Energy monitoring in an IIoT world: Applications, concepts, and integration

Phoenix Contact · Clinton Hommel

A May 2020 Phoenix Contact white paper on the benefits of energy monitoring through reliability, accountability and efficiency (RAE), IIoT architecture, interpreting measured parameters and applications including a data-centre HVAC example.

On this page

Overview

The white paper argues that treating energy monitoring only as a consumption-reduction tool leaves opportunities on the table, and groups the benefits as RAE: reliability, accountability and efficiency. On reliability, energy signatures and power quality are used for just-in-time maintenance (JITm): energy use, utilization and quality are compared with a historical baseline and anomalies are investigated before failure. Logs are also valuable for root-cause analysis of sudden failures.

The accountability section explains that energy logs kept independently of utility metering let facility managers verify billed quantities, time of day and rate data and document the quality of service delivered; these logs help in utility failures or billing disputes. The efficiency section goes beyond swapping in efficient equipment to optimisation: wasteful machine cycles, equipment faults causing excess consumption and parasitic loads.

The IIoT section defines three layers: measurement and sensors, communications and connectivity, and analytics and user interfaces. Cloud services work through internet-based interfaces such as HTML5, REST API and MQTT. Section 3 covers interpreting basic parameters such as voltage, current and power, including conditions such as voltage sags and swells and poor power factor. Among the real applications, the third example is predictive maintenance of data-centre HVAC equipment: energy meters embedded in control cabinets send data over Ethernet, and a separate cellular route independent of the data-centre network is used for remote service.

The last section covers the investment decision: compare failure frequency and downtime cost with the cost of the monitoring device. Voltage/phase monitoring relays and basic current transducers almost always pay for themselves on the first outage prevented; advanced platforms with energy meters, power quality meters and analytics can cost well over 10,000 dollars and are not right for every application. The document is a vendor white paper with a general industrial view, not a data-centre-specific design guide.

Key points

  1. RAE: reliability, accountability, efficiency; the most important benefit is uptime and reliability, not energy saving.
  2. Just-in-time maintenance (JITm) compares energy use and quality with a historical baseline and flags anomalies before failure.
  3. Energy logs independent of the utility verify billed quantities, time of day and rate data, and service quality.
  4. IIoT has three layers: sensors and measurement, communications and connectivity, analytics and interface; cloud interfaces use HTML5, REST API and MQTT.
  5. Every machine has a unique energy signature; a change signals a maintenance need.
  6. In the data-centre HVAC example, embedded meter data goes over Ethernet and a separate cellular link serves remote service.
  7. Low-end monitoring (voltage/phase relay, current transducer) almost always pays back on the first outage prevented.
  8. Advanced monitoring platforms can exceed 10,000 dollars; investment scales with failure frequency and downtime cost.

Using it in design

  • Include energy signature and power quality monitoring of critical power and cooling equipment in the predictive maintenance plan.
  • Add metering points independent of the utility to create evidence records for billing and service quality disputes.
  • Design the remote service route (cellular) separate from the data-centre network; this affects BMS and security architecture.
  • Scale monitoring investment against failure frequency and downtime cost, from simple relays to a power quality platform.
  • State measurement protocols (Ethernet, MQTT, REST) in the BMS and DCIM integration specification.

Who should read it

Electrical and operations engineers planning energy monitoring and predictive maintenance architecture, and BMS/DCIM integrators.

Document contents

  1. Introduction
  2. Section 1: Three ways to leverage energy data
  3. Section 2: How is IIoT impacting energy monitoring (and vice versa)?
  4. Section 3: What's flowing through your wires, and how can it help you?
  5. Section 4: Real-world applications of energy meters
  6. Section 5: Is energy monitoring the right investment for me?
  7. Conclusions

Publication details

Authors
Clinton Hommel
Publisher
Phoenix Contact
Year
2020
Document number
U003050A.05.20
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Official public manufacturer source inspected. No redistribution permission established. Metadata and original brief summaries only; local files are research evidence, not a redistribution package.

Citation

Clinton Hommel (2020). Energy monitoring in an IIoT world: Applications, concepts, and integration. Phoenix Contact. U003050A.05.20. https://assets.phoenixcontact.com/file/d12450a6-c9d7-4546-977e-9e8828a31649/media/original?Energy_monitoring_in_an_IIoT_World_Whitepaper_Final.pdf=

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.