Base Specification for Single Phase Water-Based Cold Plate Coolants v1.3

Open Compute Project · Philip Yu

This 2026 OCP specification defines water-based (including propylene-glycol-based) coolant properties for single-phase cold plate technology cooling systems. It gives numeric limits for conductivity, pH, turbidity and microbial count.

On this page

Overview

The acceptance limits are clear: conductivity below 2,000 uS/cm, pH 8.0-10.5 (buffered), turbidity below 5 NTU and total viable bacteria count below 1 CFU/ml. The base water must be purified, with low conductivity and TDS, and ASTM Type IV reagent water is given as an example. In other words a purified base water is wanted rather than tap water, with an inhibitor and biocide package added afterwards.

The specification calls for inhibitor and biocide packages, so corrosion and microbial growth stay under control over the loop's life. The limits underpin fluid-quality checks at commissioning and during continuing monitoring; how often to measure is this summary's design suggestion, not a requirement of the specification itself. The biocide package covers the microbial side that the inhibitor does not protect, while the inhibitor limits corrosion on metal surfaces. Together they aim to keep the narrow channels in the cold plate from clogging.

The scope is the fluid in the cold plate TCS loop; the facility water (FWS) needs separate limits. The ASHRAE TC9.9 water-cooled servers white paper gives TCS conductivity of 0.2-20 micromho/cm, turbidity below 20 NTU and pH 8.0-9.5, while this specification gives 2,000 uS/cm, 5 NTU and pH 8.0-10.5. The values do not align, so the project specification must state which source governs.

Key points

  1. Conductivity below 2,000 uS/cm.
  2. pH 8.0-10.5 (buffered).
  3. Turbidity below 5 NTU.
  4. Total viable bacteria count below 1 CFU/ml.
  5. Base water: purified, low conductivity/TDS (e.g. ASTM Type IV reagent water).
  6. Inhibitor and biocide packages are required.

Using it in design

  • In the commissioning and operations module, generate a TCS fluid-quality test plan with these acceptance limits (conductivity, pH, turbidity, total viable count) at fill and at periodic intervals (default quarterly).
  • Define water/inhibitor and PG25 options with property sets in the coolant catalog.
  • Show the TCS pH difference between the ASHRAE white paper (8.0-9.5) and this specification (8.0-10.5) and make the project pick one.

Monthly newsletter · free

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.

SoSo CAD

Check cooling capacity alongside your design

Review zone heat loads, available capacity and the capacity balance after the largest unit is lost in SoSo CAD.

Request a demo
Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Who should read it

Engineers who audit cold plate TCS fluid quality during commissioning and operation.

Related standards

  • OCP ACS Cold Plate Requirements
  • ASHRAE TC9.9 Liquid Cooling Guidelines

Publication details

Authors
Philip Yu
Publisher
Open Compute Project
Year
2026
Document number
v1.3
Document language
English
Source type
Industry body
Access
Free to read
Licence
Copyright retained; citation only — the publisher’s terms apply to the original document

Citation

Philip Yu (2026). Base Specification for Single Phase Water-Based Cold Plate Coolants v1.3. Open Compute Project. v1.3. https://www.opencompute.org/documents/base-specification-for-single-phase-water-based-cold-plate-coolant-v1-3-final-pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.