Protect Plus S300 Technical Data
AEG Power Solutions
This 10-page technical data document from AEG Power Solutions (no. 8000066304 TD, dated 17 April 2018) specifies the Protect Plus S300 three-phase UPS series in eleven ratings from 10 to 200 kVA. The units are transformerless double-conversion, class VFI SS 111; AC/AC efficiency at full load in double conversion ranges from 93.0% to 95.1%, and reaches 98% in ECO mode.
On this page
Overview
The document is the official technical data sheet prepared by the R&D department of AEG Power Solutions in Warstein-Belecke, and it presents the Protect Plus S300 series in three tables: 10, 15, 20 and 30 kVA; 40, 60 and 80 kVA; and 100, 120, 160 and 200 kVA. Each table follows the same headings: operating modes, rectifier, bypass line, battery line, inverter, overall data and communication. All ratings are class VFI SS 111 to IEC EN 62040-3, work on TT, TN-S, TN-C and IT systems, and support a VFD-class ECO mode.
On the input side an IGBT rectifier is fed at 380/400/415 V (3 phases + N + PE), with an input power factor above 0.99 and a voltage window of ± 20% at full load; between -20% and -40% the power is derated from 100% towards 70%. Input current harmonic distortion is tabulated by load and rating: 2.2% to 4.2% at full load and 5.8% to 11% at 25% load. The bypass line is separate and independent from the mains input, transfers without a break and includes backfeed protection to IEC 62040-1.
The battery line is VRLA and runs at a nominal 720 V DC (360 + 360) with plus, neutral and minus terminals: two strings of 30 blocks of 12 V each, that is 2 × 180 cells, settable up to 2 × 32 blocks. Float voltage is 2.25 V per cell at 25 °C and end-of-discharge voltage is 1.67 V per cell. The inverter is a transformerless IGBT bridge; the output power factor is 0.9 from 10 to 80 kVA and 1 from 100 to 200 kVA. Output voltage stability is ± 0.5% on balanced load and the crest factor is 3:1.
Efficiency values are given with their measurement points. For the ratings from 10 to 80 kVA, double-conversion AC/AC efficiency is listed separately at 25%, 50%, 75% and 100% load; for the 80 kVA model the values are 91.9%, 94.0%, 94.5% and 94.8% respectively. The 100 to 200 kVA ratings carry a single value each, from above 94.0% to above 95.1%. In parallel operation up to 7+1 units can be connected for redundancy and up to 8 units for power increase, and several UPS units can share a common battery string. The document dates from 2018.
Key points
- Eleven ratings: 10, 15, 20, 30, 40, 60, 80, 100, 120, 160 and 200 kVA; all VFI SS 111, transformerless double conversion.
- Output power factor is 0.9 from 10 to 80 kVA and 1 from 100 to 200 kVA (up to 40 °C).
- Double-conversion AC/AC efficiency at full load: 93.0% for 10 to 20 kVA; 93.3% for 30 and 40 kVA; 94.8% for 60 and 80 kVA; above 94.0% for 100 kVA, 94.9% for 120 kVA, 95.0% for 160 kVA and 95.1% for 200 kVA. 98% in ECO mode.
- Part-load efficiency (10 to 20 kVA): 89.7% at 25% load, 92.2% at 50% load, 93.3% at 75% load.
- Battery: VRLA, 720 V DC (360 + 360), 2 × 30 blocks (2 × 180 cells), settable up to 2 × 32 blocks; float 2.25 V per cell, end of discharge 1.67 V per cell.
- Inverter overload: up to 105% continuously, then transfer to bypass after 1 hour at 110%, 10 minutes at 125% and 1 minute at 150%. Bypass: 150% continuously, 180% for 1 minute, 1000% for 100 ms.
- Input THDi at full load is 2.2% to 4.2%; input power factor is above 0.99; input frequency window is 40 to 70 Hz.
- Dimensions (W × D × H) and weight without batteries: 10 to 30 kVA 400 × 815 × 1040 mm, 87 to 100 kg; 40 to 80 kVA 515 × 855 × 1440 mm, 173 to 209 kg; the 100 to 200 kVA table gives 475 × 890 × 1440 mm, 210 to 270 kg.
- Environment: 0 to 40 °C operating, 0 to 95% relative humidity (non-condensing), 1000 m without derating and up to 3000 m with derating; degree of protection IP20.
- Parallel operation: up to 7+1 units for redundancy and up to 8 units for power increase; a common battery string is supported.
Using it in design
- Use the correct power factor for the rating in active-power calculations: the 80 kVA model delivers 72 kW and the 100 kVA model 100 kW.
- Calculate losses and cooling load with the efficiency at the real load ratio; in N+1 or 2N arrangements the units mostly run at 25 to 50% load, where the small ratings fall to 89.7% to 92.2%.
- Design the battery cabinet for 720 V DC centre-tapped strings (plus, neutral, minus) of 2 × 30 blocks, with three-conductor battery protection and cabling.
- If ECO mode is to be used, state in the design report that the 98% efficiency is obtained in VFD class and that the load stays exposed to mains quality.
- Plan separate supplies and protection for the rectifier input and the bypass, and verify downstream selectivity against the bypass short-time capability of 1000% for 100 ms.
- Apply derating to IEC 62040-3 at sites above 1000 m, and leave a plinth or raised-floor void for bottom cable entry.
Who should read it
Electrical designers selecting three-phase UPS units from 10 to 200 kVA, engineers writing specifications, and teams sizing batteries and cooling.
Document contents
- Operating Modes
- Rectifier
- Bypass Line
- Battery Line
- Inverter
- Overall
- Communication features
Publication details
- Authors
- AEG Power Solutions
- Publisher
- AEG Power Solutions
- Year
- 2018
- Document number
- 800006 6304 TD en
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
AEG Power Solutions (2018). Protect Plus S300 Technical Data. AEG Power Solutions. 800006 6304 TD en. https://www.upss.ro/web/b2b/images/uploaded/products/PDF/AEG_PROTECT_PLUS_S300_EN_2.PDF
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.