Technical guideFree to read2025

Huawei AI Data Center Reference Design

Huawei Digital Power

A catalogue of 21 reference designs for AI data centres in two construction forms: fully prefabricated modules (RD 01-14) and steel-structure halls (RD 15-21). Each comes in 50, 70 and 132 kW/rack variants.

On this page

Overview

Every design lists module count and kW, liquid-cooled and network rack counts, ride-through time, and transformer, generator, UPS power module, fan-wall and TMU/CDU quantities with redundancy, plus cooling-tower or air-cooled chiller sizing. The prefab solution covers 1.74-7.15 MW of IT and claims construction cut from 18 to 6 months. Power distribution supports 2N, distributed redundant (DR) and block redundant (BR) architectures.

Numeric examples make the designs concrete. The 50 kW/rack prefab module is 872 kW per module with 16 liquid-cooled racks plus 6 network racks at 12 kW, and 10 min of IT and cooling backup. The RD 01 plant has 3 x 1.8 MW power modules, 3 x 2000 kVA transformers, 3 x 2000 kW DCC generators, fan walls of 210 kW each (4+1) and TMU 360 kW (2+1) x 2. The 132 kW/rack module is 1176 kW with 8 liquid racks; steel-structure halls use air:liquid ratios of 2:8 or 3:7 (range 1:9-3:7).

Equipment conditions are in the datasheets at the end. The TMU/CDU rated condition is primary 37/45 C water and secondary 40/50 C deionised water, with a primary inlet range of 10-50 C and secondary supply of 20-60 C. The SmartLi example gives 300 kW for 10 min or 200 kW for 15 min, operating at 0-40 C with 20-25 C recommended. The fan wall nominal condition is 36 C return air and 20/28 C water.

Key points

  1. Prefab solution covers 1.74-7.15 MW IT and claims construction cut from 18 to 6 months.
  2. 50 kW/rack module: 872 kW per module, 16 liquid-cooled racks plus 6 network racks at 12 kW; 10 min IT/cooling backup.
  3. RD 01: 3 x 1.8 MW power modules, 3 x 2000 kVA transformers, 3 x 2000 kW DCC generators, fan walls 210 kW (4+1), TMU 360 kW (2+1) x 2.
  4. Power distribution supports 2N, DR and BR architectures.
  5. 132 kW/rack module: 1176 kW with 8 liquid racks; steel halls use air:liquid 2:8 or 3:7 (range 1:9-3:7).
  6. TMU/CDU rating: primary 37/45 C, secondary 40/50 C deionised water; primary inlet 10-50 C, secondary supply 20-60 C.
  7. SmartLi: 300 kW for 10 min or 200 kW for 15 min; operating 0-40 C, 20-25 C recommended.
  8. Fan wall nominal condition: 36 C return air, 20/28 C water.

Using it in design

  • Import RD 01-21 as parametric AI-hall templates (rack kW, racks per module, module kW, redundancy of fan walls/TMUs/towers, generator and transformer counts) and as golden test cases for capacity math.
  • Add an architecture enum {2N, DR, BR} and an air:liquid ratio per hall.
  • Check secondary-loop temperatures against CDU limits.
  • Default UPS/battery autonomy to 10 min for AI IT and cooling.

Monthly newsletter · free

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.

SoSo CAD

Check cooling capacity alongside your design

Review zone heat loads, available capacity and the capacity balance after the largest unit is lost in SoSo CAD.

Request a demo
Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Who should read it

Designers choosing between prefabricated and steel-structure AI-hall architectures, and teams that need reference cases to validate capacity calculations.

Related standards

  • IEC 62040-3
  • TIA-942
  • Uptime Tier

Publication details

Authors
Huawei Digital Power
Publisher
Huawei Digital Power
Year
2025
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only — the publisher’s terms apply to the original document

Citation

Huawei Digital Power (2025). Huawei AI Data Center Reference Design. Huawei Digital Power. https://digitalpower.huawei.com/admin/asset/v1/pro/view/ebce6552984743528e3d148e2449e6a9.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.