Technical Application Papers No.5: ABB circuit-breakers for direct current applications
ABB
ABB's Technical Application Paper No. 5, dated September 2007, sets out the basics of protection in low-voltage DC circuits: because direct current has no natural zero crossing, the arc is extinguished by connecting breaker poles in series; the pole connection is chosen from three earthing typologies (insulated, one polarity earthed, mid-point earthed), and battery short-circuit current is calculated per IEC 61660-1.
On this page
Overview
The paper opens with where direct current is used today (photovoltaic plants, electric traction, emergency and auxiliary supplies, particular industrial applications) and how it is generated (storage batteries, static converters, dynamos). For data centres the relevant parts are UPS battery circuits and DC auxiliary buses. The aim is to let the reader pick a protection and isolation device quickly from tables, based on fault type, installation voltage and earthing arrangement.
Interruption of direct current is explained in its own chapter. Alternating current passes through a natural zero every half cycle; direct current does not, so the breaker has to force the current to zero by raising arc voltage above the supply voltage. Extinction time is proportional to the circuit time constant T = L/R. The arc has to be cooled and lengthened, and as voltage rises the number of breaking points in series is increased. The paper expects three things of DC breakers: rapid tripping with adequate breaking capacity, high current limitation and reduction of overvoltage.
Three network typologies are examined through fault scenarios. In a network insulated from earth, a first earth fault has no consequence but a second can become a short circuit, so insulation monitoring is recommended. With one polarity earthed, a fault between the non-earthed polarity and earth is a short circuit fed at full voltage. With the mid-point earthed, a fault between a polarity and earth is fed at half the voltage (U/2), but breaking is needed on both polarities. For each typology, tables give the pole connection diagrams for miniature, moulded-case and air circuit-breakers and the breaking capacities achieved.
Chapter 8 covers using thermal magnetic breakers built for alternating current on DC: the magnetic trip threshold is corrected by a factor km that depends on the connection (10 x 160 x 1.3 = 2080 A for a 160 A breaker in the example), and connecting poles in parallel requires derating the rated current. Annex B calculates the short-circuit current of a stationary lead-acid battery per IEC 61660-1: peak ipb = Eb/R and quasi steady-state Ikb = 0.95 Eb/(R + 0.1 Rb). In the 240 V example the peak is 4.8 kA and the quasi steady-state value 4.15 kA. Annex C lists breakers and switch-disconnectors up to 1000 V DC. The paper dates from 2007 and its product tables cover ABB ranges of that period.
Key points
- Direct current has no natural zero crossing; the arc goes out once arc voltage exceeds supply voltage, and extinction time is proportional to the time constant T = L/R.
- As voltage rises, more poles are connected in series; the more contacts opening the circuit, the higher the breaking capacity.
- Three network typologies: insulated from earth, one polarity earthed, and mid-point of the supply source earthed.
- In a mid-point earthed network a fault between a polarity and earth is fed at U/2, and breaking must be provided on both polarities.
- In an insulated network a single earth fault sets up no current; because a second fault can cause a short circuit, an insulation monitoring device is recommended.
- Battery short circuit (IEC 61660-1): ipb = Eb/R and Ikb = 0.95 Eb/(R + 0.1 Rb), where R = 0.9 Rb + Rbl + Ry. In the 240 V example ipb is 4.8 kA and Ikb 4.15 kA.
- When an AC thermal magnetic breaker is used on DC, the magnetic threshold is multiplied by km; for Tmax T1 to T4 in one connection km is 1.3.
- Derating for poles in parallel is 0.9 for 2 poles, 0.8 for 3 poles and 0.7 for 4 poles; above 800 A ABB recommends air circuit-breakers with DC releases over parallel connection.
- Tmax thermal magnetic breakers can be used on DC from 1.6 A to 800 A; Annex C covers applications up to 1000 V DC.
Using it in design
- Before selecting the UPS battery circuit breaker, calculate battery short-circuit current with the IEC 61660-1 relations, taking the battery's internal resistance from manufacturer data.
- Decide the earthing typology of the DC system (insulated, one polarity earthed, mid-point earthed) at the start of design; the pole connection diagram and breaking capacity depend on it.
- Confirm the breaker's DC breaking capacity from the table for the chosen pole connection and system voltage; do not use the AC breaking capacity for DC.
- On insulated battery systems, provide an insulation monitoring device and make sure the first earth fault raises an alarm.
- If an AC breaker is used in a DC circuit, correct the magnetic trip threshold by km and run the selectivity study with the corrected value.
- Compare the circuit's L/R time constant with the time constant of the breaker's test conditions, and consult the manufacturer for long cable runs or inductive circuits.
Who should read it
Electrical engineers designing battery and DC distribution circuits, UPS system integrators, and writers of DC protection specifications.
Document contents
- 1 Introduction
- 2 Generalities on direct current
- 3 Applications
- 4 Generation
- 5 Remarks on the interruption of direct current
- 6 Typologies of d.c. networks
- 6.1 Network insulated from earth
- 6.2 Network with one polarity earthed
- 6.3 Network with the middle point of the supply source connected to earth
- 7 Choice of the protective device
- 8 Use of alternating current equipment in direct current
- 9 ABB offer
- Annex A: Direct current distribution systems
- Annex B: Calculation of short-circuit currents
- Annex C: Circuit-breakers and switch-disconnectors for applications up to 1000 V d.c.
- Glossary
Related standards
- IEC 60947-2
- IEC 61660-1
- IEC 60364-1
Publication details
- Authors
- ABB
- Publisher
- ABB
- Year
- 2007
- Document number
- 1SDC007104G0201
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
ABB technical application paper, free download from ABB library; copyright ABB, no open licence.
Citation
ABB (2007). Technical Application Papers No.5: ABB circuit-breakers for direct current applications. ABB. 1SDC007104G0201. https://library.e.abb.com/public/37340c2cd069c912c1257385003d26d2/1SDC007104G0201.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.
