RC223 (type B) residual-current release (White Paper)

ABB

An ABB white paper explaining the difference between type AC, A and B residual current devices and why loads with rectifiers and inverters need type B: the smooth DC component in the earth-fault current of three-phase UPS systems and drives is not detected by type AC and A devices, and EN 62040-1 calls for type B on three-phase UPS and type A on single-phase UPS.

On this page

Overview

The paper defines residual current device types by the current waveforms they detect. Type AC detects only sinusoidal alternating residual currents, type A adds pulsating direct currents, and type B also detects smooth direct currents. Single-phase electronic loads (UPS, PCs, printers, electromedical equipment) produce earth-fault currents with DC components. Three-phase UPS, computed tomography and magnetic resonance equipment, variable speed drives and AC/DC converters produce direct currents large enough to impair the residual current device protecting their supply circuit.

Because the toroid of a type AC device does not necessarily detect these fault currents, type A is chosen for single-phase users and type B for three-phase users. In a three-phase drive the fault can occur in the DC link or on the inverter output; in the latter case only a type B device detects the resulting high-frequency, harmonic-rich fault current. Three references are cited: EN 50178 accepts only type B on the supply side of mobile electronic equipment above 4 kVA or fixed equipment producing reduced-ripple DC fault current; EN 62040-1 defines UPS protection; and IEC 60364-712 requires type B in photovoltaic systems without at least simple separation between the AC and DC sides.

The conditions under which a type B device must trip are listed per IEC/TR 60755: sinusoidal currents at 50 to 60 Hz and unidirectional pulsating currents as for type A, alternating currents superimposed on smooth DC of 0.4 times rated residual current, pulsating currents superimposed on smooth DC of 0.4 x IΔn or 10 mA, whichever is higher, currents resulting from rectifier circuits, and smooth direct currents. A table of nine connection examples shows which type suffices for which rectifier arrangement; type B is necessary for single-phase with smoothing, three-phase star, two-pulse bridge between phases and six-pulse bridge.

The product section presents the RC223 release. It uses a single toroid, but the toroid is energised with a rectangular voltage at kHz frequency and a microprocessor with a low-pass filter isolates the fault component even when it is direct. The RC223 is used with 4 pole Tmax T3 and T4 breakers up to 250 A (225 A on T3); the trip threshold is selected in six steps from 0.03 to 1 A and the fault frequency sensitivity at 400, 700 or 1000 Hz. An emergency arrest function for remote opening is also included.

Key points

  1. Type AC detects only sinusoidal AC residual current, type A also pulsating DC, and type B additionally smooth DC.
  2. For loads with rectifiers and inverters, type A is chosen for single-phase users and type B for three-phase users.
  3. EN 62040-1 calls for type B earth-fault protection on three-phase UPS and type A on single-phase UPS where an earth-fault current with DC components is possible.
  4. Under EN 50178, only type B is accepted on the supply side of mobile electronic equipment above 4 kVA or fixed equipment producing reduced-ripple DC fault current.
  5. Type B must trip for alternating current superimposed on smooth DC of 0.4 x IΔn and for pulsating current superimposed on smooth DC of 0.4 x IΔn or 10 mA, whichever is higher (IEC/TR 60755).
  6. An earth fault on the inverter output of a drive produces high-frequency current rich in harmonics, which only type B detects.
  7. RC223 data: service voltage 110 to 500 V, rated current up to 250 A (225 A on the T3 breaker), trip thresholds 0.03, 0.05, 0.1, 0.3, 0.5 and 1 A.
  8. The non-trip time at 2 x IΔn is set in eight steps from instantaneous to 3 s; trip time tolerance is ±20% and fault frequency sensitivity is selectable at 400, 700 or 1000 Hz.

Using it in design

  • Where residual current protection is needed on circuits feeding three-phase UPS, drives or rectifiers, specify type B and do not use type AC on those circuits.
  • Where a load needing type B sits below another residual current device, check the upstream device type as well; a smooth DC component weakens detection by an upstream type AC or A device.
  • On supplies to variable speed drives in the cooling plant (pumps, fans, chillers), choose the fault frequency sensitivity from the drive's output frequency range.
  • For graded selectivity, coordinate the trip threshold and delay (instantaneous to 3 s) with the residual current devices on downstream circuits.
  • Where a rooftop photovoltaic system exists, assess the type B requirement under IEC 60364-712 from whether the AC and DC sides are separated.

Who should read it

Electrical engineers designing low-voltage protection, designers of UPS and drive supply circuits, and specification writers.

Document contents

  1. 1. Generals
  2. 2. Application description
  3. 2.1 Applications
  4. 2.2 Application examples
  5. 2.3 How does an RC223 operate?
  6. 3. Application indications
  7. 3.1 Technical characteristics
  8. 3.2 Configuration indications
  9. 3.3 Emergency Arrest (EA)
  10. 3.4 Operating time and current
  11. 3.5 "Testing field" section

Related standards

  • IEC 60755
  • IEC 62423
  • EN 50178
  • IEC 62040-1
  • IEC 60364-7-712

Publication details

Authors
ABB
Publisher
ABB
Year
2009
Document number
1SDC007404G0201
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

ABB white paper, free download; copyright ABB, no open licence.

Citation

ABB (2009). RC223 (type B) residual-current release (White Paper). ABB. 1SDC007404G0201. https://library.e.abb.com/public/9d3c391e35638d68c1257ac5003ecff9/1SDC007404G0201.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.