StandardCitation2023

An Investigation of Multi-Parameters Effects on the Performance of Liquid-to-Liquid Heat Exchangers in Rack Level Cooling (ITherm 2023)

IEEE · Ali Heydari, Qusai Soud et al.

An experimental study of a rack-mounted liquid-to-liquid CDU serving a rack of thermal test vehicles, looking at coolant supply temperature stability and case temperature uniformity under different controller settings (abstract only).

On this page

Overview

This record rests only on the abstract (metadata) of an experimental study presented at IEEE ITherm 2023. The study examines a rack-mounted liquid-to-liquid CDU feeding a multi-server rack of thermal test vehicles (TTVs) at several load levels. In the test set-up the CDU is connected to primary and secondary loops and serves the multi-server TTV rack at multiple heat loads. The full text is not in the record.

There are two performance indicators: stability of the coolant supply temperature and uniformity of TTV case temperatures. They were studied against different controller settings. This approach shows that not only the thermal capacity of the CDU but also the behaviour of its control loop determines the reliability of a liquid-cooled rack.

The main finding is that the integral (reset) term of the PID loop has the biggest effect on supply-temperature fluctuation; the integral coefficient was the most influential PID parameter for reducing it. It was also seen that small oscillations with amplitude under 1 C could grow into larger amplitudes under some settings.

The limit of the document is that only the abstract was assessed, and numeric tuning values, load levels and measurement uncertainty are not in the record. The result belongs to a specific CDU and test set-up, and generalising it would need further verification. For designers and commissioning teams the message is that CDU controller tuning should be verified across load steps.

Key points

  1. Test set-up: rack-mount CDU connected to primary and secondary loops serving a multi-server TTV rack at multiple heat loads.
  2. Target indicators: coolant supply temperature stability and TTV case-temperature uniformity.
  3. The integral (reset) coefficient was the most influential PID parameter for reducing supply-temperature fluctuation.
  4. Fluctuations with amplitude under 1 C could converge into larger oscillations depending on settings.
  5. The record rests only on the abstract (metadata).
  6. The study compares different controller settings.

Using it in design

  • Record controller type and supply-temperature stability (e.g. +/- C) in CDU catalogue entries.
  • Add a loop-tuning check of supply temperature stability across load steps to commissioning templates.
  • Document the integral term as a separate parameter in controller settings.

Monthly newsletter · free

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.

SoSo CAD

Check cooling capacity alongside your design

Review zone heat loads, available capacity and the capacity balance after the largest unit is lost in SoSo CAD.

Request a demo
Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Who should read it

Engineers who select, tune and commission CDUs for liquid-cooled racks.

Publication details

Authors
Ali Heydari; Qusai Soud; Mohammad Tradat; Ahmad Gharaibeh; Naimeh Fallahtafti; Pardeep Shahi; Jeremy Rodriguez; Bahgat Sammakia
Publisher
IEEE
Year
2023
Document number
DOI 10.1109/ITherm55368.2023.10177525
Event
IEEE ITherm 2023
Document language
English
Source type
Standard
Access
Citation only
Licence
Copyright retained; citation only — the publisher’s terms apply to the original document

Citation

Ali Heydari; Qusai Soud; Mohammad Tradat; Ahmad Gharaibeh; Naimeh Fallahtafti; Pardeep Shahi; Jeremy Rodriguez; Bahgat Sammakia (2023). An Investigation of Multi-Parameters Effects on the Performance of Liquid-to-Liquid Heat Exchangers in Rack Level Cooling (ITherm 2023). IEEE. DOI 10.1109/ITherm55368.2023.10177525. IEEE ITherm 2023. https://par.nsf.gov/biblio/10435662

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.