White paperFree to read2020

Considerations for Selecting a Lithium-ion Battery System for UPSs and Energy Storage Systems

Schneider Electric · Scott Daniels

This paper explains the variables that drive lithium-ion battery decisions for UPS and storage: chemistry, C-rate, depth of discharge, cycle and calendar life, round-trip efficiency and temperature. It prepares buyers for vendor trade-offs rather than giving a design procedure.

On this page

Overview

The paper explains the variables that drive lithium-ion battery system decisions: cathode chemistry (NMC, LFP, NCA, LTO), C-rate, depth of discharge, cycle life, calendar life, round-trip efficiency and temperature. The common cathode chemistries for UPS and energy storage systems are named as NMC, LFP and NCA. The text aims to prepare buyers for vendor trade-offs rather than to give a design procedure.

An important section shows that short-runtime UPS discharges extract only a fraction of a lead-acid battery's nominal energy. Lead-acid energy extraction is about 100% at the 20-hour rate but about 33% at the 5-minute rate. A lead-acid battery priced at $100/kWh with 33% extraction is therefore effectively about $300/kWh, which changes simple cost comparisons. Comparisons across chemistries and vendors therefore need to use the same assumptions throughout, or they can mislead.

The end-of-life definition also affects comparison: typically 80% of initial capacity is used in automotive applications and 70% in stationary ones. A UPS loaded at 50% gets more than double its full-load runtime (for example more than 20 minutes). A limit is that the paper gives no numerical design method for a specific product or system, so results must be checked against chemistry and manufacturer data.

Key points

  1. End of life: typically 80% of initial capacity (automotive) and 70% (stationary).
  2. Lead-acid energy extraction is about 100% at the 20-hour rate but about 33% at the 5-minute rate.
  3. Example: $100/kWh lead-acid at 33% extraction is effectively about $300/kWh.
  4. A UPS loaded at 50% gets more than double the full-load runtime (for example more than 20 minutes).
  5. Common cathode chemistries for UPS and ESS: NMC, LFP, NCA.

Using it in design

  • Use C-rate-dependent usable energy (Peukert-like) in the battery runtime calculator rather than nameplate kWh.
  • Add catalogue fields: chemistry, maximum C-rate, cycle life, calendar life, round-trip efficiency, end-of-life percentage.
  • For dual-use UPS/BESS, make cycle life a required input.

Monthly newsletter · free

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.

SoSo CAD

Review your power design in SoSo CAD

Inspect supply paths, equipment loads and UPS failure scenarios in one model.

Request a demo
Single-line diagram in the SoSo CAD power and capacity workspace

Who should read it

Buyers and designers selecting a lithium-ion battery system for UPS and energy storage.

Related standards

  • IEC 62619
  • IEC 62040-1
  • UL 1973
  • UL 9540A

Publication details

Authors
Scott Daniels
Publisher
Schneider Electric
Year
2020
Document number
WP 284
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only — the publisher’s terms apply to the original document

Citation

Scott Daniels (2020). Considerations for Selecting a Lithium-ion Battery System for UPSs and Energy Storage Systems. Schneider Electric. WP 284. https://download.schneider-electric.com/files?p_Doc_Ref=SPD_WP284_EN