White paperFree to read2017

Types of Prefabricated Modular Data Centers

Schneider Electric · Wendy Torell

This 2017 Schneider Electric white paper classifies factory-built data center modules by three attributes: functional block, form factor and configuration.

On this page

Overview

The functional block is power, cooling or IT space. A power module holds switchgear/switchboards, ATS, UPS with batteries, transformers and panelboards, with standby generators usually a separate module. Cooling module types are chiller plant (air-cooled chiller, pumps/drives, storage tank, dry/evaporative cooler), DX plant, indirect air (air-to-air heat exchanger, evaporative, DX backup) and direct air (filters, evaporative, DX backup).

Form factor is ISO container, non-ISO enclosure or skid. ISO container footprints are 20 x 8 ft (6.10 x 2.44 m) and 40 x 8 ft (12.2 x 2.44 m), at 8 ft 6 in (2.591 m) or high-cube 9 ft 6 in (2.896 m). Practical container capacity is about 500 kW for power or cooling plant and about 200-250 kW for IT space. Skid-mounted modules often cost up to 40% less than equivalent enclosure designs but are generally indoor-only, and are not logical for IT space because they lack air separation.

Configuration is semi-prefabricated, fully prefabricated or micro/all-in-one. An all-in-one (power, cooling, IT) module is limited to about 150 kW in an ISO footprint, and beyond 2 or 3 micro data center modules on a site (about 500 kW) they become cost prohibitive. Walk-in enclosures must provide lighting, fire protection, security and a means of egress.

The paper distinguishes pre-engineered designs (documented and specified) from prefabricated ones (also factory assembled and tested). Use cases include retrofit capacity shortfalls, multi-tenant step-and-repeat growth, and edge or temporary sites.

Key points

  1. Three attributes: functional block, form factor, configuration.
  2. ISO containers are 20 x 8 ft and 40 x 8 ft, 8 ft 6 in or 9 ft 6 in high-cube.
  3. Practical ISO capacity: about 500 kW power/cooling plant, about 200-250 kW IT space.
  4. Skid modules cost up to 40% less than enclosures, are generally indoor-only and unsuited to IT space.
  5. All-in-one modules reach about 150 kW in an ISO footprint; beyond 2-3 units (about 500 kW) per site they are cost prohibitive.
  6. Walk-in enclosures need lighting, fire protection, security and egress.
  7. Pre-engineered means documented; prefabricated also means factory assembled and tested.

Using it in design

  • Give the module catalog functional block, form factor, indoor/outdoor rating, walk-in flag, shipping sections, footprint and height.
  • Warn when an ISO power/cooling module exceeds about 500 kW or an ISO IT module about 250 kW, and treat a skid used for IT space as an error.
  • Suggest semi- or fully prefabricated options when an all-in-one exceeds 150 kW or 2-3 units per site.
  • Drive the selection wizard from the use case: retrofit shortfall, multi-tenant or edge/temporary.

Monthly newsletter · free

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.

SoSo CAD

Review your power design in SoSo CAD

Inspect supply paths, equipment loads and UPS failure scenarios in one model.

Request a demo
Single-line diagram in the SoSo CAD power and capacity workspace

Who should read it

Designers choosing among prefabricated module types and their capacity ceilings.

Related standards

  • ISO 668
  • ISO 1496-1
  • UL 2755
  • NFPA 101

Publication details

Authors
Wendy Torell
Publisher
Schneider Electric
Year
2017
Document number
WP 165
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only — the publisher’s terms apply to the original document

Citation

Wendy Torell (2017). Types of Prefabricated Modular Data Centers. Schneider Electric. WP 165. https://download.schneider-electric.com/files?p_Doc_Ref=SPD_WTOL-97GLP9_EN