White paperFree to read2017

The Use of Ceiling-Ducted Air Containment in Data Centers

Schneider Electric · Jim VanGilder, Simon Zhang et al.

This 2017 Schneider Electric white paper examines hot-air containment that ducts IT exhaust into a drop-ceiling return plenum: passive individually ducted racks (chimneys), fan-assisted ducted racks and ducted hot-aisle containment (HACS).

On this page

Overview

Using a flow-network model coupled to CFD, the analysis shows that performance is governed mainly by the vacuum the ceiling plenum holds relative to the room, which depends on cooling-to-IT airflow ratio, ceiling leakiness and plenum depth, more than on duct construction. Assumptions are IT airflow of 125 cfm/kW (212 m3/h/kW), racks filled to 30U, HACS clusters of 20 racks and 8 in (200 mm) server-to-rear-door clearance for ducted racks; 'Bad' means at least 10% recirculation.

At a plenum vacuum of 0.03 inH2O (7.5 Pa), individually ducted racks are limited to about 8 kW/rack while ducted HACS supports up to about 16 kW/rack. Vacuum above 0.03 inH2O needs deliberate sealing effort, and above about 0.06 inH2O (15 Pa) typical ceiling tiles begin to lift, capping achievable vacuum. A cooling-to-IT airflow ratio of 1 is generally acceptable for ducted HACS, but ducted racks may need 1.2 or higher. Rack-to-rack uniformity for HACS is good with plenums deeper than 18-24 in (0.46-0.61 m), even at 12 kW racks.

Active ducted racks allow up to about 12 kW/rack but add about 10 in (250 mm) to rack depth. Capital cost per rack is $500-700 for passive ducted, $1,800-2,000 for active ducted and $500-1,000 for ducted HACS.

The recommendation is to fix plenum pressure before adding fans. Implementation guidance: plenum at least 18 in (450 mm) deep, and ducted cooling airflow at least 10% above ducted IT airflow, or 20% for passive ducted racks with leaky ceilings.

Key points

  1. At 0.03 inH2O (7.5 Pa) vacuum, ducted racks reach about 8 kW/rack and ducted HACS about 16 kW/rack.
  2. Above about 0.06 inH2O (15 Pa), typical ceiling tiles lift and cap the vacuum.
  3. Cooling-to-IT airflow ratio: 1 for HACS, 1.2 or higher for ducted racks.
  4. HACS uniformity is good with plenums deeper than 18-24 in (0.46-0.61 m), even at 12 kW racks.
  5. Active ducted racks reach about 12 kW/rack and add about 10 in (250 mm) of depth.
  6. Cost per rack: passive $500-700, active $1,800-2,000, ducted HACS $500-1,000.
  7. Plenum at least 18 in (450 mm); ducted cooling airflow at least 10% above IT (20% for passive racks with leaky ceilings).

Using it in design

  • Add passive and active ducted racks and ducted HACS to the containment selector, with density limits tied to a ceiling plenum vacuum input (default 0.03 inH2O / 7.5 Pa, warning above 0.06 inH2O / 15 Pa).
  • Raise an error for plenum depth under 18 in (450 mm) in ducted designs, and warn when the cooling/IT airflow ratio is under 1.1 (1.2 for passive chimneys).
  • Suggest ducted HACS when a passive chimney rack exceeds about 8 kW.
  • For active ducted racks, state that CFD verification is required and add 250 mm to rack depth or row pitch.

Monthly newsletter · free

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.

SoSo CAD

Check cooling capacity alongside your design

Review zone heat loads, available capacity and the capacity balance after the largest unit is lost in SoSo CAD.

Request a demo
Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Who should read it

Cooling and layout engineers designing ceiling-plenum containment.

Related standards

  • ASHRAE TC 9.9 Thermal Guidelines for Data Processing Environments
  • EN 50600-2-3

Publication details

Authors
Jim VanGilder; Simon Zhang; Paul Lin
Publisher
Schneider Electric
Year
2017
Document number
WP 182
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only — the publisher’s terms apply to the original document

Citation

Jim VanGilder; Simon Zhang; Paul Lin (2017). The Use of Ceiling-Ducted Air Containment in Data Centers. Schneider Electric. WP 182. https://download.schneider-electric.com/files?p_Doc_Ref=SPD_VAVR-8Q7K3X_EN

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.