Double Ground Fault Protection: Implementation (White Paper)
ABB
An ABB white paper on the "Double G" function, which combines the internal earth-fault protection of the main low-voltage breaker at an MV/LV substation with an external toroid on the transformer star-point earth conductor; in the example setting the internal protection is 0.2 x In at 0.25 s and the external 0.5 x In at 0.5 s, and a fault between transformer and breaker is cleared by tripping the medium-voltage breaker.
On this page
Overview
The paper separates three zones where an earth fault can occur in a typical MV/LV distribution substation. An unrestricted (downstream) fault lies on the load side of the air circuit-breaker at the transformer secondary and is detected by the breaker's G protection. A restricted (upstream) fault lies between the transformer secondary winding and the breaker's incoming terminals; opening the low-voltage breaker does not clear it, and because it appears as a very small current on the medium-voltage side, primary protections do not detect it easily. The third method, source ground return, uses a toroid on the star-point earth conductor and sees both fault types without telling them apart.
The Double G function combines the two measurements in one trip unit. The unit holds two independent G curves: internal G, driven by the breaker's own current sensors, sees only the downstream fault, while external G (Gext), driven by the external toroid, sees both. The toroid is placed between the neutral and PE connections, so neutral currents do not pass through it and only fault current returning through the PE is measured. Discrimination is by current and time grading: the external G curve is always set above the internal G curve.
Operation is explained through two scenarios. On a downstream fault both protections start timing, the faster internal G trips the low-voltage breaker, and the medium-voltage breaker is not opened unnecessarily. An upstream fault is seen only by the toroid; when the external G time elapses, a signalling contact of the trip unit closes and commands the opening release of the medium-voltage breaker. The function is available on New Emax breakers with PR123/P LSIG trip units and on X1 breakers with PR333/P LSIG units; PR122/P and PR332/P units allow only one of internal or external G to be set.
The application example covers a substation with a medium-voltage breaker, an E2N 1600 4 pole incomer with PR123/P LSIG and a star-point toroid. The practical guide uses circuit diagrams to show how to connect the toroid, how to program the contact of a PR120/K, PR021/K or LD030 DO signalling module for external G tripping, and how to wire that contact to the shunt opening release of the medium-voltage breaker. The paper is product specific, yet the principle that a restricted earth fault needs dedicated detection and a medium-voltage trip applies to any manufacturer's equipment.
Key points
- Three protection zones are defined: unrestricted earth fault (load side of the breaker), restricted earth fault (between transformer secondary and breaker terminals) and source ground return.
- A restricted fault is not cleared by opening the low-voltage breaker; complete protection requires tripping the medium-voltage breaker.
- The external homopolar toroid sits on the star-point earth conductor between the neutral and PE connections, so it measures fault current returning through the PE and not neutral current.
- Discrimination is by current and time grading; the example settings are I4 = 0.2 x In, t4 = 0.25 s for internal G and I4 = 0.5 x In, t4 = 0.5 s for external G.
- The trip unit measures earth-fault current from 0.05 In to 4 In; the standard operating range is 0.3 In to 4 In with ±1.5% tolerance.
- The function is available on New Emax breakers with PR123/P LSIG and X1 breakers with PR333/P LSIG trip units.
- The medium-voltage trip signal is issued through a contact of the PR120/K, PR021/K or LD030 DO signalling unit; PR120/K and PR021/K contacts switch up to 100 W or 1250 VA on resistive load.
Using it in design
- Show restricted earth-fault protection separately on the single-line diagram for the busbar or cable section between the transformer secondary and the main LV breaker.
- Fix the position of the star-point toroid relative to the neutral and PE connection points; in the wrong position it measures neutral current and trips falsely.
- Set the external G threshold and time above internal G, and include time grading with the earth-fault protection on outgoing circuits in the coordination study.
- Include the wiring from the LV trip unit to the MV breaker opening release and the continuity of its auxiliary supply in the design, and test it by primary injection during commissioning.
- Where equipment from another manufacturer is used, write an equivalent restricted earth-fault relay arrangement into the specification.
Who should read it
Electrical engineers designing substation and main LV switchboard protection, protection coordination specialists, and commissioning teams.
Document contents
- 1. Generalities
- 2. Application Description
- 2.1 Introduction
- 2.2 Application solution
- 3. References
- 3.1 Application example
- 4. Practical Guide
- 5. Bibliography
Related standards
- IEC 60947-2
- IEC 60364-4-41
Publication details
- Authors
- ABB
- Publisher
- ABB
- Year
- 2009
- Document number
- 1SDC007403G0201
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
ABB white paper, free download from ABB library; copyright ABB, no open licence.
Citation
ABB (2009). Double Ground Fault Protection: Implementation (White Paper). ABB. 1SDC007403G0201. https://library.e.abb.com/public/fd983dd10192b529c1257ac5003e1dba/1SDC007403G0201.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.