AI-driven Thermal-aware Data Center Capacity Planning
arXiv preprint (Cadence Design Systems) · Yixing Li, Mark Fenton et al.
An arXiv preprint in which Cadence engineers describe a U-Net surrogate that predicts the cabinet-inlet temperature field in milliseconds and use it for capacity placement.
On this page
Overview
This document is a 2026 arXiv preprint (arXiv:2610.02442) by Cadence Design Systems engineers Yixing Li, Mark Fenton, Matthew Kaufeler, Ka Ming Leung, Xin Ai and Zhiyu Zeng. The Reality DC (formerly 6SigmaDCX) team describes a U-Net surrogate that predicts the cabinet-inlet temperature field, rather than the whole room, from multi-channel inputs: cabinet layout, IT placement and power, and ACU setpoints and fan speeds.
The model is trained on scripted batches of CFD runs, learning from CFD-extracted cabinet-inlet temperature, velocity and pressure; inlet temperature was chosen as the most operationally critical output. As a practical guideline, an initial dataset is about 500 simulation cases with around ten randomised parameters, extended as needed. The example is a 10.8 m x 9 m x 4.5 m raised-floor room with 4 rows (32 cabinets, 21 x 2U units each), four row-end ACUs and full cold-aisle containment; IT unit power was sampled from 0 to 10 kW and ACU fan speed was varied.
Results are summarised in speed and accuracy: 1000 CFD cases were used (85/10/5 split, about 5 h of training), inference took 9 ms per case against about 25 minutes for full CFD (about 150,000x faster). The paper claims MAE below 0.25 C for cabinet-inlet prediction, but a few cabinets showed maximum-inlet errors of about 3 C, while the relative temperature ranking across cabinets was preserved. The authors note that an earlier HPE 3D-CNN surrogate reported maximum absolute errors of several degrees, which motivated focusing on cabinet inlets.
The preserved ranking matters because the capacity-placement engine uses it to choose cabinets for new load. A limit is that the example covers a single room template; the results are the authors' own report and should not be generalised beyond that configuration. The method should therefore be seen as a screening stage that speeds up candidate selection, not as a replacement for full CFD.
Key points
- The surrogate is trained on CFD-extracted cabinet-inlet temperature, velocity and pressure; inlet temperature was chosen as the most operationally critical output.
- As a practical guideline, an initial dataset is about 500 simulation cases with around ten randomised parameters.
- Raised-floor case: 10.8 x 9 x 4.5 m room, 4 rows (32 cabinets), four row-end ACUs, full cold-aisle containment; IT unit power 0-10 kW.
- 1000 CFD cases (85/10/5 split, about 5 h training); inference 9 ms per case versus about 25 minutes for full CFD (about 150,000x faster).
- MAE below 0.25 C claimed for cabinet-inlet prediction; a few cabinets showed maximum errors of about 3 C, while relative ranking was preserved.
- An earlier HPE 3D-CNN surrogate reported maximum absolute errors of several degrees, motivating the focus on cabinet inlets.
Using it in design
- For layout iteration and add-load what-ifs, a surrogate that predicts only cabinet-inlet temperature (the compliance quantity) is cheaper and more accurate than full-field surrogates.
- Use it to rank candidate cabinets, but confirm the chosen design with full CFD because per-cabinet errors can reach about 3 C.
- Plan for about 500-1000 CFD runs per room template to train one.
- The UI should show surrogate confidence and the CFD-confirmed status.
Monthly newsletter · free
Keep your reading list current
Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.
SoSo CAD
Check cooling capacity alongside your design
Review zone heat loads, available capacity and the capacity balance after the largest unit is lost in SoSo CAD.
Request a demo
Who should read it
Engineers and researchers building data center capacity planning, thermal simulation and CFD-based placement tools.
Related standards
- ASHRAE TC 9.9 Thermal Guidelines for Data Processing Environments
Publication details
- Authors
- Yixing Li; Mark Fenton; Matthew Kaufeler; Ka Ming Leung; Xin Ai; Zhiyu Zeng
- Publisher
- arXiv preprint (Cadence Design Systems)
- Year
- 2026
- Document number
- arXiv:2610.02442
- Document language
- English
- Source type
- Scientific
- Access
- Free to read
- Licence
- arXiv distribution permission — reuse conditions remain with the rights holder
Original licence note
arXiv default non-exclusive distribution licence; no CC licence, so citation only.
Citation
Yixing Li; Mark Fenton; Matthew Kaufeler; Ka Ming Leung; Xin Ai; Zhiyu Zeng (2026). AI-driven Thermal-aware Data Center Capacity Planning. arXiv preprint (Cadence Design Systems). arXiv:2610.02442. https://doi.org/10.48550/arXiv.2610.02442
Events on this subject
- SC26 – International Conference for High Performance Computing, Networking, Storage and Analysis
- Data Center World Middle East
- Datacenter Forum Stockholm
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.