Technical guideFree to read2025

Protect Plus M600 Advanced: Technical Specifications (05/2025 V1)

Original title Protect Plus M600 Advanced: technical specifications

AEG Power Solutions

A two-page technical specification of the AEG Protect Plus M600 modular three-phase UPS family, scalable from 30 to 900 kVA with hot-swappable 30 kVA power modules.

On this page

Overview

The document presents the M600 Advanced version as a transformerless, double-conversion (VFI-SS-11), modular and lithium-ion compatible UPS. The system scales from 30 kVA to 900 kVA with 30 kVA hot-swappable power modules. Output power factor is 1 (1 kVA = 1 kW); input power factor is above 0.99 and input THDi below 3%, and these values hold at low load. AC/AC efficiency reaches 95% in double conversion and up to 99% in ECO mode, and the efficiency curve is flat from 35% of load. Typical applications are data centres, transportation, retail and light industry.

The technical table gives three frames: 180 kVA (up to 6 power modules), 300 kVA (up to 10 modules) and 600 kVA (up to 20 modules). The 180 and 300 kVA frames can be paralleled up to 3 frames; parallel operation is not supported on the 600 kVA frame. Dimensions are 600 x 1100 x 1600 mm (165 kg), 600 x 1100 x 2000 mm (220 kg) and 2000 x 1050 x 2000 mm (660 kg) respectively, with IP20 protection. The power module is 460 x 790 x 134 mm, 34 kg and 30 kVA; the charging module is the same size and weight and gives 50 A at 480 VDC (adjustable 1-50 A).

The mains input is 3 phase + N + G, 380/400/415 V, with a voltage range of 304-478 V at full load and 228-304 V at reduced load, and 50/60 Hz frequency (range 40-70 Hz). Output is 380/400/415 V with voltage THD below 1% at linear load and below 5.5% at non-linear load (IEC EN 62040-3). Overload through the inverter line is 110% for 60 minutes, 125% for 10 minutes, 150% for 1 minute and over 150% for 200 ms. Nominal battery voltage is 480 VDC (plus or minus 240), the default number of series batteries is 40 (settable 32-44) and temperature compensation is minus 3.0 mV per cell per degree C.

Operating temperature is 0-40 degrees C, storage minus 40 to 70 degrees C, relative humidity 0-95% non-condensing, and noise at 1 m is below 65 dB at full load and 62 dB at 45% load. Communication is RS232, RS485, dry contacts and USB, with SNMP and an expansion dry-contact card optional. Standards are IEC EN 62040-1, -2 and -3. The document states that technical data constitute no binding guarantee; frame and module limits should be read separately from parallel system capacity.

Key points

  1. Power range 30-900 kVA; 30 kVA hot-swappable power modules; double conversion VFI-SS-11; transformerless.
  2. Output power factor 1 (kVA = kW); input power factor >0.99, input THDi <3%.
  3. Frames: 180 kVA (up to 6 modules), 300 kVA (10 modules), 600 kVA (20 modules); 180 and 300 kVA frames parallel up to 3 frames, 600 kVA frame no parallel.
  4. Efficiency: 95% in double conversion and battery mode, up to 99% in ECO mode; flat curve from 35% of load.
  5. Overload (inverter line): 110% 60 min, 125% 10 min, 150% 1 min, >150% 200 ms.
  6. Input 380/400/415 V; voltage range 304-478 V (full load), 228-304 V (reduced load); frequency range 40-70 Hz.
  7. Battery line 480 VDC (plus or minus 240), 40 blocks default (32-44 settable); charging module 50 A at 480 VDC (1-50 A adjustable).
  8. Size and weight: 180 kVA 600 x 1100 x 1600 mm / 165 kg; 300 kVA 600 x 1100 x 2000 mm / 220 kg; 600 kVA 2000 x 1050 x 2000 mm / 660 kg; module 460 x 790 x 134 mm / 34 kg.
  9. Operating temperature 0-40 degrees C, humidity 0-95% non-condensing, noise <65 dB (full load) and <62 dB (45% load); IP20.

Using it in design

  • Read frame rating and maximum module count separately from parallel system capacity: the 180 kVA frame is limited to 6 modules and the 300 kVA frame to 10, and both can be paralleled up to 3 frames.
  • For N+1 module redundancy, choose one more installed module than the load needs and check that the frame's maximum module count is not exceeded.
  • For floor loading and layout, include frame weight (165, 220, 660 kg) and the separate charging module weight; note in the capacity growth plan that the 600 kVA frame cannot be paralleled.
  • Size the battery system at 480 VDC nominal with 40 blocks by default; set charge current within 1-50 A and weigh lithium-ion compatibility in battery selection.
  • 99% efficiency in ECO mode means a different protection class from double conversion; if ECO mode is used, verify load sensitivity separately.

Who should read it

Electrical engineers selecting and sizing data centre UPS systems and teams preparing a product catalogue.

Document contents

  1. Features and benefits
  2. Typical applications
  3. Specifications: M600 frame, power module, charging module
  4. Mains input line (rectifier)
  5. Output line (inverter)
  6. Efficiency
  7. Battery line
  8. User interface and communications
  9. Environment
  10. Standards and certifications

Publication details

Authors
AEG Power Solutions
Publisher
AEG Power Solutions
Year
2025
Document number
05/2025 V1
Document language
Unverified
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

AEG Power Solutions (2025). Protect Plus M600 Advanced: technical specifications. AEG Power Solutions. 05/2025 V1. https://www.aegps.com/en/wp-content/uploads/2023/07/AEGPS_ProtectPlus_M600_Advanced_EN.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.