Research paperPDF2026

Toxicological and environmental evaluation of the two-phase immersion cooling fluid HFO-153-10mczz-E

Frontiers in Toxicology (Frontiers Media SA) · Grayson Abele, Sarah Smallets et al.

This review by TRC Strategic Health Sciences evaluates the human-health and environmental hazard of HFO-153-10mczz-E (decafluoro-3-hexene), a non-flammable hydrofluoroolefin dielectric fluid marketed for two-phase immersion cooling.

CC BY 4.0 — share with attribution

On this page

Overview

HFO-153-10mczz-E is a volatile, non-flammable hydrofluoroolefin (HFO) developed as a dielectric fluid in heat-transfer applications such as two-phase immersion cooling (2-PIC). Its high vapour pressure and low water solubility indicate inhalation is the primary route of exposure. The review compiles physical-chemical properties, atmospheric fate, inhalation toxicology, genotoxicity and reproductive studies, and a 2025 WEEL occupational exposure limit. The fluid falls in the short-chain PFAS category under the OECD structural definition.

Properties: boiling point of 48.8 °C, melting point below -54 °C, no flash point across 0-40 °C, autoignition temperature of 580 °C and water solubility of 794.1 µg/L. Estimated atmospheric lifetimes are 71 days for the (E)-isomer and 37 days for the (Z)-isomer; GWP of the (E)-isomer is 36, 10 and 3 for 20-, 100- and 500-year horizons. The 13-week rat inhalation study found no adverse effects up to 3,037 ppm (NOAEC), and the WEEL committee used a 3,000 ppm point of departure to set a recommended occupational exposure limit of 200 ppm. Acute data classify the compound as 'Practically Non-toxic' on the Hodge and Sterner scale (LC50 between 5,000 and 15,000 ppm).

2-PIC fluids need low boiling points (40-60 °C), high dielectric strength, non-flammability and material compatibility, so feasible substitutes are a narrow class of high-volatility dielectrics; single-phase oils and esters are not viable replacements. The authors conclude it is low-hazard with limited exposure potential, mainly by inhalation.

Limits: all underlying studies were sponsored by the manufacturer (Chemours), and the authors flag gaps in chronic, endocrine and real-world release data: limited human toxicokinetic and endocrine data, aquatic-test limitations from volatility, and scarce occupational exposure and release data. Developments in PFAS regulation may affect selection.

Key points

  1. HFO-153-10mczz-E meets the OECD structural definition of a PFAS and falls in the short-chain PFAS category.
  2. Boiling point 48.8 °C, melting point below -54 °C, no flash point across 0-40 °C, autoignition temperature 580 °C and water solubility 794.1 µg/L.
  3. Estimated atmospheric lifetimes are 71 days for the (E)-isomer and 37 days for the (Z)-isomer; GWP of the (E)-isomer is 36, 10 and 3 for 20-, 100- and 500-year horizons.
  4. The 13-week rat inhalation study found no adverse effects up to 3,037 ppm (NOAEC); the WEEL committee used a 3,000 ppm point of departure to set a recommended occupational exposure limit of 200 ppm.
  5. Acute data classify the compound as 'Practically Non-toxic' on the Hodge and Sterner scale (LC50 between 5,000 and 15,000 ppm).
  6. 2-PIC fluids need low boiling points (40-60 °C), high dielectric strength, non-flammability and material compatibility; single-phase oils and esters are not viable replacements.
  7. Stated uncertainties include limited human toxicokinetic and endocrine data, aquatic-test limitations from volatility, scarce occupational exposure and release data, and that all toxicity studies were performed on behalf of Chemours.

Using it in design

  • When selecting a two-phase immersion fluid, add toxicology and occupational exposure limit (here WEEL 200 ppm) to the specification alongside boiling point (40-60 °C), dielectric strength, non-flammability and material compatibility.
  • Assess the fluid's short-chain PFAS status and regulatory risk in procurement and operating decisions.
  • Document in the alternatives assessment that single-phase oils and esters are not viable 2-PIC replacements, and consider ventilation and detection for fluid release and inhalation exposure.

Monthly newsletter · free

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.

SoSo CAD

Check cooling capacity alongside your design

Review zone heat loads, available capacity and the capacity balance after the largest unit is lost in SoSo CAD.

Request a demo
Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Who should read it

Engineers and specialists selecting two-phase immersion cooling fluids and doing procurement and EHS assessment.

Document contents

  1. 1 Introduction
  2. 2 Materials and methods
  3. 3 Physical, chemical, and environmental fate (3.1 Physicochemical properties, 3.2 Partitioning, 3.3 Biodegradability, 3.4 Environmental fate)
  4. 4 Toxicology (4.1 Acute and subacute toxicity, 4.2 Reproductive and developmental, 4.3 Genotoxicity and mutagenicity, 4.4 Cardiac sensitization, 4.5 Eye irritation, 4.6 Skin irritation and sensitization, 4.7 Environmental/aquatic toxicity)
  5. 5 Discussion (5.1 Human health hazard profile, 5.2 Environmental hazard, 5.3 Alternatives assessment considerations, 5.4 Uncertainties and implications for use)
  6. 6 Conclusion

Related standards

  • OECD PFAS definition (2021)
  • OECD Test Guidelines (GLP)

Read the document

hfo-2pic-fluid-toxicology-2026.pdf

PDF · 2.2 MB · English

CC BY 4.0 — share with attribution

The document is provided unaltered because its licence permits redistribution.

Publication details

Authors
Grayson Abele; Sarah Smallets; My Hua; Aryatara Shakya; David Brew; Patricia Underwood; Dennis Paustenbach
Publisher
Frontiers in Toxicology (Frontiers Media SA)
Year
2026
Volume
8
Pages
1840120
Document language
English
Source type
Scientific
Access
Open licence — downloadable
Licence
CC BY 4.0 — share with attribution
Licence evidence
doi.org
Original licence note

Article states it is open access under a Creative Commons Attribution (CC BY / CC BY 4.0) licence (verified in PDF text).

Citation

Grayson Abele; Sarah Smallets; My Hua; Aryatara Shakya; David Brew; Patricia Underwood; Dennis Paustenbach (2026). Toxicological and environmental evaluation of the two-phase immersion cooling fluid HFO-153-10mczz-E. Frontiers in Toxicology (Frontiers Media SA). 8, 1840120. https://doi.org/10.3389/ftox.2026.1840120

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.