The Different Types of Air Distribution for IT Environments
Schneider Electric · Neil Rasmussen
Neil Rasmussen's paper classifies data-centre air distribution into a 3x3 taxonomy of nine types, depending on whether supply and return paths are flooded, targeted or contained, and gives each a density ceiling.
On this page
Overview
In the taxonomy, supply and return can each be flooded, targeted or contained. Targeted means a mechanism (duct, perforated tile, in-row cooler) directs air within 3 meters (10 feet) of IT intake and exhaust; contained means complete enclosure with no mixing. For each combination the paper gives typical applications, relative efficiency, the share of hot exhaust captured and an indicative maximum rack density.
The figures form a clear staircase. Flooded supply with flooded return cools up to 3 kW per rack and suits small LAN rooms under 40 kW. Flooded supply with targeted return reaches 6 kW and captures 40-70% of exhaust; targeted/targeted reaches 8 kW and 60-80%. Any combination with contained return (or contained supply) is rated to 30 kW, and contained return captures 70-100% of hot exhaust.
The recommendations rest on market reality: traditional raised-floor flooded-return systems reliably cool only 5-6 kW per rack by design, while typical racks draw 3-5 kW and some exceed 30 kW. New builds are advised to use a hard floor with contained return, and row-based targeted-supply hard-floor implementations are recommended below 1 MW. Containing one air stream is judged enough; containing both is advised only for harsh environments.
Key points
- Targeted means a mechanism (duct, perforated tile, in-row cooler) directs air within 3 meters (10 feet) of IT intake and exhaust; contained means full enclosure with no mixing.
- Flooded supply/flooded return cools up to 3 kW per rack and suits small LAN rooms under 40 kW.
- Flooded supply/targeted return reaches 6 kW and captures 40-70% of exhaust; targeted/targeted reaches 8 kW and 60-80%.
- Any combination with contained return (or contained supply) is rated up to 30 kW; contained return captures 70-100% of exhaust.
- Traditional raised-floor flooded-return systems reliably cool only 5-6 kW per rack; typical racks are 3-5 kW and some exceed 30 kW.
- Row-based targeted-supply hard-floor implementations are recommended for data centres below 1 MW.
- Contained supply or return is generally used for 5-15 kW racks; containing both streams is not recommended outside harsh environments.
Using it in design
- Model each white-space zone with supplyMode and returnMode enums (flooded, targeted, contained).
- Compare the zone's maximum rack kW with the ceiling for its combination (3/6/6/8/30 kW) and warn when exceeded; warn when both supply and return are contained without a harsh-environment flag.
- Default new builds to hard floor plus contained return, and suggest row-based cooling for halls under 1 MW.
- Offer a 3x3 picker in the UI that shows capture ratio and density limit for each cell.
Monthly newsletter · free
Keep your reading list current
Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.
SoSo CAD
Check cooling capacity alongside your design
Review zone heat loads, available capacity and the capacity balance after the largest unit is lost in SoSo CAD.
Request a demo
Who should read it
Mechanical designers and decision makers choosing the air distribution architecture for a new hall.
Related standards
- ASHRAE TC 9.9 Thermal Guidelines
Publication details
- Authors
- Neil Rasmussen
- Publisher
- Schneider Electric
- Year
- 2020
- Document number
- WP 55
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only — the publisher’s terms apply to the original document
Citation
Neil Rasmussen (2020). The Different Types of Air Distribution for IT Environments. Schneider Electric. WP 55. https://download.schneider-electric.com/files?p_Doc_Ref=SPD_NRAN-5TN9QM_EN
Events on this subject
- ISK-SODEX Istanbul 2027
- SC26 – International Conference for High Performance Computing, Networking, Storage and Analysis
- ASHRAE Winter Conference
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.