Comparison of Dielectric Fluids for Immersive Liquid Cooling of IT Equipment
Schneider Electric · Robert Bunger, Paul Lin
A Schneider Electric white paper comparing the two dielectric fluid families used in immersion cooling, hydrocarbon oils and fluorocarbons, on cost, material compatibility, safety, environmental impact and maintenance.
On this page
Overview
The paper compares the two fluid families used in immersion cooling: hydrocarbon oils (mineral, synthetic, bio-based) and fluorocarbons (used in single- and two-phase systems). The comparison covers TCO, material compatibility, safety (flash point, toxicity), environmental impact, and IT maintenance and handling. Synthetic oils are cheap and benign but make servicing messy; fluorocarbons evaporate cleanly and are compatible with more materials, but cost more.
The numbers: hydrocarbon fluid flash points run from about 115 C for mineral oil to more than 200 C for synthetics (one example 268 C). Fluorocarbon boiling points range from about 50 C for two-phase use to about 270 C for single-phase use. Single-phase immersion dielectric typically operates at about 50 to 60 C, reaching the OSHA touch-safety threshold of 60 C at the high end. Sealed two-phase systems can lose about 1 to 2% of fluid (evaporation) per year.
Regulatory risk is decisive. Many fluorocarbons are PFAS; 3M's announced exit from all PFAS manufacturing by the end of 2025, and emerging EU and US restrictions, are named as the key risks for two-phase systems. Fluoroketones can have a GWP below 1. On fire safety, a flash point above 93 C gives a lower NFPA 704 flammability rating, and the paper advises engaging the local AHJ.
Key points
- Hydrocarbon immersion fluids: flash point from about 115 C (mineral oil) to more than 200 C (synthetic); one example 268 C.
- Fluorocarbon boiling points range from about 50 C (two-phase use) to about 270 C (single-phase use).
- Single-phase immersion dielectric typically operates at about 50 to 60 C, reaching the OSHA touch-safety threshold of 60 C at the high end.
- Sealed two-phase systems can lose about 1 to 2% of fluid (evaporation) per year.
- Fluoroketones can have GWP below 1, but many fluorocarbons are PFAS; 3M announced exit from all PFAS manufacturing by end of 2025.
- NFPA 704: a flash point above 93 C gives a lower flammability rating; engage the local AHJ.
Using it in design
- Add a dielectric-fluid catalog with family (hydrocarbon, fluorocarbon), phase (1p, 2p), flash point, boiling point, GWP, PFAS status, cost per litre and annual loss percentage.
- In fire and compliance checks, flag hydrocarbon fluids with a flash point below 93 C for AHJ review and NFPA 704 labelling.
- Flag PFAS fluids with a regulatory-risk warning.
- In the O&M module, add servicing-time and drip-tray requirements for oil immersion.
Monthly newsletter · free
Keep your reading list current
Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.
SoSo CAD
Check cooling capacity alongside your design
Review zone heat loads, available capacity and the capacity balance after the largest unit is lost in SoSo CAD.
Request a demo
Who should read it
Engineers selecting fluids for immersion cooling, fire and environmental compliance owners, and operations teams.
Related standards
- NFPA 704
- NFPA 75
- EU PFAS restriction proposal (ECHA)
- ASHRAE TC9.9 Liquid Cooling Guidelines
Publication details
- Authors
- Robert Bunger; Paul Lin
- Publisher
- Schneider Electric
- Year
- 2023
- Document number
- WP 291
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only — the publisher’s terms apply to the original document
Citation
Robert Bunger; Paul Lin (2023). Comparison of Dielectric Fluids for Immersive Liquid Cooling of IT Equipment. Schneider Electric. WP 291. https://download.schneider-electric.com/files?p_Doc_Ref=SPD_WP291_EN