Research paperFree to read2023

Enabling Low-Cost Server Level Power Monitoring in Data Centers Using Conducted EMI

ACM SenSys 2023 / UTA author publication · Pranjol Sen Gupta, Zahidur Talukder et al.

A SenSys 2023 paper that estimates the power of each server by separating conducted electromagnetic interference (EMI) from server power supplies in a single voltage measurement.

On this page

Overview

The paper starts from the observation that server-level power metering is expensive, so most facilities monitor only at UPS or cluster PDU level. A dedicated per-server meter costs about 400 dollars in extra equipment and licensing, and a smart PDU with metered outlets about 80 dollars per server. The authors propose cutting this cost with one sensor that extracts the power of all servers on a circuit.

The method relies on the power factor correction (PFC) stage in each server power supply. PFC switching produces EMI in a narrow frequency band specific to each supply, and its amplitude or frequency shifts with server power. The Dell servers behave as frequency-modulated PFC (FM-PFC) and the Lenovo servers as amplitude-modulated PFC (AM-PFC). Because different servers occupy roughly orthogonal bands, each signature can be separated in the frequency domain from one voltage measurement on the supply line.

Validation used ten servers, six Dell PowerEdge and four Lenovo ThinkSystem, over five days with real workload traces. Mean absolute error stayed below about 7 percent. The L-N connection was chosen as the sensing point, and sampling near 200 thousand samples per second with low-cost ADCs proved sufficient. PFC switching frequencies are about 70 kHz for the Dell units and about 65 kHz for the Lenovo units.

The limits are stated plainly. Because the approach depends on PFC, it works only in AC-distributed facilities and not in DC-powered data centres. The separation algorithm is heuristic, the experiment covers ten servers from two vendors, and scaling to facilities with hundreds of servers and general applicability remain unvalidated. For one phase, the authors derive an upper bound of 200 servers in a 150 kVA three-phase cluster PDU example.

A cost estimate is included: a Raspberry Pi Pico based sensor prototype costs about 20 dollars. That is about 2 dollars per server for ten servers and about 0.1 dollars per server at 200 servers, against roughly 83 dollars per server for a 24-outlet smart PDU. The authors note that the smart PDU offers extra functions such as remote switching.

Key points

  1. One voltage sensor yields per-server power estimates from the PFC-generated EMI bands of all servers in the cluster.
  2. On ten servers (six Dell PowerEdge, four Lenovo ThinkSystem) the mean absolute error is below about 7 percent over a five-day experiment.
  3. Dell supplies show FM-PFC behaviour (PFC switching near 70 kHz); Lenovo supplies show AM-PFC behaviour (near 65 kHz).
  4. The method works only with AC power distribution and cannot be used in DC-powered data centres.
  5. Scalability is bounded by one cluster PDU phase: at most 200 servers for a 150 kVA three-phase PDU with 250 W servers.
  6. The sensor prototype is estimated at about 20 dollars: about 7 for the microcontroller, about 3 for analog filters, about 10 for packaging and USB power.
  7. Cost per server is about 2 dollars at 10 servers and about 0.1 dollars at 200 servers, against about 83 dollars for a 24-outlet smart PDU.
  8. The approach can be retrofitted without service interruption and suits colocation, where tenant servers must be observed without intervention.

Using it in design

  • When budgeting server-level metering, compare smart PDU and server management module costs with this method's estimated cost, keeping in mind that it is a research prototype.
  • Do not treat the method as applicable where distribution is DC or where server power supplies use different PFC designs.
  • In colocation design that needs power verification without touching tenant servers, consider it as a second measurement layer alongside existing PDU metering.
  • When planning servers per phase, reflect the paper's 200 servers per phase bound and the risk of overlapping EMI bands in the metering architecture.
  • Add the roughly 7 percent error to the uncertainty budget before feeding such data into PUE and capacity-tracking calculations.

Who should read it

Electrical and operations engineers designing power-monitoring architecture, and researchers who need server-level energy data.

Document contents

  1. Introduction
  2. Preliminaries
  3. Characterization of conducted EMI
  4. EMI-based power monitoring
  5. Performance evaluation
  6. Discussion
  7. Conclusion

Publication details

Authors
Pranjol Sen Gupta; Zahidur Talukder; Tasnim Azad Abir; Phuc Nguyen; Mohammad A. Islam
Publisher
ACM SenSys 2023 / UTA author publication
Year
2023
Document language
English
Source type
Scientific
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Author-hosted institutional PDF inspected. First-page permission is personal/classroom and excludes commercial advantage; no commercial full-text redistribution permission established.

Citation

Pranjol Sen Gupta; Zahidur Talukder; Tasnim Azad Abir; Phuc Nguyen; Mohammad A. Islam (2023). Enabling Low-Cost Server Level Power Monitoring in Data Centers Using Conducted EMI. ACM SenSys 2023 / UTA author publication. https://doi.org/10.1145/3625687.3625801

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.