Base Specification for Single Phase Water-Based Cold Plate Coolants v1.3
Open Compute Project · Philip Yu
This 2026 OCP specification defines water-based (including propylene-glycol-based) coolant properties for single-phase cold plate technology cooling systems. It gives numeric limits for conductivity, pH, turbidity and microbial count.
On this page
Overview
The acceptance limits are clear: conductivity below 2,000 uS/cm, pH 8.0-10.5 (buffered), turbidity below 5 NTU and total viable bacteria count below 1 CFU/ml. The base water must be purified, with low conductivity and TDS, and ASTM Type IV reagent water is given as an example. In other words a purified base water is wanted rather than tap water, with an inhibitor and biocide package added afterwards.
The specification calls for inhibitor and biocide packages, so corrosion and microbial growth stay under control over the loop's life. The limits underpin fluid-quality checks at commissioning and during continuing monitoring; how often to measure is this summary's design suggestion, not a requirement of the specification itself. The biocide package covers the microbial side that the inhibitor does not protect, while the inhibitor limits corrosion on metal surfaces. Together they aim to keep the narrow channels in the cold plate from clogging.
The scope is the fluid in the cold plate TCS loop; the facility water (FWS) needs separate limits. The ASHRAE TC9.9 water-cooled servers white paper gives TCS conductivity of 0.2-20 micromho/cm, turbidity below 20 NTU and pH 8.0-9.5, while this specification gives 2,000 uS/cm, 5 NTU and pH 8.0-10.5. The values do not align, so the project specification must state which source governs.
Key points
- Conductivity below 2,000 uS/cm.
- pH 8.0-10.5 (buffered).
- Turbidity below 5 NTU.
- Total viable bacteria count below 1 CFU/ml.
- Base water: purified, low conductivity/TDS (e.g. ASTM Type IV reagent water).
- Inhibitor and biocide packages are required.
Using it in design
- In the commissioning and operations module, generate a TCS fluid-quality test plan with these acceptance limits (conductivity, pH, turbidity, total viable count) at fill and at periodic intervals (default quarterly).
- Define water/inhibitor and PG25 options with property sets in the coolant catalog.
- Show the TCS pH difference between the ASHRAE white paper (8.0-9.5) and this specification (8.0-10.5) and make the project pick one.
Monthly newsletter · free
Keep your reading list current
Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.
SoSo CAD
Check cooling capacity alongside your design
Review zone heat loads, available capacity and the capacity balance after the largest unit is lost in SoSo CAD.
Request a demo
Who should read it
Engineers who audit cold plate TCS fluid quality during commissioning and operation.
Related standards
- OCP ACS Cold Plate Requirements
- ASHRAE TC9.9 Liquid Cooling Guidelines
Publication details
- Authors
- Philip Yu
- Publisher
- Open Compute Project
- Year
- 2026
- Document number
- v1.3
- Document language
- English
- Source type
- Industry body
- Access
- Free to read
- Licence
- Copyright retained; citation only — the publisher’s terms apply to the original document
Citation
Philip Yu (2026). Base Specification for Single Phase Water-Based Cold Plate Coolants v1.3. Open Compute Project. v1.3. https://www.opencompute.org/documents/base-specification-for-single-phase-water-based-cold-plate-coolant-v1-3-final-pdf
Events on this subject
- SC26 – International Conference for High Performance Computing, Networking, Storage and Analysis
- Data Center World Middle East
- Datacenter Forum Stockholm
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.