White paperFree to read2023

Comparison of Dielectric Fluids for Immersive Liquid Cooling of IT Equipment

Schneider Electric · Robert Bunger, Paul Lin

A Schneider Electric white paper comparing the two dielectric fluid families used in immersion cooling, hydrocarbon oils and fluorocarbons, on cost, material compatibility, safety, environmental impact and maintenance.

On this page

Overview

The paper compares the two fluid families used in immersion cooling: hydrocarbon oils (mineral, synthetic, bio-based) and fluorocarbons (used in single- and two-phase systems). The comparison covers TCO, material compatibility, safety (flash point, toxicity), environmental impact, and IT maintenance and handling. Synthetic oils are cheap and benign but make servicing messy; fluorocarbons evaporate cleanly and are compatible with more materials, but cost more.

The numbers: hydrocarbon fluid flash points run from about 115 C for mineral oil to more than 200 C for synthetics (one example 268 C). Fluorocarbon boiling points range from about 50 C for two-phase use to about 270 C for single-phase use. Single-phase immersion dielectric typically operates at about 50 to 60 C, reaching the OSHA touch-safety threshold of 60 C at the high end. Sealed two-phase systems can lose about 1 to 2% of fluid (evaporation) per year.

Regulatory risk is decisive. Many fluorocarbons are PFAS; 3M's announced exit from all PFAS manufacturing by the end of 2025, and emerging EU and US restrictions, are named as the key risks for two-phase systems. Fluoroketones can have a GWP below 1. On fire safety, a flash point above 93 C gives a lower NFPA 704 flammability rating, and the paper advises engaging the local AHJ.

Key points

  1. Hydrocarbon immersion fluids: flash point from about 115 C (mineral oil) to more than 200 C (synthetic); one example 268 C.
  2. Fluorocarbon boiling points range from about 50 C (two-phase use) to about 270 C (single-phase use).
  3. Single-phase immersion dielectric typically operates at about 50 to 60 C, reaching the OSHA touch-safety threshold of 60 C at the high end.
  4. Sealed two-phase systems can lose about 1 to 2% of fluid (evaporation) per year.
  5. Fluoroketones can have GWP below 1, but many fluorocarbons are PFAS; 3M announced exit from all PFAS manufacturing by end of 2025.
  6. NFPA 704: a flash point above 93 C gives a lower flammability rating; engage the local AHJ.

Using it in design

  • Add a dielectric-fluid catalog with family (hydrocarbon, fluorocarbon), phase (1p, 2p), flash point, boiling point, GWP, PFAS status, cost per litre and annual loss percentage.
  • In fire and compliance checks, flag hydrocarbon fluids with a flash point below 93 C for AHJ review and NFPA 704 labelling.
  • Flag PFAS fluids with a regulatory-risk warning.
  • In the O&M module, add servicing-time and drip-tray requirements for oil immersion.

Monthly newsletter · free

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.

SoSo CAD

Check cooling capacity alongside your design

Review zone heat loads, available capacity and the capacity balance after the largest unit is lost in SoSo CAD.

Request a demo
Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Who should read it

Engineers selecting fluids for immersion cooling, fire and environmental compliance owners, and operations teams.

Related standards

  • NFPA 704
  • NFPA 75
  • EU PFAS restriction proposal (ECHA)
  • ASHRAE TC9.9 Liquid Cooling Guidelines

Publication details

Authors
Robert Bunger; Paul Lin
Publisher
Schneider Electric
Year
2023
Document number
WP 291
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only — the publisher’s terms apply to the original document

Citation

Robert Bunger; Paul Lin (2023). Comparison of Dielectric Fluids for Immersive Liquid Cooling of IT Equipment. Schneider Electric. WP 291. https://download.schneider-electric.com/files?p_Doc_Ref=SPD_WP291_EN

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.