White paperFree to read2013

Power and Cooling Guidelines for Deploying IT in Colocation Data Centers

Schneider Electric · Paul Lin, Victor Avelar

This 2013 Schneider Electric white paper explains why multi-tenant colocation rooms end up with stranded space, power, power distribution, cooling and cooling distribution, and proposes acceptable-use-policy clauses for tenants.

On this page

Overview

The causes are fragmented leasing, many low-density racks that each take a PDU breaker position, cooling designed for around 4 kW per rack, and hot/cold air mixing. Low-density racks are typically fed by a single-phase 16-20 A circuit and draw under 2 kW, yet each takes a branch-circuit position and can strand transformer capacity. The DCD 2012 census average was 4.05 kW, with 58% of racks under 5 kW, 28% at 5-10 kW and 14% above 10 kW.

The paper argues that raising average rack density recovers the first three kinds of stranding (space, power, power distribution) while containment recovers cooling-distribution capacity. More than 50% air leakage (bypass) is routinely observed. Hot aisle containment is cited as saving 43% of annual cooling system energy cost versus cold aisle containment, about a 15% reduction in annualized PUE (from WP 135).

Recommended practices are overhead cabling, 750-800 mm wide racks rather than standard 600 mm for cable management, hot/cold aisle layout with containment and blanking, ducted or close-coupled cooling for high-density racks, and scalable UPS/PDU and DCIM capacity management. For tenants, a 3-phase rack PDU and circuit supporting a 10-15 kW peak with a mix of C13 and C19 receptacles is recommended.

Sample AUP rules in Table 1: draw below 80% of breaker capacity; hot/cold aisle layout; equipment above 6 kW/rack must use containment and/or chimney racks; blanking panels, sealed cutouts, overhead cabling and wide racks.

Key points

  1. Low-density racks use single-phase 16-20 A feeds and draw under 2 kW but take a PDU branch-circuit position.
  2. Most colocation is designed for about 4 kW/rack; DCD 2012 average 4.05 kW (58% of racks under 5 kW, 28% 5-10 kW, 14% above 10 kW).
  3. More than 50% air leakage is routinely observed.
  4. Hot aisle containment saves 43% of annual cooling energy cost versus cold aisle, about 15% of annualized PUE (WP 135).
  5. Wide racks are 750-800 mm versus standard 600 mm.
  6. Tenant rack feed: 3-phase PDU, 10-15 kW peak, C13 and C19 mix.
  7. Example AUP: draw under 80% of breaker capacity; containment or chimney racks above 6 kW/rack.

Using it in design

  • Warn when rack branch-circuit load exceeds 80% of breaker rating.
  • Require containment or chimney/ducted racks when a rack exceeds a configurable threshold, defaulting to 6 kW.
  • Flag rows not in hot/cold aisle orientation, tenant cages facing exhaust-to-intake, and under-floor cabling in supply plenums.
  • Show the five stranding dimensions per room or cage (space, power, power distribution, cooling, cooling distribution) and highlight the binding one.

Monthly newsletter · free

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.

SoSo CAD

Check cooling capacity alongside your design

Review zone heat loads, available capacity and the capacity balance after the largest unit is lost in SoSo CAD.

Request a demo
Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Who should read it

Colocation providers and engineers planning tenant IT deployments.

Related standards

  • ASHRAE TC 9.9 Thermal Guidelines for Data Processing Environments
  • EN 50600-2-3
  • IEC 60320-1

Publication details

Authors
Paul Lin; Victor Avelar
Publisher
Schneider Electric
Year
2013
Document number
WP 173
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only — the publisher’s terms apply to the original document

Citation

Paul Lin; Victor Avelar (2013). Power and Cooling Guidelines for Deploying IT in Colocation Data Centers. Schneider Electric. WP 173. https://download.schneider-electric.com/files?p_Doc_Ref=SPD_VAVR-86MTXB_EN

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.