Guidelines for Specification of Data Center Power Density
Schneider Electric · Neil Rasmussen
This paper argues that watts per square foot or metre is an ambiguous and misleading way to specify density. It proposes specifying per rack with both average and peak values.
On this page
Overview
The paper argues that specifying density in W/ft2 or W/m2 is ambiguous and misleading. The same hypothetical 500 kW, 100-rack room can be described as anything from about 1,282 to 8,039 W/m2 (119 to 746 W/ft2) depending on which area is used. That spread causes serious misunderstandings in specifications. The proposed method is to specify density per rack, with both an average and a peak value for each row or zone. A peak-to-average rack power ratio of about 2 within a row is recommended (it must be greater than 1). Optional rules-based placement of high-density racks is also proposed.
The numbers make the problem concrete: the typical area allowance is about 2.6 m2 (28 ft2) per rack and the rack footprint about 0.62 m2, so a 50 W/ft2 specification implies only 1,400 W per rack. IT equipment needs 100 to 160 cfm (47.2 to 75.5 L/s) of air per kW. Legacy design density was typically 40 to 80 W/ft2 (430 to 861 W/m2), while actual IT density is 3 to 20 kW per rack.
Raised-floor air delivery practically limits average density to about 5 kW per rack without special measures. Infrastructure space grows sharply with density: at 1.5 kW per rack about 15 percent of floor space goes to power and cooling equipment, and above about 7 kW per rack more than 50 percent. The practical result is to take density inputs per rack: average and peak rack power for each row or zone, with a default peak-to-average ratio of 2. W/m2 should appear only as a derived metric stating its area basis. Airflow should be computed at 100 to 160 cfm per kW, and the user should be warned when average power exceeds 5 kW per rack on a raised floor.
Key points
- The same 500 kW / 100-rack room gives 119 to 746 W/ft2 (1,282 to 8,039 W/m2) depending on area definition
- Typical area allowance about 2.6 m2 (28 ft2) per rack including aisles; rack footprint about 0.62 m2 (6.7 ft2)
- A 50 W/ft2 spec implies only 1,400 W per rack
- IT equipment requires 100 to 160 cfm (47.2 to 75.5 L/s) of air per kW
- Raised-floor delivery practically limits average density to about 5 kW per rack without special measures
- Recommended peak-to-average rack power ratio in a row is about 2 (must be above 1)
- At 1.5 kW/rack about 15 percent of floor space goes to infrastructure; above 7 kW/rack more than 50 percent
- Legacy design density 40-80 W/ft2 (430-861 W/m2) versus actual IT density of 3-20 kW per rack
Using it in design
- Make the primary density inputs per rack: avgRackKw and peakRackKw per row or zone, default peak/avg 2
- Show W/m2 only as a derived metric that states its area basis (IT-only, white space, gross)
- Compute required airflow with 100-160 cfm/kW (default 120 cfm/kW, about 56.6 L/s per kW)
- Warn when raised-floor supply is chosen with average rack power above 5 kW
- Optional rule: a rack can exceed the average only by the amount its neighbours are below it
Monthly newsletter · free
Keep your reading list current
Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.
SoSo CAD
Check cooling capacity alongside your design
Review zone heat loads, available capacity and the capacity balance after the largest unit is lost in SoSo CAD.
Request a demo
Who should read it
Designers, consultants and client representatives who write power-density specifications.
Related standards
- ASHRAE TC9.9 Thermal Guidelines
- TIA-942
Publication details
- Authors
- Neil Rasmussen
- Publisher
- Schneider Electric
- Year
- 2014
- Document number
- WP 120
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only — the publisher’s terms apply to the original document
Citation
Neil Rasmussen (2014). Guidelines for Specification of Data Center Power Density. Schneider Electric. WP 120. https://download.schneider-electric.com/files?p_Doc_Ref=SPD_NRAN-69ANM9_EN
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.