Protect Plus S300 Technical Data

AEG Power Solutions

This 10-page technical data document from AEG Power Solutions (no. 8000066304 TD, dated 17 April 2018) specifies the Protect Plus S300 three-phase UPS series in eleven ratings from 10 to 200 kVA. The units are transformerless double-conversion, class VFI SS 111; AC/AC efficiency at full load in double conversion ranges from 93.0% to 95.1%, and reaches 98% in ECO mode.

On this page

Overview

The document is the official technical data sheet prepared by the R&D department of AEG Power Solutions in Warstein-Belecke, and it presents the Protect Plus S300 series in three tables: 10, 15, 20 and 30 kVA; 40, 60 and 80 kVA; and 100, 120, 160 and 200 kVA. Each table follows the same headings: operating modes, rectifier, bypass line, battery line, inverter, overall data and communication. All ratings are class VFI SS 111 to IEC EN 62040-3, work on TT, TN-S, TN-C and IT systems, and support a VFD-class ECO mode.

On the input side an IGBT rectifier is fed at 380/400/415 V (3 phases + N + PE), with an input power factor above 0.99 and a voltage window of ± 20% at full load; between -20% and -40% the power is derated from 100% towards 70%. Input current harmonic distortion is tabulated by load and rating: 2.2% to 4.2% at full load and 5.8% to 11% at 25% load. The bypass line is separate and independent from the mains input, transfers without a break and includes backfeed protection to IEC 62040-1.

The battery line is VRLA and runs at a nominal 720 V DC (360 + 360) with plus, neutral and minus terminals: two strings of 30 blocks of 12 V each, that is 2 × 180 cells, settable up to 2 × 32 blocks. Float voltage is 2.25 V per cell at 25 °C and end-of-discharge voltage is 1.67 V per cell. The inverter is a transformerless IGBT bridge; the output power factor is 0.9 from 10 to 80 kVA and 1 from 100 to 200 kVA. Output voltage stability is ± 0.5% on balanced load and the crest factor is 3:1.

Efficiency values are given with their measurement points. For the ratings from 10 to 80 kVA, double-conversion AC/AC efficiency is listed separately at 25%, 50%, 75% and 100% load; for the 80 kVA model the values are 91.9%, 94.0%, 94.5% and 94.8% respectively. The 100 to 200 kVA ratings carry a single value each, from above 94.0% to above 95.1%. In parallel operation up to 7+1 units can be connected for redundancy and up to 8 units for power increase, and several UPS units can share a common battery string. The document dates from 2018.

Key points

  1. Eleven ratings: 10, 15, 20, 30, 40, 60, 80, 100, 120, 160 and 200 kVA; all VFI SS 111, transformerless double conversion.
  2. Output power factor is 0.9 from 10 to 80 kVA and 1 from 100 to 200 kVA (up to 40 °C).
  3. Double-conversion AC/AC efficiency at full load: 93.0% for 10 to 20 kVA; 93.3% for 30 and 40 kVA; 94.8% for 60 and 80 kVA; above 94.0% for 100 kVA, 94.9% for 120 kVA, 95.0% for 160 kVA and 95.1% for 200 kVA. 98% in ECO mode.
  4. Part-load efficiency (10 to 20 kVA): 89.7% at 25% load, 92.2% at 50% load, 93.3% at 75% load.
  5. Battery: VRLA, 720 V DC (360 + 360), 2 × 30 blocks (2 × 180 cells), settable up to 2 × 32 blocks; float 2.25 V per cell, end of discharge 1.67 V per cell.
  6. Inverter overload: up to 105% continuously, then transfer to bypass after 1 hour at 110%, 10 minutes at 125% and 1 minute at 150%. Bypass: 150% continuously, 180% for 1 minute, 1000% for 100 ms.
  7. Input THDi at full load is 2.2% to 4.2%; input power factor is above 0.99; input frequency window is 40 to 70 Hz.
  8. Dimensions (W × D × H) and weight without batteries: 10 to 30 kVA 400 × 815 × 1040 mm, 87 to 100 kg; 40 to 80 kVA 515 × 855 × 1440 mm, 173 to 209 kg; the 100 to 200 kVA table gives 475 × 890 × 1440 mm, 210 to 270 kg.
  9. Environment: 0 to 40 °C operating, 0 to 95% relative humidity (non-condensing), 1000 m without derating and up to 3000 m with derating; degree of protection IP20.
  10. Parallel operation: up to 7+1 units for redundancy and up to 8 units for power increase; a common battery string is supported.

Using it in design

  • Use the correct power factor for the rating in active-power calculations: the 80 kVA model delivers 72 kW and the 100 kVA model 100 kW.
  • Calculate losses and cooling load with the efficiency at the real load ratio; in N+1 or 2N arrangements the units mostly run at 25 to 50% load, where the small ratings fall to 89.7% to 92.2%.
  • Design the battery cabinet for 720 V DC centre-tapped strings (plus, neutral, minus) of 2 × 30 blocks, with three-conductor battery protection and cabling.
  • If ECO mode is to be used, state in the design report that the 98% efficiency is obtained in VFD class and that the load stays exposed to mains quality.
  • Plan separate supplies and protection for the rectifier input and the bypass, and verify downstream selectivity against the bypass short-time capability of 1000% for 100 ms.
  • Apply derating to IEC 62040-3 at sites above 1000 m, and leave a plinth or raised-floor void for bottom cable entry.

Who should read it

Electrical designers selecting three-phase UPS units from 10 to 200 kVA, engineers writing specifications, and teams sizing batteries and cooling.

Document contents

  1. Operating Modes
  2. Rectifier
  3. Bypass Line
  4. Battery Line
  5. Inverter
  6. Overall
  7. Communication features

Publication details

Authors
AEG Power Solutions
Publisher
AEG Power Solutions
Year
2018
Document number
800006 6304 TD en
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

AEG Power Solutions (2018). Protect Plus S300 Technical Data. AEG Power Solutions. 800006 6304 TD en. https://www.upss.ro/web/b2b/images/uploaded/products/PDF/AEG_PROTECT_PLUS_S300_EN_2.PDF

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.