ABB MegaFlex DPA (500 kW - 2000 kW) 380 V to 480 V Modular Three-Phase UPS Brochure
Original title MegaFlex DPA universal voltage UPS system: 2026 brochure and weight tables
ABB
ABB's brochure for the 380 V to 480 V modular three-phase UPS built on decentralized parallel architecture (DPA) with 250 kW modules and frames up to 2000 kW, with technical tables and weights for the distributed and centralized bypass versions.
On this page
Overview
The brochure presents MegaFlex DPA as a modular online double-conversion UPS for hyperscale and cloud data centres. In the decentralized parallel architecture (DPA) every module works practically as its own UPS, which gives redundancy and fault tolerance. If one module fails in an N+1 setup, the others take its load, and modules can be added or removed without powering down. A single frame reaches 2000 kW; redundant ratings are given as 1250 kW N+1 and 1750 kW N+1. The frame has 3 or 4 power-module slots and connection frames rated 1000, 1500 and 2000 kW.
On efficiency, it states up to 97.6% at system level in VFI double-conversion mode and up to 99.4% in VFD eco mode (99% in the technical table). With Xtra VFI mode enabled, the number of active modules adjusts dynamically to load and unneeded modules go to standby, reducing losses when load is below 25% of full capacity. An example for a 48 MW IT load, 2N design and 15-year UPS life shows 20% less (losses). Footprint savings of up to 45% and a design life of up to 15 years are stated.
Technical tables are given for distributed bypass (DSB, 1000, 1250, 1500 kW) and centralized bypass (CSB, 1500, 1750, 2000 kW). Topology is VFI-SS-111; input is 380/400/415 VAC (50 Hz) or 415/480 VAC (60 Hz), input current THDi below 3%, input power factor 0.99, output voltage tolerance ±1%, output THDU below 2%, output power factor 1.0, IP20. Batteries can be VRLA, Li-Ion or nickel-zinc. DSB weights with all modules: 1940 kg for 1000 kW, 2595 kg for 1250 kW, 3250 kg for 1500 kW; sizes 2235 x 2000 x 1000 mm and 3045 x 2000 x 1000 mm. The cover quotes up to 6000 kW in a parallel configuration while the technical table gives parallel system capability of 4500 kW (3 x 1500 kW) or, for CSB, 4000 kW (2 x 2000 kW).
Key points
- Module is 250 kW; frame up to 2000 kW; redundant ratings 1250 kW N+1 and 1750 kW N+1.
- Topology online double conversion VFI-SS-111; output power factor 1.0, output voltage tolerance ±1%, THDU below 2%.
- Efficiency: up to 97.6% at system level in VFI mode; up to 99.4% in eco mode (VFD), 99% in the technical table.
- Xtra VFI mode adjusts active module count at low load and reduces losses when load is below 25% of full capacity.
- Input: 380/400/415 VAC (50 Hz) or 415/480 VAC (60 Hz); THDi below 3%; power factor 0.99; voltage tolerance +15% (all loads), -30% (partial loads).
- DSB (distributed bypass) weight with all modules: 1940 kg (1000 kW), 2595 kg (1250 kW), 3250 kg (1500 kW).
- Dimensions (W x H x D): 2235 x 2000 x 1000 mm (1000 kW DSB), 3045 x 2000 x 1000 mm (1250 and 1500 kW DSB).
- Batteries: VRLA, Li-Ion and nickel-zinc ready; decentralized charger per power module.
- Standards: IEC/EN 62040-1, 62040-2, 62040-3, UL1778; UL9540A in process; footprint savings up to 45%, design life up to 15 years.
Using it in design
- Translate the redundancy target (for example 1250 kW N+1 or 1750 kW N+1) into frame and module count, and write the module-addition plan against IT load growth.
- When choosing between distributed bypass (DSB) and centralized bypass (CSB), compare the power ranges (1000 to 1500 kW and 1500 to 2000 kW) and the bypass fault-tolerance approach.
- Check cabinet weight (for example 3250 kg) against floor loading and layout; assess the frame and module weights in the table separately.
- Evaluate eco mode (up to 99% efficiency) and Xtra VFI against the pulsing AI load profile together with protection and acceptance criteria.
- Confirm the parallel capacity figures (6000 kW on the cover, 4500 kW and 4000 kW in the table) with the supplier project by project.
Who should read it
Electrical designers and specification engineers selecting modular UPS for large-scale data centres.
Document contents
- AI-enhanced operational reliability
- Smart power protection for dynamic growth (flexible approach, optimized efficiency, reliable operations, high serviceability)
- The MegaFlex DPA portfolio (distributed bypass DSB and centralized bypass CSB)
- The MegaFlex DPA as reliable and eco-friendly UPS
- Control and monitoring
- Tested and trusted, services
- Technical specifications (DSB and CSB)
Publication details
- Authors
- ABB
- Publisher
- ABB
- Year
- 2026
- Document number
- 9AKK108471A8305
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
ABB (2026). MegaFlex DPA universal voltage UPS system: 2026 brochure and weight tables. ABB. 9AKK108471A8305. https://library.e.abb.com/public/3b67c5bb35b64134a487c5ba729f2a3a/9AKK108471A8305_en_B_ABB%20MegaFlex%20DPA%20-%20universal%20voltage%20modular%203-phase%20380V%20to%20480V%20UPS%20system.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.