 °C cooler operation; compare component-level temperature targets with that gain.
Monthly newsletter · free
Keep your reading list current
Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.
SoSo CAD
Check cooling capacity alongside your design
Review zone heat loads, available capacity and the capacity balance after the largest unit is lost in SoSo CAD.
Request a demo
Who should read it
Cooling engineers selecting dielectric fluids for single-phase immersion and hybrid direct liquid cooling.
Document contents
- 1. Introduction
- 3. Fluids comparison experimental test (3.1 Experimental setup and procedure, 3.2 Results and discussion: FOM1 criteria evaluation)
- 4. Numerical methodology (4.1 Model description, 4.2 Grid independence analysis, 4.3 Results and discussion: water and fluid behavior, IT components behavior)
- 5. Conclusion
Related standards
- OCP Immersion Cooling Sub-Project (FOM1)
Read the document
immersion-fluid-comparison-single-phase-2025.pdf
CC BY 4.0 — share with attribution
The document is provided unaltered because its licence permits redistribution.
Publication details
- Authors
- Ayoub Ruichek; Mohamad Hnayno; Ali Chehade; Farouk Fardoun; Tala Moussa; Guillaume Polidori; Chadi Maalouf
- Publisher
- Applied Thermal Engineering (Elsevier BV)
- Year
- 2025
- Volume
- 280
- Pages
- 128355
- Document language
- English
- Source type
- Scientific
- Access
- Open licence — downloadable
- Licence
- CC BY 4.0 — share with attribution
- Licence evidence
- hal.science
Original licence note
HAL deposit of the published version; HAL cover page states 'Distributed under a Creative Commons CC BY 4.0 - Attribution - International License' and the article p.1 says open access under CC BY. PDF page numbers include the 1-page HAL cover.
Citation
Ayoub Ruichek; Mohamad Hnayno; Ali Chehade; Farouk Fardoun; Tala Moussa; Guillaume Polidori; Chadi Maalouf (2025). Immersion cooling fluid comparison using a single-phase immersion/liquid technique for data centers. Applied Thermal Engineering (Elsevier BV). 280, 128355. https://doi.org/10.1016/j.applthermaleng.2025.128355
Events on this subject
- NVIDIA GTC
- SC26 – International Conference for High Performance Computing, Networking, Storage and Analysis
- Data Center World Middle East
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.