Study on the Characterization of Filters for a Direct-to-Chip Liquid Cooling System (40th SEMI-THERM Symposium, 2024)
SEMI-THERM · Pardeep Shahi, Ali Heydari et al.
An experimental study measuring the effect of strainer filters of different mesh sizes in the secondary loop of a direct-to-chip system on pressure drop and flow.
On this page
Overview
This paper is an experimental study presented at the 40th SEMI-THERM Symposium in 2024. Its authors include Pardeep Shahi, Ali Heydari, Dereje Agonafer and Mohammad Tradat. The study starts from the premise that filtration in the coolant distribution unit (CDU) is key to protecting cold-plate microchannels from particulates.
The experiments were carried out on strainer filters in the secondary loop of a direct-to-chip system. Using a CDU and rack, filters of 25, 50 and 100 micron mesh were compared with the no-filter case; CDU pump speed was varied between 20% and 100% by a variable frequency drive, with the coolant held at 32 C. The authors measured pressure drop across the filters, the resulting loop flow, and filter condition over time.
According to the results, the pressure-drop difference between no filter and the 25 micron filter grew from about 0.11 psi at 20% pump speed to about 0.64 psi at 100%. At maximum pump speed loop flow was about 390 L/min, and flow differences between filter cases were around 1% or less. With 100 and 50 micron filters at 80% speed, flow was 308-309 L/min, and the 25 micron filter gave the highest pressure loss. These findings show that finer mesh adds a measurable but small hydraulic penalty.
As a limit, the results are confined to the flows tested, a single CDU and rack arrangement; behaviour may change with a different coolant, contamination load or long-term clogging. Even so, the study offers a measured reference for how filter micron rating can enter the hydraulic calculation, and it should be read alongside the OCP Cold Plate Cooling Loop Requirements.
Key points
- Filters of 25, 50 and 100 micron mesh compared with no filter at CDU pump speeds of 20-100% (VFD), coolant held at 32 C.
- Pressure-drop difference between no filter and the 25 micron filter grew from about 0.11 psi at 20% pump speed to about 0.64 psi at 100%.
- At maximum pump speed loop flow was about 390 L/min; flow differences between filter cases were around 1% or less.
- With 100 and 50 micron filters at 80% speed, flow was 308-309 L/min; the 25 micron filter gave the highest pressure loss.
- Filtration in the CDU is presented as key to protecting cold-plate microchannels from particulates.
- Finer mesh adds a measurable but small pressure drop and flow penalty.
Using it in design
- Include the filter micron rating and its pressure-drop curve in the hydraulic calculation for CDU and loop objects.
- Default to finer filtration (25 micron) for microchannel cold plates, since its hydraulic penalty is small.
- Add monitoring of filter condition over time to the maintenance plan.
- Account for the pressure-drop difference growing with pump speed when selecting pumps.
Monthly newsletter · free
Keep your reading list current
Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.
SoSo CAD
Check cooling capacity alongside your design
Review zone heat loads, available capacity and the capacity balance after the largest unit is lost in SoSo CAD.
Request a demo
Who should read it
Engineers designing CDUs, filters and secondary-loop hydraulics for direct-to-chip liquid-cooled systems.
Related standards
- OCP Cold Plate Cooling Loop Requirements
Publication details
- Authors
- Pardeep Shahi; Ali Heydari; Himanshu Modi; Lochan Sai Reddy Chinthaparthy; Anto Barigala; Qusai Soud; Uschas Chowdhury; Dereje Agonafer; Mohammad Tradat; Jeremy Rodriguez
- Publisher
- SEMI-THERM
- Year
- 2024
- Document number
- 40th SEMI-THERM Symposium; NSF PAR 10537801
- Event
- 40th SEMI-THERM Symposium (2024)
- Document language
- English
- Source type
- Industry body
- Access
- Free to read
- Licence
- Copyright retained; citation only — the publisher’s terms apply to the original document
Citation
Pardeep Shahi; Ali Heydari; Himanshu Modi; Lochan Sai Reddy Chinthaparthy; Anto Barigala; Qusai Soud; Uschas Chowdhury; Dereje Agonafer; Mohammad Tradat; Jeremy Rodriguez (2024). Study on the Characterization of Filters for a Direct-to-Chip Liquid Cooling System (40th SEMI-THERM Symposium, 2024). SEMI-THERM. 40th SEMI-THERM Symposium; NSF PAR 10537801. 40th SEMI-THERM Symposium (2024). https://par.nsf.gov/servlets/purl/10537801
Events on this subject
- SC26 – International Conference for High Performance Computing, Networking, Storage and Analysis
- Data Center World Middle East
- Datacenter Forum Stockholm
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.