Technical Application Papers No.11: Guidelines to the construction of a low-voltage assembly complying with the Standards IEC 61439 Part 1 and Part 2
ABB
ABB's Technical Application Paper No. 11 explains how low-voltage assemblies are verified under IEC 61439-1 and IEC 61439-2: temperature rise can be verified by calculation only up to 630 A (power-loss method) or 1600 A (IEC 60890), and above that a test or derivation from a tested design is required.
On this page
Overview
The paper explains the changes introduced by IEC 61439-1 and IEC 61439-2, which replaced IEC 60439-1. These standards cover all low-voltage switchgear and controlgear assemblies with a rated voltage not above 1000 V AC or 1500 V DC. The old split between type-tested (TTA) and partially type-tested (PTTA) assemblies is gone; in its place each characteristic is covered by design verification through testing, calculation or design rules. Responsibility is shared between the original manufacturer, who carries out the design verifications, and the assembly manufacturer, who carries out the routine verifications.
The opening chapters define the rated characteristics of an assembly (rated voltage, insulation voltage, impulse withstand voltage, rated current, short-time withstand current Icw, conditional short-circuit current Icc, rated diversity factor RDF), the classification of assemblies, IP and IK degrees of protection, and the forms of internal separation. Forms 1 to 4, with a and b variants, state how far busbars, functional units and terminals are separated from each other. The explanations are illustrated with ABB's ArTu assembly range.
The most detailed part is temperature-rise verification. The limits assume an ambient temperature not above +40 °C with a 24 hour average not above +35 °C. The power-loss method applies to single-compartment assemblies up to 630 A, and the IEC 60890 calculation to multi-compartment assemblies up to 1600 A; in both, circuit current must not exceed 80% of the device's rated current in free air. The IEC 60890 calculation produces a map of internal air temperature rising linearly from bottom to top of the enclosure, and is shown through worked examples.
The short-circuit chapter shows how to compare the prospective short-circuit current of the plant with the assembly's Icw or Icc, and how to obtain the peak current from Ipk = Icw x n. Withstand verification is not needed for assemblies with a rated short-time or conditional short-circuit current not above 10 kA, or for assemblies protected by current-limiting devices with a limited peak not above 17 kA. Dielectric tests, protection against electric shock, breaker positioning and conductor anchoring rules, handling and installation, routine verifications and a step-by-step ArTu design example follow.
The paper was written against the 2009 edition of IEC 61439, so details need checking against the edition in force, while the verification logic and the split of responsibilities remain valid. The practical chapters on breaker positioning, connection to busbars and minimum installation distances contain dimensions specific to ABB SACE Tmax and Emax breakers; for assemblies built with another manufacturer's devices those values come from that manufacturer's documents. Annex A provides sample forms for the declaration of conformity and the test certificate that the assembly manufacturer issues at handover, and the owner's side can use the same forms to check the content of the acceptance file.
Key points
- IEC 61439 replaces the TTA and PTTA concepts with design verification by testing, calculation or design rules, and tabulates which method is accepted for each characteristic.
- Scope: low-voltage assemblies with rated voltage not above 1000 V AC or 1500 V DC.
- Temperature-rise verification by calculation: power-loss method for single-compartment assemblies up to 630 A, IEC 60890 method for multi-compartment assemblies up to 1600 A (formerly up to 3150 A).
- In the calculation methods the rated current of circuits must not exceed 80% of the free-air rated current of the devices; in ventilated enclosures the air outlet cross-section must be at least 1.1 times the inlet cross-section.
- Temperature-rise limits hold for ambient temperature not above +40 °C and a 24 hour average not above +35 °C.
- Short-circuit withstand verification is not needed for assemblies with Icw or Icc not above 10 kA, or protected by current limiters with a limited peak not above 17 kA.
- Peak withstand current follows from Ipk = Icw x n; in the example, Icw of 35 kA and n of 2.1 give Ipk 73.5 kA and I2t 1225 (kA)2s.
- Forms of separation are defined as 1, 2a, 2b, 3a, 3b, 4a and 4b; in form 4b the terminals sit in a compartment separate from the functional unit.
- Design verifications are the original manufacturer's responsibility; routine verifications (wiring, insulation, protective circuit continuity checks) belong to the assembly manufacturer.
Using it in design
- State the design verification method in the switchboard specification: for main distribution boards above 1600 A, ask for evidence by test or by derivation from a tested design.
- Compare the prospective short-circuit current at the connection point with the assembly's Icw or Icc, and the peak with Ipk, and record the result on the single-line diagram.
- Set the electrical room design temperature against the +35 °C 24 hour average limit; for hotter rooms ask the manufacturer for derating.
- Define simultaneous loading of outgoing circuits through the rated diversity factor (RDF); for data-centre circuits that run continuously at full load, request the factor accordingly.
- Choose the form of separation (form 4b, for example) and the IP degree from the need to work on the board while it stays energised.
- At handover, ask for the routine verification records and the declaration of conformity, using the Annex A forms as a checklist.
Who should read it
Electrical engineers who design and specify low-voltage switchboards, panel builders, and commissioning teams running acceptance tests.
Document contents
- Introduction
- 1 Standards on low-voltage assemblies and relevant applicability
- 2 Rated electrical characteristics of an assembly
- 3 Classification of electrical assemblies
- 4 Degree of protection IP of an assembly
- 5 Degree of protection IK of enclosures
- 6 Forms of internal separations
- 7 Verification of the temperature-rise limits inside an assembly
- 8 Verification of performances under short-circuit conditions
- 9 Verification of dielectric properties of the assembly
- 10 Protection against electric shocks
- 11 Practical indications for the construction of assemblies
- 12 Guide to the certification of assemblies
- 13 Example of construction of an ArTu assembly
- Annex A: Forms for the declaration of conformity and test certificate
Related standards
- IEC 61439-1
- IEC 61439-2
- IEC 60890
Publication details
- Authors
- ABB
- Publisher
- ABB
- Year
- 2010
- Document number
- 1SDC007110G0201
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document