White paperFree to read2012

Choosing Between Room, Row, and Rack-based Cooling for Data Centers

Schneider Electric · Kevin Dunlap, Neil Rasmussen

This paper compares room-, row- and rack-based cooling architectures, with and without containment, on first cost, efficiency, predictability and density capability. It gives clear thresholds for choosing.

On this page

Overview

The paper compares room-based, row-based and rack-based cooling architectures, with and without containment, on first cost, efficiency, predictability and density capability. The goal is clear guidance on which architecture to choose given project scale and density. Uncontained room cooling works for low, stable densities (about 1 to 2 kW per rack; 323 to 753 W/m2) but becomes unpredictable and wasteful as rack power rises. The recommendation: for new data centres above 200 kW, room-based cooling with hot-aisle containment; below 200 kW, row-based cooling with no raised floor needed. For existing rooms, row-based cooling is advised for pods of 5 kW per rack or more.

Rack-based (closed) cooling reaches the highest densities, up to about 50 kW per rack, and is reserved for extreme density or unstructured layouts. The analysis assumes IT airflow of 120 cfm per kW, and an uncontained room delivers about 125 percent of rated airflow because of mixing and bypass. Close-coupled row cooling can save more than 50 percent of fan power.

A 480 kW case study compares the electrical cost of each approach across 3 to 20 kW per rack. N+1 row-based cooling remains practical up to about 25 kW per rack, while the number of room CRAHs can roughly double above 10 kW per rack to keep N+1. Containment strategies make operating densities of 3 kW per rack or higher practical.

The thresholds convert directly into a cooling-architecture recommender: for a new build, room cooling with hot-aisle containment if IT load is above 200 kW and row-based cooling below it. In a legacy room, a row-based pod is suggested if a zone averages above 5 kW per rack, and rack-based or liquid cooling above 25 kW per rack. The default airflow is 120 cfm per kW.

Key points

  1. Uncontained room cooling is effective at about 1 to 2 kW per rack (323 to 753 W/m2, 30 to 70 W/ft2)
  2. New data centres above 200 kW: room-based cooling with hot-aisle containment
  3. New data centres below 200 kW: row-based, no raised floor; existing rooms use row-based for pods of 5 kW/rack or more
  4. Rack-based (closed) cooling reaches up to about 50 kW per rack
  5. Analysis assumption: IT airflow 120 cfm per kW; uncontained room delivers about 125 percent of rated airflow due to mixing/bypass
  6. Row-based close coupling can save more than 50 percent fan power versus uncontained room cooling
  7. N+1 row-based remains practical up to about 25 kW per rack; room CRAH count can roughly double above 10 kW/rack
  8. Containment makes operating densities of 3 kW per rack or higher practical

Using it in design

  • Drive the cooling-architecture recommender: for a new build with IT load above 200 kW, default to room cooling + hot-aisle containment
  • Below 200 kW, default to row-based cooling
  • If any zone in a legacy room averages above 5 kW/rack, suggest a row-based pod
  • Above 25 kW/rack, suggest rack-based or liquid cooling
  • Use 120 cfm/kW as the default airflow factor, with a 1.25 bypass multiplier for uncontained rooms and 1.0 to 1.1 when contained

Monthly newsletter · free

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.

SoSo CAD

Check cooling capacity alongside your design

Review zone heat loads, available capacity and the capacity balance after the largest unit is lost in SoSo CAD.

Request a demo
Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Who should read it

Data-centre designers and consultants choosing a cooling architecture.

Related standards

  • ASHRAE TC9.9 Thermal Guidelines
  • ASHRAE 90.4

Publication details

Authors
Kevin Dunlap; Neil Rasmussen
Publisher
Schneider Electric
Year
2012
Document number
WP 130
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only — the publisher’s terms apply to the original document

Citation

Kevin Dunlap; Neil Rasmussen (2012). Choosing Between Room, Row, and Rack-based Cooling for Data Centers. Schneider Electric. WP 130. https://download.schneider-electric.com/files?p_Doc_Ref=SPD_VAVR-6J5VYJ_EN

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.