Technical guideFree to read2024

Powering the Future: Revolutionizing Data Center Design (BUS PAC)

Legrand (Server Technology) · Legrand

This 2024 Legrand/Server Technology white paper covers how to build rack- and row-level power distribution as densities climb toward 40-200 kW. Its central proposal is overhead track busway feeding high-amperage rack PDUs in place of traditional 120/208 V distribution and remote power panels.

On this page

Overview

The paper opens with survey data showing how thin high density still is in the field: in a 2022 survey only 10% of sites had racks at 20-29 kW, 7% at 30-39 kW and 3% at 40-49 kW. That small base is used to frame its argument that the jump is coming from AI and HPC loads, and that sites will have to rethink the distribution architecture rather than stretch the old one. For AI and HPC racks it cites 40-125 kW today, with extreme cases of 80-200 kW per rack.

The proposed answer is three-phase track busway rated from 40 A up to 1,250 A. The busway runs overhead along the row, racks are fed from it through tap-off boxes, and adding or moving a load means plugging into the track rather than pulling new cable runs. Inside the rack, high-amperage rack PDUs take over. The range described has inputs of 16-100 A, single-phase inputs at 100-277 V and three-phase inputs at 208, 400, 415 and 480 V.

Metering accuracy of +/-0.5% (billing grade) and environmental sensing are offered, which turns per-rack energy measurement into a product feature instead of a separate engineering job. It is a vendor paper and the comparison is framed around its own product family, so it contains no independent cost or reliability data. The standards it ties to (IEC 61439-6 for busbar trunking, UL 857, NEC 645) still give a useful frame for understanding why remote panels and whip-based distribution lose flexibility as density rises.

Key points

  1. 2022 survey: only 10% of sites had 20-29 kW racks, 7% at 30-39 kW and 3% at 40-49 kW.
  2. AI/HPC racks run 40-125 kW today; extreme cases reach 80-200 kW per rack.
  3. Track busway is rated from 40 A to 1,250 A, three-phase.
  4. Rack PDU inputs are 16-100 A; single-phase 100-277 V, three-phase 208/400/415/480 V.
  5. PDU metering accuracy is +/-0.5% (billing grade).
  6. Related standards: IEC 61439-6, UL 857, NEC 645.
  7. Traditional 120/208 V distribution with remote power panels (RPPs) loses flexibility in dense rows.

Using it in design

  • Add busway entries with 40-1,250 A ampacity and tap-off ratings to the electrical catalog; define rack PDU entries at 16-100 A and 208/415/480 V.
  • For racks above 20 kW, default to three-phase 415 V (or 480 V) PDUs.
  • Where a row has many racks or density changes often, suggest overhead busway instead of RPP whip distribution.
  • Add a rule requiring metered PDUs with +/-0.5% accuracy on racks that must be billed per tenant.

Monthly newsletter · free

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.

SoSo CAD

Review your power design in SoSo CAD

Inspect supply paths, equipment loads and UPS failure scenarios in one model.

Request a demo
Single-line diagram in the SoSo CAD power and capacity workspace

Who should read it

Electrical designers and colocation operators choosing power distribution for high-density racks.

Related standards

  • IEC 61439-6
  • UL 857
  • NEC 645

Publication details

Authors
Legrand
Publisher
Legrand (Server Technology)
Year
2024
Document number
V2076 R2
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only — the publisher’s terms apply to the original document

Citation

Legrand (2024). Powering the Future: Revolutionizing Data Center Design (BUS PAC). Legrand (Server Technology). V2076 R2. https://cdn10.servertech.com/assets/documents/documents/1070/original/BUS_PAC_Powering-the-Future-Revolutionizing-Data-Center-Design_White-Paper_V2076_R2.pdf?1716386176

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.