Specifying Data Center IT Pod Architectures
Schneider Electric · Robert Bunger, Patrick Donovan
Schneider Electric WP 260 (2017) defines the IT pod as the deployment unit between the IT room and the single rack, and derives its size from three inputs.
On this page
Overview
A pod is a row or pair of rows of racks sharing a PDU, containment, network and similar infrastructure. Its size is driven by three inputs: the electrical sub-feed available (voltage and breaker rating), the physical space (number of racks and row length) and the targeted average rack density. Table 1 gives available pod power: 400/230 V IEC 400 A = 275 kW, 250 A = 170 kW; 480/277 V 400 A = 260 kW, 250 A = 165 kW; 208/120 V 400 A = 150 kW, 250 A = 70 kW (ANSI values de-rated to 80% per NEC).
Common voltage and breaker combinations collapse into two standard classes: a low-power pod of about 150 kW (400 V/250 A, 480 V/250 A, 208 V/400 A) and a high-power pod of about 250 kW (400 V/400 A, 480 V/400 A). Airflow needed is 8,500-11,400 l/s (18,000-24,000 CFM) for 150 kW and 14,000-19,000 l/s (30,000-40,000 CFM) for 250 kW, assuming an 11-15 °C IT delta-T. Water flow at 5.6 °C delta-T is 7 L/s for 150 kW and 11.7 L/s for 250 kW.
Typical maximum continuous row length is 20-25 racks; longer rows are generally only seen in hyperscale facilities. A 250 kW pod is 40 racks (2 x 20) at 6 kW, 20 racks (2 x 10) at 12 kW or 12 racks (2 x 6) at 20 kW; a 150 kW pod is 24, 12 and 6 racks. Average density is pod power divided by rack count, while peak density is set by the rack branch circuit, so with good containment a 20 kW rack can sit beside a 2 kW rack. The authors advise under-estimating average density, because deploying below design density strands the more expensive power and cooling capacity while space is usually the cheapest resource.
Key points
- Sub-feed power: 400/230 V 400 A 275 kW, 250 A 170 kW; 480/277 V 400 A 260 kW, 250 A 165 kW; 208/120 V 400 A 150 kW, 250 A 70 kW.
- Two classes: about 150 kW low-power and about 250 kW high-power pods.
- Airflow: 8,500-11,400 l/s for 150 kW; 14,000-19,000 l/s for 250 kW (11-15 °C delta-T).
- Water flow at 5.6 °C delta-T: 7 L/s (150 kW) and 11.7 L/s (250 kW).
- Typical maximum continuous row length is 20-25 racks.
- 250 kW pod: 40 racks at 6 kW, 20 at 12 kW, 12 at 20 kW.
- Peak rack density comes from the rack branch circuit, average from pod power over rack count.
- Under-estimate average density; space is usually the cheapest resource.
Using it in design
- Make the pod a first-class object between room and rack, with feed power, input voltage, feeder breaker, feed redundancy, UPS location and rack count.
- Offer 150 kW and 250 kW pod templates and compute required airflow and 5.6 °C delta-T chilled-water flow from pod kW.
- Warn when row length exceeds 20-25 racks (egress check), when rack loads sum above the pod feed, or when a rack is fed from a PDU outside its pod.
- Apply 80% continuous de-rating in NEC jurisdictions.
Monthly newsletter · free
Keep your reading list current
Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.
SoSo CAD
Review your power design in SoSo CAD
Inspect supply paths, equipment loads and UPS failure scenarios in one model.
Request a demo
Who should read it
Designers specifying rack rows, PDUs and cooling as repeatable pod units.
Related standards
- NFPA 70 (NEC)
Publication details
- Authors
- Robert Bunger; Patrick Donovan
- Publisher
- Schneider Electric
- Year
- 2017
- Document number
- WP 260
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only — the publisher’s terms apply to the original document
Citation
Robert Bunger; Patrick Donovan (2017). Specifying Data Center IT Pod Architectures. Schneider Electric. WP 260. https://download.schneider-electric.com/files?p_Doc_Ref=SPD_WTOL-AHAPRN_EN
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.